Current Input:
I.
CT secondary
1 / 5 Amp. (Selectable)
II.
Nominal Burden at In
(without tripping condition)
< 0.20 VA at rated current (In)
III.
Thermal Withstand Capacity
40 x rated current (In) for 3sec
2 x rated current (In) continuous for Phase and EF CT
IV.
Measurement Linearity
Range for Non – Offset AC
Current
Linear up to 40 In
Auxiliary Supply Input:
I.
Nominal operating range
24 – 230V AC/ DC
II.
Voltage operating range
80% of lower nominal range and 120% of upper nominal
range (For DC Supply)
80% of lower nominal range and 110% of upper nominal
range (For AC Supply)
III.
Nominal Burden on 24 –
230V Auxiliary Power
Supply
24
–
230 VAC
< 12 VA
24
–
230 VDC
< 5 W
IV.
Tolerable AC ripple
Up to 15% of highest dc supply, As per IEC 60255-26:
2013
V.
Relay power up time
< 2.5 Sec
Opto Isolated Input:
I.
Opto Isolated input operating
Range
24 – 230 VDC
II.
Threshold Voltage for DC
18V +/- 3volts
Maximum operating voltage
range
250 VDC
III.
Drop out
Within 85% of threshold voltage value
IV.
VA Burden of Opto Isolated
Status Input
For each status < 1.5 Watt / VA
V.
Filtering Time
< 40ms
VI.
Logic input recognition time
: For all Status filtering time + 5ms ± 5 ms
Summary of Contents for ADR141A
Page 10: ...Page intentionally Left Blank...
Page 16: ...Page intentionally Left Blank...
Page 28: ...Page intentionally Left Blank...
Page 43: ...Page intentionally Left Blank...
Page 53: ...Page intentionally Left Blank...
Page 69: ...Page intentionally Left Blank...
Page 73: ...Page intentionally Left Blank...
Page 80: ...Page intentionally Left Blank...
Page 92: ...Page intentionally Left Blank...
Page 122: ...Page intentionally Left Blank...
Page 136: ...Page intentionally Left Blank...
Page 140: ...ADR141A ADR241A Doc ID ADR241A_IM_01 Ref ID ADR241A IM DR Rev No 02 Page No 140 of 150...
Page 141: ...Page intentionally Left Blank...
Page 151: ......