AC36VHES-1, -3 / AC45VHES-1, -3 / AC54VHES-1, -3 Operations Manual....
13
4
SPECIFICATIONS, cont.
4.2
PHYSICAL SPECIFICATIONS
Parameter
AC36VHES-1, -3
AC45VHES-1, -3
AC54VHES-1, -3
4.2.1 Mechanical
Height
56.13"/142.6cm
56.13"/142.6cm
56.13"/142.6cm
Width, Enclosure
32.66"/83.0cm
32.66"/83.0cm
32.66"/83.0cm
Depth
21.81"/55.4cm
21.81"/55.4cm
21.81"/55.4cm
Weight
836lbs/379kg
836lbs/379kg
840lbs/381kg
4.2.2 Environmental
Ambient Temperature Range
0-50
C non-condensing
Internal Air Exchange Rate
900CFM (ft
3
/min) / 1,530 m
3
/hour
4.2.3 Coolant Requirements
Water Flow Rate
4-10 GPM range (minimum and maximum, respectively)
Coolant Flow Rate
8-16 GPM range (minimum and maximum, respectively)
Water/Coolant Flow Min. Rate
4 + (4 * Percent Coolant)
e.g.
100% coolant mix, 4 + (4 *1.00) = 8 GPM
50% coolant mix, 4 + (4 *0.50) = 6 GPM
Water/Coolant Temperature
4-10°C for full output power capability. See derating chart
on the previous page for operation at other temperatures.
Water/Coolant Pressure
150 psi / 10.3 bar maximum
Pressure Drop at 4GPM
0.4 bar per heat exchanger (two)