AC36VHES-1, -3 / AC45VHES-1, -3 / AC54VHES-1, -3 Operations Manual....
35
6.4
TURN-OFF PROCEDURE
6.4.1 Systems Not Equipped With The Seamless Transfer Option
Transfer power from the converter to the generator. This must be performed in a “break-before-
make” method. That is to say that at no time can the generator(s) and shore power converter be
operated in parallel.
Disable the Auto-Restart feature if enabled.
Press the CONVERTER POWER OFF
(11)
button. The red Converter Power OFF indicator
LED
(11A)
should now be lit. If the SUMMARY DISPLAY is active, it should indicate
CONVERTER: OFFLINE. Power has now been removed from the output, but the system
remains active. The system is now in the “standby” state.
Next press the SHORE POWER OFF
(10)
button. The red Shore Power indicator LED
(10A)
should now be lit. This will initiate the inverter shutdown. The system will complete the
shutdown process within 10 seconds.
Turn the Disconnect Switch
(14)
to the OFF position. Open the shore power (input) circuit
breaker or switch to the converter.
The converter is now shut down.