In case some parameters are not protected, when one tries to have
access at the programming, the display will show all the
parameters not protected and the par. 

“r.P”

 (through which will be

possible to have access to the “protected” parameters.)

5 sec.

Hold for

2 sec.

Hold for

2.5 - RESET PARAMETERS TO DEFAULT VALUE/LEVEL

The instrument allows the reset of the parameters to values
programmed in factory as default.  
To restore to the values of default the parameters set the value 

-48

to “r.P” password request.
Once confirmed the password with the key P the display it shows
"---" for 2 sec. therefore the instrument effects the parameters
reset..

2.6 - KEYBOARD LOCK FUNCTION

On the instrument  it’s possibile to lock completely the keyboard. 
This function is particularly useful when the regulator is reachable
by the users and it’s desired to avoid any modification.
To activate the keyboard lock it’s enough program the par. 

“t.Lo”

to a different value to oF. 
The value program to this parameter it is the time of inactivity of the
keys afterwhich the keyboard will be locked.
Insofar not pressing  any key for the time "t.Lo" the instrument
automatically disable the normal functions of the keys.
When the keyboard is lock, if any of the key is pushed, on the
display will appear  

“Ln” 

to indicate the active lock.

To unlock the keyboard it’s enough to contemporarily push  key P
and UP and keep them pushed for 5 sec., afterwhich the label 

“LF”

will appear on the display and all the keys functions will be availab-
le again .

3 - INFORMATION ON INSTALLATION AND USE

3.1 - PERMITTED USE

The instrument has been projected and
manufactured as a measuring and control device to
be used according to EN60730-1 for the altitudes
operation until 2000 ms.

 

The use of the instrument

for applications not expressly permitted by the above mentioned
rule must adopt all the necessary protective measures. The
instrument CANNOT be used in dangerous environments
(flammable or explosive) without adequate protection. 
The instrument used with NTC 103AT11 probe (identifiable by the
printed code “103AT-11” visible on the sensor part) is compliant
with standard EN 13485 ("Thermometers for measuring the air and
product temperature for the transport,storage and distribution of
chilled, frozen, deep-frozen/quick-frozen food and ice cream”) with
the following classification: [EN13485 air, S, A, 2,- 50°C +90°C]
Remember that the end user must periodically checks and verify
the thermometers in compliance with standard EN 13486.
The installer must ensure that EMC rules are respected, also after
the instrument installation, if necessary using proper filters.

Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, thing or animals, please
remember that the plant has to be equipped with additional devices
which will guarantee safety.

3.2 - MECHANICAL MOUNTING

The instrument, in case 78 x 35 mm, is designed for flush-in panel
mounting. Make a hole 71 x 29 mm and insert the instrument, fixing
it with the provided special brackets. We recommend that the
gasket is mounted in order to obtain the front protection degree as
declared. Avoid placing the instrument in environments with very
high humidity levels or dirt that may create condensation or
introduction of conductive substances into the instrument. Ensure
adequate ventilation to the instrument and avoid installation in
containers that house devices which may overheat or which may
cause the instrument to function at a higher temperature than the
one permitted and declared. Connect the instrument as far away as
possible from sources of electromagnetic disturbances such as
motors, power relays, relays, solenoid valves, etc.

3.3 - ELECTRICAL CONNECTION

Carry out the electrical wiring by connecting only one wire to each
terminal, according to the following diagram, checking that the
power supply is the same as that indicated on the instrument and
that the load current absorption is no higher than the maximum
electricity current permitted. As the instrument is built-in equipment
with permanent connection inside housing, it is not equipped with
either switches or internal devices to protect against overload of
current: the installation will include an overload protection and a
two-phase circuit-breaker, placed as near as possible to the
instrument, and located in a position that can easily be reached by
the user and marked as instrument disconnecting device which
interrupts the power supply to the equipment. It is also
recommended that the supply of all the electrical circuits connected
to the instrument must be protect properly, using devices (ex.
fuses) proportionate to the circulating currents. It is strongly
recommended that cables with proper insulation, according to the
working voltages and  temperatures, be used. Furthermore, the
input cable of the probe has to be kept separate from line voltage
wiring. If the input cable of the probe is screened, it has to be
connected to the ground with only one side. Whether the
instrument is F o G (12 / 24 V) supply version it’s recommended to
use an external transformer TCTR, or with equivalent features
(Class II insulation) , and to use only one transformer for each
instrument because there is no insulation between supply and
input. We recommend that a check should be made that the
parameters are those desired and that the application functions
correctly before connecting the outputs to the actuators so as to
avoid malfunctioning that may cause irregularities in the plant that
could cause damage to people, things or animals.

3.4 - ELECTRICAL WIRING DIAGRAM

NO

NO

Z31

SUPPLY

1

3

2

4

SPST-NO

SPDT

PROBE

11

INPUT

NC

C

8

6

5

OUT

7

9 10

C

BUZZER

INTERNAL

12

5 FLA

30 LRA

12 A Res.

(12 A MAX for extr. conn. model)

EN

16 (9) A

61810

Out:

10 (4) A

60730

EN

UL

4 - FUNCTIONS

4.1 - ON / STAND-BY

 

FUNCTION

The instrument, once powered up, can assume 2 different
conditions:

ASCON TECNOLOGIC - Z31- 

 

-OPERATING INSTRUCTIONS- Vr. 02 - 03/12 -  ISTR-MZ31-ENG02 -  PAG. 3

Advanced Thermoelectric       toll-free 1-866-665-5434      (603) 888-2467      [email protected]

Summary of Contents for Z31

Page 1: ...TALLATION AND USE 3 KEYBOARD LOCK FUNCTION 2 6 RESET PARAMETERS TO DEFAULT VALUE LEVEL 2 5 CUSTOMIZED MODE PARAMETER PROGRAMMING PARAMETERS PROGRAMMING LEVEL 2 4 PARAMETER PROTECTION USING THE PASSWOR...

Page 2: ...identifies the first parameter Using the UP and DOWN keys the desired parameter can be selected and pressing the P key the display will alternately show the parameter code and its setting that can be...

Page 3: ...nting Make a hole 71 x 29 mm and insert the instrument fixing it with the provided special brackets We recommend that the gasket is mounted in order to obtain the front protection degree as declared A...

Page 4: ...r HC H SP off O N r HC H tim e r d SP Temp r d tim e r HC C O N O N ON ON O N off off off Temp Out Out In the event of probe error it is possible to set the instrument so that that the output continue...

Page 5: ...arm thresholds set in parameters A HA maximum alarm and A LA minimum alarm and the relative differential A Ad Through the parameter A Ay it is possible to set the alarm thresholds A HA and A LA which...

Page 6: ...nt Probes Type i SE 4 i parameters relative to inputs 0 0 LS HS Set Point SP 3 99 9 LS 999 Maximum Set Point S HS 2 50 0 99 9 HS Minimum Set Point S LS 1 S parameters relative to Set Point Note Def Ra...

Page 7: ...t of a faulty instrument either within the period of warranty or further to its expiry please contact our sales department to obtain authorisation for sending the instrument to our company The faulty...

Page 8: ...37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 7 5 INSTRUMENT ORDERING CODE Z31 instrument with mechanical keyboard Z31S instrument with Sensitive Touch keyboard a b c d e f g h ii jj...

Reviews: