38
7. PERFORMANCE DATA
1
st
Step
Interpolation of Indoor DB
Find TC, SC, PI for
(a) Indoor:
25°C DB
, 16°C WB
Outdoor: 35°C DB
(b) Indoor:
25°C DB
, 19°C WB
Outdoor: 35°C DB
(c) Indoor:
25°C DB
, 16°C WB
Outdoor: 40°C DB
(d) Indoor:
25°C DB
, 19°C WB
Outdoor: 40°C DB
2
nd
Step
Interpolation of Indoor WB
Find TC, SC, PI for
(a) Indoor: 25°C DB,
17°C WB
Outdoor: 35°C DB
(b) Indoor: 25°C DB,
17°C WB
Outdoor: 40°C DB
3
rd
Step
Interpolation of Outdoor DB
Find TC, SC, PI for
(a) Indoor: 25°C DB, 17°C WB
Outdoor:
37°C DB
Interpolation
method can be used to get the total capacity, TC and sensible capacity, SC and power input,
PI at those temperatures which are not stated out in the table. Extrapolation method are not allowed to be
used to get the TC, SC and PI.
Example:
Model:
A5RT150BR
Indoor Condition:
25°C DB, 17°C WB
Outdoor Condition:
37°C DB
Fan Speed:
High (5650CFM)
Solution:
Overall
Based on the Performance Table
1. Refer to the Indoor DB column,
- 25°C
is located between 24°C and 27°C for 16˚CWB (Thus, Interpolation need to be applied)
- 25°C
is located between 24°C and 27°C for 19˚CWB (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
- 17°C
is located between 16°CWB and 19°CWB for 25°CDB
(Thus, Interpolation need to be applied)
3. Refer to the Outdoor DB column,
- 37°C
is located between 35°C and 40°C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.
Calculation Steps
Summary of Contents for A5RT 120 BR
Page 22: ...20 Control Module Of Unit A5RT90BR Control Module Of Unit A5RT120BR...
Page 23: ...21 Control Module Of Unit A5RT150BR Control Module Of Unit A5RT180BR...
Page 51: ...49 Model A5RT150BR All dimensions are in mm CENTER OF GRAVITY...
Page 52: ...50 Model A5RT180BR All dimensions are in mm CENTER OF GRAVITY...
Page 53: ...51 Model A5RT90BR 9 WIRING DIAGRAMS...
Page 54: ...52 Model A5RT120BR...
Page 55: ...53 Model A5RT150BR...
Page 56: ...54 Model A5RT180BR...