42
Indoor WB
˚C
Indoor DB
˚C
Outdoor DB,˚C
40
TC (kW)
....
....
........................
39.31
17
25
x
6
y
6
19
16
41.46
35.41
29.99
z
6
13.96
14.13
Total capacity, TC
Sensible capacity, SHC
Interpolation Method:
⇒
19ºC – 16ºC
=
41.46kW – 39.31kW
41.46kW – x
6
kW
19ºC – 17ºC
⇒
x
6
= 40.03kW
(b) Indoor Condition:
25°C DB,
17°C WB
Outdoor Condition:
40°C DB
SHC (kW)
PI (kW)
Interpolation Method:
⇒
19ºC – 16ºC
=
29.99kW – 35.41kW
29.99kW – y
6
kW
19ºC – 17ºC
⇒
y
6
= 33.60kW
Power Input, PI
Interpolation Method:
⇒
19ºC – 16ºC
=
14.13kW – 13.96kW
14.13kW – z
6
kW
19ºC – 17ºC
⇒
z
6
= 14.02kW