43
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition:
25°C DB, 17°C WB
Outdoor Condition:
37°C DB
Indoor WB
˚C
Indoor DB
˚C
Outdoor DB, ˚C
35
TC
(kW)
SHC
(kW)
25
......
42.92
35.61
PI
(kW)
37
40
TC
(kW)
SHC
(kW)
PI
(kW)
12.91
40.03
33.60 14.02
x
y
z
Total capacity, TC
Interpolation Method:
⇒
40º C – 35º C
=
40.03kW – 42.92kW
40.03kW – xkW
40º C – 37ºC
⇒
x = 41.76kW
Sensible capacity, SHC
Interpolation Method:
⇒
40º C – 35º C
=
33.60kW – 35.61kW
40º C – 37º C
⇒
y
= 34.81kW
33.60kW – ykW
Power Input, PI
Interpolation Method:
⇒
40º C – 35º C
=
14.02kW – 12.91kW
40º C – 37º C
⇒
z = 13.35kW
14.02kW – zkW
17
TC
(kW)
SHC
(kW)
PI
(kW)