– OPERATING INSTRUCTIONS – MX33HENG00 - PAGE 3

 

At  this  point,  using  the  UP  and  DOWN  keys,  set  the  password 
number programmed and press the P key. 

H o ld  fo r

5  s e c .

1  s e c .

H o ld  fo r

 

If  the  password  is  correct,  the  display  will  show  the  code  that 
identifies  the  first  group  of  parameters  and  it  will  be  possible  to 
program  the  parameters  of  the  appliance  in  the  same  way  as 
described in the previous paragraph. 
Password protection is disabled by setting the “PASS” par. to OFF.

 

 
2.4  -  PROGRAMMING  OF  THE  CUSTOMIZED  PARAMETERS 
AND THE LEVELS OF PARAMETER PROGRAMMING 

From the factory settings of the device, the protection by means of 
password acts on all the parameters. 
If,  after  having  enabled  the  Password  by  means  of  the  “PASS” 
parameter,  it  is  wished  to  make  some  parameters  programmable 
without protection while maintaining protection on the others, follow 
the procedure below. 
Go  to  programming  by  entering  the  Password  and  select  the 
parameter  it  is  wished  to  make  programmable  without  password 
protection. 
Once the parameter has been selected, if the SET LED is flashing, 
it means that the parameter can only be programmed by means of a 
password and is hence “protected”. 
To  modify  the  visibility  of  the  parameter,  press  the  P  key  and, 
keeping it pressed, press the UP key at the same time. 
The  SET  LED  will  change  its  state  to  indicate  the  new  level  of 
accessibility  of  the  parameter  (on  =  not  protected;  flashing  = 
protected by means of password). 
In the event the Password is enabled, and in the case that certain 
parameters  are  “unprotected”  when  the  user  accesses  the 
programming  mode,  all  the  parameters  configured  as  “not 
protected”  will  be  displayed  without  any  division  into  groups,  with 
the 

“r.PAS”

 par. listed last, by means of which it will be possible to 

access the “protected” parameters. 

H old for

5 sec.

H old for

1 sec.

 

NOTE: 

in  the  event  of  losing  the  password,  remove  the  power 

supply from the device, press the P key and reconnect the device to 
the power while keeping the key pressed for approximately 5 sec. 
In this way, access is gained to all the parameters and it will hence 
be possible to check and modify the “PASS” parameter. 
 

2.5 - CONFIGURATION OF THE PARAMETERS WITH “A01”

 

The appliance is equipped with a connector that allows the transfer 
of  the  operating  parameters  to  and  from  the  appliance  through  a 

 

A01

 device, which is fitted with a 5-pole connector. 

The  A01  device  can  be  used  for  the  serial  programming  of 
appliances  that  must  have  the  same  configuration  of  the 
parameters,  or  for  keeping  a  copy  of  the  programming  of  one 
appliance which can be transferred rapidly to another. 
The same device allows connection via the USB port to a PC with 
which,  using  the  appropriate  software  for  configuring  devices, 
“ASCON  TECNOLOGIC  UniversalConf”,  it  is  possible  to  configure 
the operating parameters. 
To  use  the  A01  device,  it  is  possible  to  supply  power  to  just  the 
device or just the appliance.

 

SUPPLY

 

SUPPLY ADAPTER

12 VDC

AC SUPPLY 

 

For further information, refer to the user manual of the A01 device.

 

 

2.6 - KEYPAD LOCK 

The keypad of the appliance may be completely locked.  
This function is useful when the controller is exposed to the public 
or, in any case, it is wished to block any command. 
To  activate  the  keypad  lock,  press  and  hold  the  UP  and  DOWN 
keys at the same time for 5 sec. when the controller is switched on. 
After  the  5  sec.  have  elapsed,  the  display  will  read 

“LOn”

  and  all 

the  functions  of  the  keys  will  result  as  being  blocked,  with  the 
exception of the display of the Set Point.

 

If  any  key  is  pressed  when  the  keypad  is  locked,  the 

“LOn

” 

message is shown again to indicate it is locked.

 

To  unlock  the  keypad,  simply  press  and  hold  the  UP  and  DOWN 
keys  at  the  same  time  for  5  sec.,  after  which  the  display  will  read 

“LOF”

  and  all  the  functions  of  the  keys  will  result  as  being 

operational again.

 

 

3 - WARNINGS FOR INSTALLATION AND USE  

 

3.1 - PERMITTED USE

 

The  appliance  was  designed  as  measuring  and 
regulating  apparatus  in  conformity  with  the 
EN60730-1 standard for operation at an altitude of 
up  to  2000  m.  The  use  of  the  appliance  in 
applications  that  are  not  expressly  envisaged  by 
the  aforementioned  standard  necessitates  all 

adequate means of protection. The appliance MAY NOT be used in 
environments  with  hazardous  atmospheres  (inflammable  or 
explosive)  without  suitable  protection.

 

Note  that  the  installer  must 

ensure that the regulations relating to electromagnetic compatibility 
are observed, also after installing the appliance, if necessary using 
special filters. In the event that a fault or malfunction of the device 
should  create  hazardous  or  damaging  situations  for  persons, 
property  or  animals,  note  that  the  system  must  be  fitted  with 
additional electromechanical devices designed to guarantee safety. 

 
3.2 - MECHANICAL INSTALLATION 

The appliance is housed in a container measuring 78 x 35 mm, and 
is designed for built-in mounting flush with a panel within a casing. 

 

Summary of Contents for X33H

Page 1: ...PARAMETER PROGRAMMING 2 5 CONFIGURATION OF THE PARAMETERS WITH A01 2 6 KEYPAD LOCK 3 WARNINGS FOR INSTALLATION AND USE 3 1 PERMITTED USE 3 2 MECHANICAL INSTALLATION 3 3 ELECTRICAL CONNECTIONS 3 4 ELE...

Page 2: ...n the value set will be memorized and the display will then move on to read SP h humidity Set point and the value set for it To modify this value use the UP and DOWN keys The SP h Set point can be set...

Page 3: ...ted with a 5 pole connector The A01 device can be used for the serial programming of appliances that must have the same configuration of the parameters or for keeping a copy of the programming of one...

Page 4: ...upply the appliance can be in one of 2 different states ON means that the controller actuates the control functions STAND BY means that the controller does not actuate any function and the display is...

Page 5: ...sabled The buF par allows the buzzer to be enabled YES or disabled no 4 4 TEMPERATURE REGULATOR All the parameters regarding the regulation of the temperature are contained in the rEG group The regula...

Page 6: ...he appliance is switched on for the time set in the od par During the phase of delay upon switching on the display will show the indication od alternating with the normal programmed messages The delay...

Page 7: ...hether the recycling fans must be switched on FdF On or whether they should switch off during defrosting FdF OFF In this last case it is possible to delay the re starting of the fans even after the en...

Page 8: ...he alarm conditions of the appliance are Errors in Sensors E1 E1 E2 E2 E3 E3 E4 E4 Temperature alarms HI 1 LO 1 HI 2 LO 2 HI 3 LO 3 HI 4 LO 4 External alarm AL Door open alarm AdoP 4 13 1 TEMPERATURE...

Page 9: ...upon the closure of the input and after the did time the alarm is activated and the appliance alternately shows on the upper display AL and the variable established in the diSU par 2 Signalling of an...

Page 10: ...cle the cycle is interrupted and the appliance returns to the normal regulation state STOP 7 START PAUSE STOP mode When the command is given by key the cycle is started START If the key is pressed for...

Page 11: ...the event that it is envisaged that the operator cannot be present at the end of this phase and thus cannot extract the product it is possible to program a third maintenance phase For this third phase...

Page 12: ...temp Pr3 Measurement of OFF Pr1 Pr2 Pr3 Pr4 SPt SPh Pr4 Pr3 sensor auxiliary temp Pr4 Measurement of Pr4 sensor humidity SPt Active temperature Set Point SPh Active humidity Set Point rEG group param...

Page 13: ...shold for high Pr3 temperature OFF 58 0 302 0 C F OFF 62 LAL3 Alarm threshold for low Pr3 temperature OFF 58 0 302 0 C F OFF 63 dAL3 Differential of Pr3 temperature alarms 0 0 30 0 C F 2 0 64 ALd3 Del...

Page 14: ...t AL ALL On End HEAt 86 Out3 Configuration of operation of OUT3 output see Out1 OFF CooL HEAt rh drh dEF FAnr FAnE drhE LIGH AuS ALt rH 87 Out4 Configuration of operation of OUT4 output see Out1 OFF C...

Page 15: ...encountered within 12 months of delivery The guarantee is limited to the repair or replacement of the product Any opening of the housing tampering with the appliance or non compliant use and installa...

Page 16: ...measurement sampling 130 ms Display 4 digit 1 Red and 1 Amber yellow h 7 mm Class and structure of the software Class A Conformity Directives 2004 108 CE EN55022 class B EN61000 4 2 8KV air 4KV cont E...