Ascon tecnologic X33H Operating Instructions Manual Download Page 4

Ascon Tecnologic Srl - X33H

 

– OPERATING INSTRUCTIONS – MX33HENG00 - PAGE 4

 

Make a cavity measuring 71 x 29 mm and insert the appliance into 
it, holding it in place with the special bracket provided. It is advised 
that the special gasket is fitted, so as to obtain the degree of frontal 
protection  declared.  Avoid  positioning  the  internal  part  of  the 
appliance  in  places  subject  to  levels  of  humidity  or  dirt  that  could 
cause  condensation  or  allow  conductive  objects  or  substances  to 
enter  the  appliance.  Ensure  that  the  appliance  has  adequate 
ventilation  and  avoid  installation  in  housings  where  there  are 
devices  located  that  could  cause  the  appliance  to  function  outside 
the declared temperature limits. Install the appliance as far away as 
possible  from  sources  that  could  generate  electromagnetic 
interference  such  as  engines,  solenoids,  relay  switches, 
electrovalves etc. 

 
3.3 - ELECTRICAL CONNECTIONS

 

Make the connections attaching only one conductor to each clamp 
and following the wiring diagram supplied, checking that the power 
supply voltage is the same as that indicated on the appliance, and 
that the absorption of the actuators connected to the appliance does 
not exceed the maximum current allowed. Given that it is designed 
to  be  permanently  connected  within  an  apparatus,  the  appliance 
does  not  have  a  power  switch,  nor  is  it  fitted  with  internal  power 
surge protection. The manufacturer hence advises the installation of 
a  surge  protection  device  and  a  double-pole  switch/disconnector, 
labelled  as  a  disconnection  device,  which  interrupts  the  power 
supply of the apparatus. This switch must be positioned as close as 
possible  to the appliance in  a  place  that  is  easily  accessed  by  the 
user. In addition, it is recommended that the power supply of all the 
circuits  connected  to  the  appliance  with  devices  (e.g.  fuses)  be 
adequately  protected  from  surrounding  currents.  Use  wires  with 
insulation  appropriate  for  the  voltages,  the  temperatures  and  the 
working conditions, and ensure that the wires connected to the input 
sensors  are  kept  away  from  power  supply  cables  and  other  live 
wires to avoid electromagnetic interference.  
If  some  of  the  cables used  in  the  wiring  are shielded, it  is advised 
that  they  be  earthed  on  one  side  only.  For  the  version  of  the 
appliance  with  12  V  power  supply,  the  use  of  the  special  TCTR 
transformer  is  recommended,  or  of  a  transformer  with  equivalent 
specifications, and it is advised that a separate transformer be used 
for  each  apparatus,  as  there  is  no  insulation  between  the  power 
supply  and  the  input.  Finally, the  user  is  advised  to  check that  the 
parameters  set  are  the  desired  ones,  and  that  the  application 
functions  correctly  before  connecting  the  outputs  to  the  actuators, 
so as to avoid anomalies in the system that could cause damage to 
persons, property or animals.

 

 
3.4 - ELECTRICAL WIRING DIAGRAM 

1 9

B U Z Z E R

IN T E R N A L

O U T 3

7

X 3 3 H

O U T 2

O U T 1

1 6

1 4

1 3

C

1 5

N O

C

N O

1 7

N C

1 8

P r2

2

1

3

P r1

4

5

6

IN P U T S

O U T 4

2 2

2 1

2 0

2 4

2 3

1 0

8

9

1 2

1 1

O u t1 : 1 6 A -A C 1 (6 A -A C 3 )/2 5 0  V A C ;1 H P  2 5 0 V A C ,1 /2  H P  1 2 5 V A C
O u t2 : 8 A -A C 1 (3 A -A C 3 )/2 5 0 V A C ;1 /2  H P  2 5 0 V A C ,1 /3  H P  1 2 5 V A C  

L in k  T L

-

+

S

N O

C

N O

C

O u t3 ,4 : 5 A -A C 1 (2 A -A C 3 )/2 5 0 V A C ;1 /8 H P  2 5 0 V A C ,1 /1 0 H P  1 2 5 V A C

S U P P L Y

T L L  (R S , K e y )

d i1

P r3

(2  w ire s )

4 ..2 0  m A

P A S S IV E

g e n .

e x t.

A C T IV E

0 /4 ..2 0  m A

-

+

+

+

4 ..2 0  m A

A C T IV E

-

1 2  V D C

+

(2 0  m A  M A X )

P r4

d i2

d i3

 

 
 

4 - OPERATION

 

 

4.1 - ON / STAND-BY FUNCTION

 

Once connected to the power supply, the appliance can be in one of 
2 different states: 
- ON: means that the controller actuates the control functions. 
-  STAND-BY:  means  that  the  controller  does  not  actuate  any 
function, and the display is switched off except for the SET LED. 
In the event of loss of power and its subsequent reinstatement, the 
system  always  returns  to  the state it  was  in before  the  power  was 
cut.

 

The ON/Stand-by command may be selected: 
by pressing the U key for approximately 1 sec. if "USrb" = 4, 
by pressing the UP key for approximately 1 sec. if "Fbu" = 4, 
by pressing the DOWN key for approximately 1 sec. if "Fbd" = 4, 
- through one of the digital inputs if the related “diF” par. = 10 
(See  also  the  par.  relating  to  the  operation  of  the  keys  and  the 
digital inputs) 
 

4.2 - CONFIGURATION  OF  THE INPUTS, MEASUREMENT AND 
DISPLAY

 

All  the  parameters  regarding  measurement  are  contained  in  the 

]

InP”

 group

Using  the 

“SEnt”

  par.,  it  is  possible  to  select  the  type  of 

temperature  sensor  (Pr1,  Pr2,  Pr3)  it  is  wished  to  use,  which  can 
be: PTC KTY81-121 (Ptc) or NTC 103AT-2 (ntc) thermistors. 
Having  selected  the  type  of  temperature  sensor  used,  the 

“Unit”

 

parameter  can  be  used  to  select  the  unit  of  measurement  of  the 
temperature (°C or °F) 
Similarly,  with  the 

“SEnh” 

parameter,  it  is  possible  to  select  the 

type  of  input  (Pr4)  on  the  basis  of  the  humidity  transducer  it  is 
intended  to  use,  which  can  have  a  0..20  mA  (0.20)  or  4..20mA 
(4.20) output. 
As regards measuring humidity, it will be possible to set the 

"SSCh"

  

parameter  with  the  value  that  the  appliance  must  measure  in 
correspondence  with  the  start  of  the  scale  (0/4  mA),  and  the 

"FSCh"

 parameter with the value that the appliance must measure 

in correspondence with the end of the scale (20 mA). 
Using the 

“dP t”

 parameter, it is possible to establish the resolution 

of  the  desired  temperature  (OFF=1°;  On=0.1°),  and  likewise  with 
the 

“dP h”

 par., that of the humidity (OFF=1%; On=0.1%). 

The  appliance  allows  the  calibration  of  the  measurements,  which 
can  be  used  for  recalibrating  the  inputs  according  to  the 
requirements of the application, using the 

“OFS”

 par. (1,2,3,4). 

Using the 

“FiLt” 

par.

 

(for the temperature measurements)

 and the 

“FiLh”

 par.

 

(for the humidity measurement), it is possible to set the 

time  constant  of  the  software  filter  relating  to  the  measurement  of 
the  values  at  the  input  so  as  to  reduce  the  sensitivity  to 
disturbances in the measurement (increasing the time). 
Using  the 

“diSU”

  par.  (for  the  upper  display)  and  the 

“diSL”

  par. 

(for  the  lower  display),  it  is  possible  to  establish  the  normal 
messages of the display, which can show: the measurement of the 
desired sensor (Pr1, Pr2, Pr3, Pr4), the active temperature set point 
(SPt),  the  active  humidity  set  point  (SPh),  or  it  is  possible  to  have 
the numerical display switched off (OFF). 
Independently of how the “diSU and “diSL” parameters are set, it is 
possible  to  display  all  the  variables  measured  in  turn  by  pressing 
and  releasing  the 

U

  key:  the  display  will  show  the  code  that 

identifies the variable (

Pr 1

Pr 2

 etc.) and its value. 

This  display  mode  is  exited  automatically  after  approximately  15 
seconds if the U key is not pressed again. 
Using  the 

“Pr  2”

“Pr  3”

  and 

“Pr  4”

  parameters,  it  is  possible  to 

enable (On) or disable (OFF) the measurement inputs whenever the 
sensors are not connected. 
In  relation  to  the  Pr2  and  Pr3  inputs,  by  setting  the  related 
parameters  =  diG,  it  is  also  possible  to  use  these  inputs  as  digital 
inputs  whose  function  will  be  defined  by  the  “diF2”  and  “diF3” 
parameters present in the “

]

din” group (see digital input par.). 

Lastly,  the  user  is  reminded  that  the  display  relating  to  the  Pr1 
sensor  can  also  be  modified  using  the  display  lock  function  while 
defrosting by means of the “dLo” par. 
 

Summary of Contents for X33H

Page 1: ...PARAMETER PROGRAMMING 2 5 CONFIGURATION OF THE PARAMETERS WITH A01 2 6 KEYPAD LOCK 3 WARNINGS FOR INSTALLATION AND USE 3 1 PERMITTED USE 3 2 MECHANICAL INSTALLATION 3 3 ELECTRICAL CONNECTIONS 3 4 ELE...

Page 2: ...n the value set will be memorized and the display will then move on to read SP h humidity Set point and the value set for it To modify this value use the UP and DOWN keys The SP h Set point can be set...

Page 3: ...ted with a 5 pole connector The A01 device can be used for the serial programming of appliances that must have the same configuration of the parameters or for keeping a copy of the programming of one...

Page 4: ...upply the appliance can be in one of 2 different states ON means that the controller actuates the control functions STAND BY means that the controller does not actuate any function and the display is...

Page 5: ...sabled The buF par allows the buzzer to be enabled YES or disabled no 4 4 TEMPERATURE REGULATOR All the parameters regarding the regulation of the temperature are contained in the rEG group The regula...

Page 6: ...he appliance is switched on for the time set in the od par During the phase of delay upon switching on the display will show the indication od alternating with the normal programmed messages The delay...

Page 7: ...hether the recycling fans must be switched on FdF On or whether they should switch off during defrosting FdF OFF In this last case it is possible to delay the re starting of the fans even after the en...

Page 8: ...he alarm conditions of the appliance are Errors in Sensors E1 E1 E2 E2 E3 E3 E4 E4 Temperature alarms HI 1 LO 1 HI 2 LO 2 HI 3 LO 3 HI 4 LO 4 External alarm AL Door open alarm AdoP 4 13 1 TEMPERATURE...

Page 9: ...upon the closure of the input and after the did time the alarm is activated and the appliance alternately shows on the upper display AL and the variable established in the diSU par 2 Signalling of an...

Page 10: ...cle the cycle is interrupted and the appliance returns to the normal regulation state STOP 7 START PAUSE STOP mode When the command is given by key the cycle is started START If the key is pressed for...

Page 11: ...the event that it is envisaged that the operator cannot be present at the end of this phase and thus cannot extract the product it is possible to program a third maintenance phase For this third phase...

Page 12: ...temp Pr3 Measurement of OFF Pr1 Pr2 Pr3 Pr4 SPt SPh Pr4 Pr3 sensor auxiliary temp Pr4 Measurement of Pr4 sensor humidity SPt Active temperature Set Point SPh Active humidity Set Point rEG group param...

Page 13: ...shold for high Pr3 temperature OFF 58 0 302 0 C F OFF 62 LAL3 Alarm threshold for low Pr3 temperature OFF 58 0 302 0 C F OFF 63 dAL3 Differential of Pr3 temperature alarms 0 0 30 0 C F 2 0 64 ALd3 Del...

Page 14: ...t AL ALL On End HEAt 86 Out3 Configuration of operation of OUT3 output see Out1 OFF CooL HEAt rh drh dEF FAnr FAnE drhE LIGH AuS ALt rH 87 Out4 Configuration of operation of OUT4 output see Out1 OFF C...

Page 15: ...encountered within 12 months of delivery The guarantee is limited to the repair or replacement of the product Any opening of the housing tampering with the appliance or non compliant use and installa...

Page 16: ...measurement sampling 130 ms Display 4 digit 1 Red and 1 Amber yellow h 7 mm Class and structure of the software Class A Conformity Directives 2004 108 CE EN55022 class B EN61000 4 2 8KV air 4KV cont E...