delta
due DY-5121 - User manual
20
Examples:
Modbus register value = 214 (D6 hex), Mask = 240 (F0 hex) -> 1101 (13) will be
viewed on web-page.
Presentation - Defines how a value will be represented on a page. Available
options are:
Show as value
This option will read from the address and present the result at the view-page.
Writeable value
This option reads the value from the address and presents it. There will be a set
button next to the value at the view-page which makes it possible to write to the
address.
Show with enumeration
This option will read the value from the address and present it with the
corresponding enum string (See Enum below).
Writeable value with enumeration
This option will read the value from the address and present it with the
corresponding enum string. There will be a drop down next to the value at the
view-page where available enum strings will be selectable. A selected value will
be written to the address.
Enum - here the enum variables is defined in following format [number]=[string].
Each enum is separated by a semi colon ';' with no blank spaces.
Examples:
0=Off;1=On
0=Sunday;1=Monday;2=Tuesday;3=Wednesday;4=Thursday;5=Friday;6=Saturday
Number of decimals - Defines how many decimals to use for this point.
Valid range - defines min and max value for a write parameter. If a user tries to
enter a value outside the range, a warning message will appear.
When you are finished with the Template, continue to the Device Configuration.
4-3
Device configuration
On the Device Configuration page, you define which Modbus slaves are attached
to the webSCADA.