PULSTRONIC
INSTALLATION
10 V
20 mA
0
5 V
10 mA
2 V
FACTORY SETTING
Max. output
pressure
(bar)
Input pressure
(
*
) Only on DN 0.5
ZERO POINT ADJUSTMENT (potentiometer P4)
Example 1
: At a setpoint of 1 volt, the output pressure should be 3 bar: Apply a setpoint of 1 volt and turn potentiometer P4 clockwise
until 3 bar are reached.
Example 2
: At a setpoint of 2 volts, the output pressure should be 0 bar: Apply a setpoint of 2 volts and turn potentiometer P4
counterclockwise until 0 bar is obtained.
In order to avoid damaging the pressure sensor,
the supply pressure must always be less than the maximum input pressure
defined above
.
Turn potentiometer P4
counterclockwise
Turn
potentiometer P4
clockwise
Saturation zone
MIN.
(bar)
MAX.
(bar)
1 (
*
)
1,5
2
2
2,5
5
3
3,5
5
6
6,5
8
10
10,5
12
Max. output
pressure
10 V
20 mA
0
SETTING 75%
FACTORY SETTING 100%
SPAN ADJUSTMENT (potentiometer P3)
Example for a valve adjustment with a maximum output pressure of 6 bar.
At a setpoint of 0 - 10 Volts the output pressure should be 0 to 5 bar:
Apply a setpoint of 10 Volts and turn potentiometer P3 counterclockwise until 5 bar are reached at the valve output.
Turn potentiometer counterclockwise.
Turn potentiometer clockwise.
The span can be adjusted between 75 and 100 % of the maximum output pressure.
The factory setting is 100 %.
Span adjustment with
potentiometer P3
Max.
output pressure
Max. output
pressure
0.75