Asco 3ADTS Installation Manual Download Page 9

ASCO 3ATS, 3ADTS, 3NTS, 3NDTS 

 

Installation Manual 

Page 2 

ASCO Power Technologies 

381333-404 B 

Line Connections 

Refer to the wiring diagram provided with the transfer switch.  
All wiring must be made in accordance with the National 
Electrical Code and local codes. 

 

 

De-energize the conductors before making any line or 
auxiliary circuit connections.  Be sure that the Normal 
and Emergency line connections are in proper phase 
rotation.  Place the engine generator starting control in 
the OFF position.  Make sure engine generator is not in 
operation. 

Testing Power Conductors 

Do not connect the power conductors to the transfer switch 
until they are tested.  Installing power cables in conduit, cable 
troughs, and ceiling-suspended hangers often requires 
considerable force.  The pulling of cables can damage 
insulation and stretch or break the conductor’s strands.  For 
this reason, after the cables are pulled into position, and before 
they are connected, they should be tested to verify that they 
are not defective or have been damaged during installation. 

Connecting Power Cables 

After the power cables have been tested, connect them to the 
appropriate terminal lugs on the transfer switch as shown on 
the wiring diagram provided with the transfer switch.  Make 
sure that the lugs provided are suitable for use with the cables 
being installed.  Standard terminal lugs are solderless screw 
type and will accept the wire sizes listed on the drawings 
provided with the transfer switch.  Be careful when stripping 
insulation from the cables, avoid nicking or ringing the 
conductor.  Remove surface oxides from cables by cleaning 
with a wire brush.  When aluminum cable is used, apply joint 
compound to conductors.  Tighten cable lugs to the torque 
specified on rating label. 

Harnesses 

The transfer switch is connected to the left side of the 
controller by a plug-in harness. 

Auxiliary Circuits 

Connect auxiliary circuit wires to appropriate terminals on the 
transfer switch as shown on the wiring diagram. 

Controller Ground 

A grounding wire must be connected to the controller’s lower 
left mounting stud.  Because the controller is mounted on the 
enclosure door, a conductive strap must be used between the 
enclosure and the door.  This connection provides proper 
grounding which does not rely upon the door hinges. 

Engine Starting Contacts 

The engine control contact connections are located on the 
transfer switch for 3ATS & 3NTS or upper right of the 
enclosure for 3ADTS & 3NDTS.  Connect signal wires to 
appropriate terminals as specified on the wiring diagram, 
Table A, and shown in Figure 1. 

Table A.  Engine Start Connections. 

When normal 

source fails 

Terminals on 

transfer switch 

contact closes 

TB1 and TB2 

contact opens 

TB1 and TB3 

 

 

Figure 1. Engine start and auxiliary circuit terminal block 

TB located on 3ATS & 3NTS transfer switch. 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2.  Main contact position indicators on right side. 

left side of 

transfer switch 

terminal block TB

on 3ATS & 3NTS

For 3ADTS & 3NDTS 

the terminal block TB 

is located in the upper 

right side of the 

enclosure. 

window 

indicators 

O

is open

is closed 

Emergency 
contacts 

Normal 
contacts 

Summary of Contents for 3ADTS

Page 1: ...URE COMMON ALARM NOT IN AUTO SIGNALING FEATURES INPHASE TRANSFER FEATURE FOR LOAD TRANSFER SOURCE AVAILABILITY SIGNALS EXTERNAL POWER SUPPLY COMPATIBILITY LOAD CURRENT METERING NON AUTOMATIC MANUAL OPERATION FOUR FUNCTION SOFTWARE BUNDLE REMOTE CONTROL FEATURES ...

Page 2: ...ASCO ASCO ...

Page 3: ...ASCO ...

Page 4: ...ASCO ...

Page 5: ...ASCO ...

Page 6: ...ASCO ...

Page 7: ...ASCO ...

Page 8: ...h for all mounting details including door opening space If bottom cable entry is used the foundation must be prepared so that the conduit stubs are located correctly Refer to the enclosure outline drawing for specified area and location Provide cable bending space and 1 inch minimum clearance to live metal parts When a concrete floor is poured use interlocking conduit spacer caps or a wood or meta...

Page 9: ...d with the transfer switch Be careful when stripping insulation from the cables avoid nicking or ringing the conductor Remove surface oxides from cables by cleaning with a wire brush When aluminum cable is used apply joint compound to conductors Tighten cable lugs to the torque specified on rating label Harnesses The transfer switch is connected to the left side of the controller by a plug in harn...

Page 10: ...s provided on the transfer switch for maintenance purposes only Manual operation of the transfer switch should be checked before it is energized operated electrically Do not manually operate the transfer switch until both power sources are disconnected open both circuit breakers 1 After deenergizing both power sources open the enclosure door Locate and remove the maintenance handle from the clip o...

Page 11: ...e positions ALL POWER MUST BE OFF Transfer Switch Position Interlocked Shafts Link between contact shafts prevents closing both N E contacts Maintenance Handle Shaft Indicators Normal E O upper contacts open N C lower contacts closed Load Disconnected E O upper contacts open N O lower contacts open Emergency E O upper contacts closed N C lower contacts open Note The hub and contact shaft turn in o...

Page 12: ...e settings in the controller 1 Close the normal source circuit breaker The normal source accepted and the load on normal lights should come on 2 Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch normal source terminals 3 Close the emergency source circuit breaker Start generator if necessary The emergency source accepted light should com...

Page 13: ...s the transfer button The engine should start and run within 15 seconds For 3NTS 3NDTS the generator must be started manually at the generator The emergency source accepted light should come on 3 For 3ATS 3ADTS the transfer switch should transfer to the emergency position The load on emergency light should come on and the load on normal light should go off For 3NTS 3NDTS press the transfer button ...

Page 14: ...ns no further lubricating is required Renew factory lubrication if the transfer switch is subjected to severe dust abnormal operating conditions or if the TS coil s is replaced Order lubrication kit 75 100 Check all cable connections retighten them Torque to values shown on the transfer switch label Replacement Parts When ordering replacement parts provide the Serial No Bill of Material No BOM and...

Page 15: ...st 90 of nominal phase to phase voltage between transfer switch terminals EA and EC or EL1 and EL2 for 2 pole switches There are factory settings For 3ATS 3ADTS the transfer switch does not transfer the load to normal source when normal returns or after transfer test Wait for the feature 3A time delay For immediate retransfer press the transfer button bypass timer If inphase transfer is active wai...

Reviews: