Asco 3ADTS Installation Manual Download Page 10

Installation Manual  

 

ASCO 3ATS, 3ADTS, 3NTS, 3NDTS 

381333-404 B 

ASCO Power Technologies 

Page 3 

left side of 

transfer switch 

maintenance 

handle 

clip

contact shaft hub

Figure 4.  Maintenance handle on 3ATS & 3NTS

left side of 
transfer switch 

maintenance 
handle 

clip

Emergency source 
contact shaft hub 

Hubs shown with 
Emergency source 
contacts open and 
Normal source contacts 
closed. See Table B 
on page 4. 

Normal source 
contact shaft hub

Figure 5.  Maintenance handle on 3ADTS & 3NDTS

hub 

frame 

handle 

UP closes the 

Normal source 

contacts (lower) 

DOWN closes the 

Emergency source 

contacts (upper) 

Functional Test 

The functional test consists of three checks:  manual 
operation, voltage checks, and electrical operation. 

 

 

Do these checks in the order presented to avoid 
damaging the transfer switch. 

1 – Manual Operation 

A maintenance handle is provided on the transfer switch for 
maintenance purposes only.  Manual operation of the transfer 
switch should be checked before it is energized (operated 
electrically). 

 

 

Do not manually operate the transfer switch until 
both power sources are disconnected:  open both 
circuit breakers. 

1.

 

After deenergizing both power sources, open the enclosure 
door.  Locate and remove the maintenance handle from the 
clip on the left side of the transfer switch.  See Figures 3, 4, 
5, & 6.  See Figure 2 for the contact position indicators. 

2.

 

Install the handle into the hole in the molded hub.  Move 
the handle up or down as shown to manually operate the 
transfer switch. It should operate smoothly without any 
binding. If it does not, check for shipping damage or 
construction debris. 

3.

 

3ADTS and 3NDTS have two contact shaft hubs.  See 
Figures 5 and 6 and Table B. 

4.

 

Return the transfer switch to the Normal position. 

Note: If Normal and Emergency connections are reversed this 
operation 
is also 
reversed. 

 

 

 

 

 

 

Figure 3.  Maintenance handle operation  

on 3ATS & 3NTS. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for 3ADTS

Page 1: ...URE COMMON ALARM NOT IN AUTO SIGNALING FEATURES INPHASE TRANSFER FEATURE FOR LOAD TRANSFER SOURCE AVAILABILITY SIGNALS EXTERNAL POWER SUPPLY COMPATIBILITY LOAD CURRENT METERING NON AUTOMATIC MANUAL OPERATION FOUR FUNCTION SOFTWARE BUNDLE REMOTE CONTROL FEATURES ...

Page 2: ...ASCO ASCO ...

Page 3: ...ASCO ...

Page 4: ...ASCO ...

Page 5: ...ASCO ...

Page 6: ...ASCO ...

Page 7: ...ASCO ...

Page 8: ...h for all mounting details including door opening space If bottom cable entry is used the foundation must be prepared so that the conduit stubs are located correctly Refer to the enclosure outline drawing for specified area and location Provide cable bending space and 1 inch minimum clearance to live metal parts When a concrete floor is poured use interlocking conduit spacer caps or a wood or meta...

Page 9: ...d with the transfer switch Be careful when stripping insulation from the cables avoid nicking or ringing the conductor Remove surface oxides from cables by cleaning with a wire brush When aluminum cable is used apply joint compound to conductors Tighten cable lugs to the torque specified on rating label Harnesses The transfer switch is connected to the left side of the controller by a plug in harn...

Page 10: ...s provided on the transfer switch for maintenance purposes only Manual operation of the transfer switch should be checked before it is energized operated electrically Do not manually operate the transfer switch until both power sources are disconnected open both circuit breakers 1 After deenergizing both power sources open the enclosure door Locate and remove the maintenance handle from the clip o...

Page 11: ...e positions ALL POWER MUST BE OFF Transfer Switch Position Interlocked Shafts Link between contact shafts prevents closing both N E contacts Maintenance Handle Shaft Indicators Normal E O upper contacts open N C lower contacts closed Load Disconnected E O upper contacts open N O lower contacts open Emergency E O upper contacts closed N C lower contacts open Note The hub and contact shaft turn in o...

Page 12: ...e settings in the controller 1 Close the normal source circuit breaker The normal source accepted and the load on normal lights should come on 2 Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch normal source terminals 3 Close the emergency source circuit breaker Start generator if necessary The emergency source accepted light should com...

Page 13: ...s the transfer button The engine should start and run within 15 seconds For 3NTS 3NDTS the generator must be started manually at the generator The emergency source accepted light should come on 3 For 3ATS 3ADTS the transfer switch should transfer to the emergency position The load on emergency light should come on and the load on normal light should go off For 3NTS 3NDTS press the transfer button ...

Page 14: ...ns no further lubricating is required Renew factory lubrication if the transfer switch is subjected to severe dust abnormal operating conditions or if the TS coil s is replaced Order lubrication kit 75 100 Check all cable connections retighten them Torque to values shown on the transfer switch label Replacement Parts When ordering replacement parts provide the Serial No Bill of Material No BOM and...

Page 15: ...st 90 of nominal phase to phase voltage between transfer switch terminals EA and EC or EL1 and EL2 for 2 pole switches There are factory settings For 3ATS 3ADTS the transfer switch does not transfer the load to normal source when normal returns or after transfer test Wait for the feature 3A time delay For immediate retransfer press the transfer button bypass timer If inphase transfer is active wai...

Reviews: