© Copyright 2010 ASAN Security Technologies Oy
www.asansecurity.com
Settings for Moxa when used with Consilium-integration
33
Port 1
Operation mode
TCP Service Mode
TCP alive check time
1 (0-99 min)
Inactivity time
0 (0-65535 ms)
Max connection
4
Ignore jammed IP
Yes
Allow driver control
No
Data packing
Packing length
0 (0-1024)
Delimiter 1
0
Delimiter 2
1
Delimiter process
Do nothing
Force transmit
0 (0-65535)
TCP Server Mode
Local TCP Port
4001
Command port
966
Operating settings - Port 1
Port 1
Port alias
COM1
Serial Parameters
Baud rate
19200
Data bits
8
Stop bits
1
Parity
None
Flow control
None
FIFO
Disable
Interface
RS-232
Serial settings - Port 1
The Moxa device must be configured in a certain way in order to work with the Consilium fire
alarm integration. Please configure the following settings via the Moxa device's interface
(accessible at the device's IP address).