Asahi/America 94 Series Installation, Operation And Maintenance Manual Download Page 24

ASAHI/AMERICA, INC  655 ANDOVER STREET  LAWRENCE, MA. 01843    TELEPHONE 800-343-3618 

File:  assembly/manuals/Series 94 Gen II A/C Modulating Svc Manual           Rev. A 

11/19/19  

Page 24 of 27 

Troubleshooting 

 

PROBLEM 

POSSIBLE CAUSES 

REMEDIES 

There is no output, but 
the motor runs 

Manual override engaged. 

 
 
 
 
 
 
Valve stem broken. 

When the manual override 
is engaged, the motor will 
run, but no output will be 
observed until the manual 
override re-engages with 
the output shaft 
 
When the valve stem is 
broken, there will not be a 
change in fluid movement, 
making it seem as if the 
actuator has no output.. 

 

No response from 
valve/actuator 

No power source to 
actuator 
No signal to actuator 
 
Power source 
disconnected 
 
Low or wrong power 
source 
Mechanical Brake 
jammed or misaligned 

Check for power 
 
Check “Fault Indicator 
 
Check for broken wire, 
loose connection 
Check for proper voltage 
 
 
Check alignment of brake 

Motor hums and no 
output is observed 

Foreign material caught 
in valve 
 
 
 
Capacitor worn 

Remove material and 
inspect valve for 
damaged and/or worn 
parts. Replace parts as 
necessary 
Replace capacitor 

No response from unit 
(All lights are off.) 

No power 
 
Excessive voltage applied 
to unit. 
 
Blown or missing fuse 

Check power source. 
 
Replace unit. 
 
 
Replace with appropriate 
fuse; see "Specifications" 
in manual. 

Summary of Contents for 94 Series

Page 1: ...TREET LAWRENCE MA 01843 TELEPHONE 800 343 3618 File assembly manuals Series 94 Gen II A C Modulating Svc Manual Rev A 11 19 19 Page 1 of 27 Series 94 Actuator For A C Modulating Service Installation O...

Page 2: ...ual Override Operation 8 Setting Limit Switches 8 Calibration 9 Outline Diagram 9 QuickCal Procedure 10 Aux Open Close Option Setup 11 Aux Position Option Setup 11 Power Signal J2 12 Actuator J1 12 Ov...

Page 3: ...ult operation upon loss of command Various option modules are easily plugged into the unit providing other features such as a position feedback signal current or voltage auxiliary switches fault relay...

Page 4: ...self without the need for any instrumentation The adaptive control feature of the DHC 100 eliminates the need for any calibration steps In the simplest application only the closed and open positions n...

Page 5: ...tting is used to maintain NEMA 4X enclosure rating NOTE We recommend sealing conduit openings on units installed outdoors or exposed to large temperature swings 15 F or more We also recommend the heat...

Page 6: ...e valve and the actuator to corresponding positions either OPEN or CLOSED The flats on the actuator shaft extension indicate valve position Type 23 Ball Valves 3 way See Drawing 0129BV sizes 3 Install...

Page 7: ...19 Page 7 of 27 indicates disc orientation Install bolts 5 washers 6 and nuts 7 and tighten evenly Flats on actuator shaft indicate valve position Disc Orientation CAUTION If mounted unit is installe...

Page 8: ...position Then loosen set screws on top cam Part 21 and rotate cam CCW into limit switch arm until a click is heard this designates the switch circuit has opened and defines a full open position Tighte...

Page 9: ...ASAHI AMERICA INC 655 ANDOVER STREET LAWRENCE MA 01843 TELEPHONE 800 343 3618 File assembly manuals Series 94 Gen II A C Modulating Svc Manual Rev A 11 19 19 Page 9 of 27 Calibration Outline Diagram...

Page 10: ...st buttons and to move the actuator and verify that the limit switches are set past the desired open and closed positions then move the actuator to mid stroke 4 If LED is solid proceed to step 7 5 If...

Page 11: ...he application If a signal input was already connected the actuator should have moved to that position Aux Open Close Option Setup 1 Push the MODE button until the AUX CLOSE OUTPUT LED is illuminated...

Page 12: ...pin 6 a local control knob can be implemented Pin 8 provides an auxiliary 15VDC output which can be used to power an input or outpur 4 20mA transmitter Actuator J1 The actuator motor and feedback pot...

Page 13: ...e OVERRIDE mode is enabled see OVERRIDE MODE the MODE button is disabled and the Manual Pot Cal indicator will turn on steady Adjust up and Adjust down The adjust up and adjust down buttons are used t...

Page 14: ...can also be terminated using the OFF or STOP function The motor is also turned off if the DHC 100 detects a stall see STALL DETECTION An OPEN or CLOSE operation can be attempted again after switching...

Page 15: ...ate as the actuator moves further away from midrange By using the adjust buttons to position the actuator to midstroke half way point between the desired open and closed positions the feedback potenti...

Page 16: ...if the unit has been previously set to the desired position Auxiliary Open Output The AUX OPEN OUTPUT function is used to set an optional output setting that is associated with the open position an a...

Page 17: ...and signal is used a loss of command signal cannot be detected Therefore if the unit is configured for a 0 5V or 0 10V command signal see COMMAND TYPE the MODE button will not select the LOSS OF COMMA...

Page 18: ...r details Note that the indicators may not indicate ALL the fault conditions that may exist This means that when the indicated fault is corrected the unit may display another fault that has not been c...

Page 19: ...ns are broken Normal operation resumes when the potentiometer is reconnected or back in range Loss of Command If the command signal is disconnected the fault indication will remain on until the signal...

Page 20: ...de variations and the DHC 100 can position the actuator more precisely at closed and open than the limit switches A limit switch serves better as a fail safe device to protect against electrical failu...

Page 21: ...provide additional features such as position feedback signals auxiliary switch outputs or digital communications Contact the factory for the latest available modules Refer to the diagram below for in...

Page 22: ...s DHC 100 Specs POWER REQUIREMENTS DHC 100 117VAC 10 50 60 Hz DHC 100A 234VAC 10 50 60 Hz DHC 100B 24VAC 10 50 60 Hz 12 VA typical not including output load Fuse Type 5A TR5 Slo Blo replaceable COMMAN...

Page 23: ...OR OUTPUTS Off state Leakage Current 15mA Maximum Load Current 150 C 5A ENVIRONMENTAL Operating Temperature Range 32 F to 150 F Storage Temperature Range 40 F to 185 F Relative Humidity Range 0 to 90...

Page 24: ...t seem as if the actuator has no output No response from valve actuator No power source to actuator No signal to actuator Power source disconnected Low or wrong power source Mechanical Brake jammed or...

Page 25: ...reverse acting Remount actuator as necessary Refer to Close and Open modes in manual Actuator does not respond to input signal FAULT indicator constantly flashes Input signal not connected Input sign...

Page 26: ...ctuator reaches the fully closed or open position Closed or open limit switches set inside the operating range Adjust limit switch cams refer to Close and Open modes in manual Actuator operates errati...

Page 27: ...e do however recommend that periodic checks are made to ensure that all fasteners are tight and properly torqued to extend the life of the actuator and valve Series 94 Actuators are manufactured with...

Page 28: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 29: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 30: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 31: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 32: ......

Page 33: ......

Page 34: ...FOR REFERENCE ONLY ASAHI AMERICA...

Reviews: