selected, the LOSS OF COMMAND feature is not available, so proceed to step
12.
10.
Push the MODE button until the “LOSS OF COMMAND” LED is illuminated;
this sets the actuator to a predetermined position upon loss of command. Use the
adjust buttons (
and
) to select appropriate position (OPEN, CLOSE, or LAST
POSITION).
11.
Please skip to
Aux Position Setup
if optional Transmitter, or optional
Transmitter with Switches is installed, otherwise continue to the next step.
12.
Push the MODE button until the “AUTO” LED is illuminated. Your calibration
is now
COMPLETE
. Connect the command signal wires to connector J2:
terminal #4 (signal ground) and terminal #5 (mA input)
OR
terminal #6 (voltage
input), depending on the application. If a signal input was already connected, the
actuator should have moved to that position.
Aux Open/Close Option Setup
1.
Push the MODE button until the “AUX CLOSE OUTPUT” LED is illuminated.
Use the adjust buttons (
and
) to drive the actuator to the desired auxiliary
close position.
2.
Push the MODE button until the “AUX OPEN OUTPUT” LED is on. Use the
adjust buttons (
and
) to drive the actuator to the desired auxiliary open
position.
3.
Continue with Step 9 in the
Quick Calibration Procedure
(see above).
Aux Position Option Setup
1.
Push the MODE button until the green “AUX POSITION OUT CAL” LED
illuminates
while
the “CLOSE” LED flashes.
2.
Use the adjust buttons (
and
) to set the desired output voltage or current
(mA) on the option module output for the closed position.
3.
Push the MODE button so the “AUX POSITION OUT CAL” LED remains
steady
while
the “OPEN” LED flashes. Use the adjust buttons (
and
) to set
the desired output voltage or current (mA) on the option module output for the
open position.
4.
Continue with Step 12 in the
Quick Calibration Procedure
(see above).