Please read the following pages to ensure that ALL of the 

selectable features are understood and selected if required. 

 

 

Power / Signal (J2) 

 

Power is connected to pins 1, 2, & 3 as shown in the wiring schematic. The fuse 
installed on the unit is rated for maximum output current that can be safely 
delivered by the AC outputs. Replacement fuses must not exceed the maximum 
rating to prevent damage to the unit. Smaller fuse sizes can be used with smaller 
motors – consult the factory for appropriate fuse size and type. 
 
An appropriate command signal, either 0-5V, 0-10V, 1-5V, 2-10V or 4-20mA, 
should be connected to pin 5 or 6 (as shown in the Block Diagram) while using 
pin 4 as the return 

signal ground

.  The DHC-100 must be configured for the type 

of command signal that is to be used (see COMMAND TYPE). 
 
Pin 7 of J2 provides an aux5V output which can be used to connect a 
command potentiometer.  By connecting one end of a potentiometer to pin 7, the 
other end to pin 4, and the wiper to pin 6, a local control knob can be 
implemented.  Pin 8 provides an aux15VDC output which can be used to 
power an input or outpur 4-20mA transmitter. 
 
 

Actuator (J1) 

 
The actuator motor and feedback potentiometer are connected to J1 as shown in 
the wiring schematic.  The motor neutral wire must be connected to pin 2, while 
one motor winding is connected to pin 1 and the other winding is connected to 
pin 3. The feedback potentiometer wiper must be connected to pin 5, while one 
end is connected to pin 4 and the other end is connected to pin 6. The 

Polarity 

Detection

 feature of the DHC-100 automatically determines which motor winding 

to control based on where the 

open

 and 

closed

 positions are set;  this feature 

also eliminates the need to rewire the unit for direct or reverse acting 
applications. 
 
When the 

 and 

 

buttons are used to control the actuator, the 

 

button will 

turn on the motor winding connected to pin 1, while the 

 button will turn on the 

motor winding connected to pin 3.  See MANUAL/FB POT CAL for more details. 
 
 

Override (J7) 

 
J7 provides a simple 2-wire connection that can override the DHC-100 to perform 
a variety of external control functions.  Using an appropriate interface module, 
commonly used auto/manual station switches are easily implemented with low 
voltage/low current switches.  The factory-installed jumper between pins 1 and 2 

Summary of Contents for 94 Series

Page 1: ...TREET LAWRENCE MA 01843 TELEPHONE 800 343 3618 File assembly manuals Series 94 Gen II A C Modulating Svc Manual Rev A 11 19 19 Page 1 of 27 Series 94 Actuator For A C Modulating Service Installation O...

Page 2: ...ual Override Operation 8 Setting Limit Switches 8 Calibration 9 Outline Diagram 9 QuickCal Procedure 10 Aux Open Close Option Setup 11 Aux Position Option Setup 11 Power Signal J2 12 Actuator J1 12 Ov...

Page 3: ...ult operation upon loss of command Various option modules are easily plugged into the unit providing other features such as a position feedback signal current or voltage auxiliary switches fault relay...

Page 4: ...self without the need for any instrumentation The adaptive control feature of the DHC 100 eliminates the need for any calibration steps In the simplest application only the closed and open positions n...

Page 5: ...tting is used to maintain NEMA 4X enclosure rating NOTE We recommend sealing conduit openings on units installed outdoors or exposed to large temperature swings 15 F or more We also recommend the heat...

Page 6: ...e valve and the actuator to corresponding positions either OPEN or CLOSED The flats on the actuator shaft extension indicate valve position Type 23 Ball Valves 3 way See Drawing 0129BV sizes 3 Install...

Page 7: ...19 Page 7 of 27 indicates disc orientation Install bolts 5 washers 6 and nuts 7 and tighten evenly Flats on actuator shaft indicate valve position Disc Orientation CAUTION If mounted unit is installe...

Page 8: ...position Then loosen set screws on top cam Part 21 and rotate cam CCW into limit switch arm until a click is heard this designates the switch circuit has opened and defines a full open position Tighte...

Page 9: ...ASAHI AMERICA INC 655 ANDOVER STREET LAWRENCE MA 01843 TELEPHONE 800 343 3618 File assembly manuals Series 94 Gen II A C Modulating Svc Manual Rev A 11 19 19 Page 9 of 27 Calibration Outline Diagram...

Page 10: ...st buttons and to move the actuator and verify that the limit switches are set past the desired open and closed positions then move the actuator to mid stroke 4 If LED is solid proceed to step 7 5 If...

Page 11: ...he application If a signal input was already connected the actuator should have moved to that position Aux Open Close Option Setup 1 Push the MODE button until the AUX CLOSE OUTPUT LED is illuminated...

Page 12: ...pin 6 a local control knob can be implemented Pin 8 provides an auxiliary 15VDC output which can be used to power an input or outpur 4 20mA transmitter Actuator J1 The actuator motor and feedback pot...

Page 13: ...e OVERRIDE mode is enabled see OVERRIDE MODE the MODE button is disabled and the Manual Pot Cal indicator will turn on steady Adjust up and Adjust down The adjust up and adjust down buttons are used t...

Page 14: ...can also be terminated using the OFF or STOP function The motor is also turned off if the DHC 100 detects a stall see STALL DETECTION An OPEN or CLOSE operation can be attempted again after switching...

Page 15: ...ate as the actuator moves further away from midrange By using the adjust buttons to position the actuator to midstroke half way point between the desired open and closed positions the feedback potenti...

Page 16: ...if the unit has been previously set to the desired position Auxiliary Open Output The AUX OPEN OUTPUT function is used to set an optional output setting that is associated with the open position an a...

Page 17: ...and signal is used a loss of command signal cannot be detected Therefore if the unit is configured for a 0 5V or 0 10V command signal see COMMAND TYPE the MODE button will not select the LOSS OF COMMA...

Page 18: ...r details Note that the indicators may not indicate ALL the fault conditions that may exist This means that when the indicated fault is corrected the unit may display another fault that has not been c...

Page 19: ...ns are broken Normal operation resumes when the potentiometer is reconnected or back in range Loss of Command If the command signal is disconnected the fault indication will remain on until the signal...

Page 20: ...de variations and the DHC 100 can position the actuator more precisely at closed and open than the limit switches A limit switch serves better as a fail safe device to protect against electrical failu...

Page 21: ...provide additional features such as position feedback signals auxiliary switch outputs or digital communications Contact the factory for the latest available modules Refer to the diagram below for in...

Page 22: ...s DHC 100 Specs POWER REQUIREMENTS DHC 100 117VAC 10 50 60 Hz DHC 100A 234VAC 10 50 60 Hz DHC 100B 24VAC 10 50 60 Hz 12 VA typical not including output load Fuse Type 5A TR5 Slo Blo replaceable COMMAN...

Page 23: ...OR OUTPUTS Off state Leakage Current 15mA Maximum Load Current 150 C 5A ENVIRONMENTAL Operating Temperature Range 32 F to 150 F Storage Temperature Range 40 F to 185 F Relative Humidity Range 0 to 90...

Page 24: ...t seem as if the actuator has no output No response from valve actuator No power source to actuator No signal to actuator Power source disconnected Low or wrong power source Mechanical Brake jammed or...

Page 25: ...reverse acting Remount actuator as necessary Refer to Close and Open modes in manual Actuator does not respond to input signal FAULT indicator constantly flashes Input signal not connected Input sign...

Page 26: ...ctuator reaches the fully closed or open position Closed or open limit switches set inside the operating range Adjust limit switch cams refer to Close and Open modes in manual Actuator operates errati...

Page 27: ...e do however recommend that periodic checks are made to ensure that all fasteners are tight and properly torqued to extend the life of the actuator and valve Series 94 Actuators are manufactured with...

Page 28: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 29: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 30: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 31: ...FOR REFERENCE ONLY ASAHI AMERICA...

Page 32: ......

Page 33: ......

Page 34: ...FOR REFERENCE ONLY ASAHI AMERICA...

Reviews: