Note: 

If the UPS is abnormal in the above regulation, please perform maintenance 

according to the steps of removing single UPS.

   

Operating process of removing the Paralleled UPS: 

1.    If you need to remove the UPS on normal running, press the Power-off button of the 

UPS that is confirmed to be removed twice continuously and the UPS will cut off its 

output immediately; 

2.    Disconnect the input breaker, the external input breaker, the output breaker and the 

battery breaker of the UPS that need to be removed. 

3.    Turn off the UPSs that are running, after all of them transfer to the Bypass mode, 

disassemble the cover board of each UPS and set the maintenance switch from 

“UPS” to “BPS” and then disconnect the input breaker of each UPS. 

4.    If the remained UPS system becomes single UPS system after removing the single 

UPS, you need to connect the short connection wire of the JP1 and JP2 located on 

the Terminal block of the UPS. 

5.    After all panels of the UPSs do not display anything any more, disassemble the cover 

board of the parallel port on the UPS connected with the parallel cable of the UPS 

that need to be removed. Remove the parallel cable and screw the cover board of 

the parallel port back again.

6.    Disassemble the cover board of the parallel port located on the UPS that need to be 

removed and remove the parallel cable, and then screw the cover board back again.   

7.    Close all of the input mains breakers of the remained UPSs. After all UPSs transfer 

to the Bypass mode, set the UPS maintenance switch from “BPS” to “UPS” and 

screw the maintenance cover board back again. Then turn on all of the UPSs and 

transfer them to the INV mode to perform the parallel operation.

8.    If the removed UPS will be used in single mode, JP1 and JP2 on the terminal block 

should be connected with a short connection wire. 

Notes for parallel maintenance: 

1.    Make sure that the maintenance switches of all UPSs (including new unit) are in the 

same positions (either in the positions of “UPS” or “BPS”) when the UPS parallel 

system is going to be in INV mode.   

2.    Make sure that the output breaker of the UPS that is removed is in the position of 

“OFF” before the UPS parallel system transfers to the INV mode. 

3.    Don’t operate the maintenance switch of any one UPS in the parallel system when 

he UPS parallel system is in the INV mode. 

4.    The UPS in the parallel system will cut off its output if its Power-Off button is pressed 

twice continuously. Please operate carefully and let the user know the operation at 

the same time.   

 

Summary of Contents for 3T10KS

Page 1: ...to Bypass after 10min Load 130 Alarm and Transfer To Bypass after 1sec Overload Bypass mode 105 Load 130 Alarm Input Breaker May Trip Load 130 Alarm Input Breaker May trip and Cut Off Output after 1m...

Page 2: ...S voltage 345V 5V BUS voltage 345V 5V Difference between the BUS voltage absolute value 5V Balance voltage zero load 500mV Charging voltage 273V 1 If the above data exceed the electric specification r...

Page 3: ...3 2 Circuit block diagram Circuit block diagram the dashed indicates the charging board of the long backup time model and the real line indicates the charging board of the standard model...

Page 4: ...the MOSFET is off the primary stored energy 1 2Llp2 is delivered to the secondary to supply load current and replenish the charge on output capacitors that they had lost when the MOSFET was on This ci...

Page 5: ...l transfer to the battery mode If disconnecting the batteries from the UPS the UPS will transfer back to the line mode Press the ON button for 0 5 second when the UPS is in the battery mode the buzzer...

Page 6: ...d voltage of the input utility power will be in the same phase and the power factor is nearly 1 3 4 Inverter circuit Half bridge inverter topology The input of the half bridge inverter topology is DC...

Page 7: ...The INV mode the inverter output is supplied to the output terminals of the unit via the filter choke the inverter relay contact generally open closed when in INV mode and the load detecting transform...

Page 8: ...wer goes through noise filter to the pre charging circuit The DC capacitors will be pre charged When the DC voltage on DC capacitor achieve the input AC power peak value then input SCR will turn on Af...

Page 9: ...model The input of the charger is connected to REC When bypass breaker on and IP SCR on the charger will work The charge voltage is 273VDC and constant charge current is 4 2A Adjust the VR1 on charger...

Page 10: ...the output send to the rectifier on the PSDR board 4 7 CCB only for 3T15KS 3T20KS The CCB common control board is used to connect the PSDR board and the CNTL board It may help the CNTL board to contr...

Page 11: ...Note 1 indicates that the jumper is connected 0 indicates that nothing is connected For the pin plugs that are not listed here are not connected pin11 pin12 pin9 pin10 pin7 pin8 pin1 pin2 T6K 0 0 0 1...

Page 12: ...15 Over temperature Fault 08 Current Un share Fault 16 Inverter Short 09 Error Model 17 Communication Fault 10 SCI RX Error 18 Battery Open 11 Negative Output Power Fault 20 Inverter Relay Short 12 7...

Page 13: ...n you don t have a discharging resistor perform the maintenance after you have waited for at least 5 minutes and the BUS voltage is less than 10V Otherwise there may be electric shock 4 After you have...

Page 14: ...X is a digit from 0 to 6 then press the ENTER key output voltage will rise drop a little step 6 INV output voltage setting Type VXXX command XXX is 220 230 240 then press the ENTER key INV output vol...

Page 15: ...y UPS must be regulated 3 The UPS who have been replaced CNTL PSDR must be regulated again 4 All the commands use capital letters 5 All the above parameter regulation can not be accumulated 6 All the...

Page 16: ...e NTC on the CN107 of the PSDR board is damaged INV output short The Fault code is 09 The buzzer beeps continuously When the time that the INV output voltage keeps less than 50V and the output current...

Page 17: ...e output cable and ensure the length of cable is same Error Model The Fault code is 17 The UPS beeps continuously Ensure the model pin plugs in right position SCI RX Error The Fault code is 18 The UPS...

Page 18: ...normal IP Fuse Open The Warning code is 24 The buzzer beeps every second Check the IP fuse If the IP fuse is damaged replace the fuse immediately 7 5 PCB maintenance 1 Charger board 1 1 Charger board...

Page 19: ...R340 R339 R341 0 5 6 open 2 PSDR board 2 1 SCR part Item Checked components DVM Function Reference Value Fail Condition 1 F301 F302 0 open A K 1 4M short 2 Q301 Q302 G K 10 short 2 2 Boost part Item...

Page 20: ...8 Parallel maintenance This UPS has the function of parallel redundancy so if you need to add single UPS to the parallel system refer to the following operating process of adding a new UPS If you need...

Page 21: ...e slot of the parallel board and screw up the connector Screw the cover board of the parallel port back again 9 Close the input breakers of all of the UPSs including the new UPS in the parallel system...

Page 22: ...screw the cover board of the parallel port back again 6 Disassemble the cover board of the parallel port located on the UPS that need to be removed and remove the parallel cable and then screw the co...

Page 23: ...PORT I P L I P N KEY ON BAT BAT BAT BAT BAT BAT O P N GND GND L OTHUPS KEY OFF MAINT SWITCH G G G BYPASS O P EMI I P EMI I P TB O P TB PSDR CHARG PAREL PANEL CNTL REC CHGINPUT G K A G K A G K A E C G...

Page 24: ...T OTHUPS KEY OFF IP SCR MAINT SWITCH G O P EMI G G BYPASS I P EMI I P TB O P TB L3 L2 L1 PSDR CHARG PAREL PANEL CNTL REC CHGINPUT G K A G K A G K A E C G E C G G K A E C G G K A G K A G K A G K A G K...

Reviews: