1
1. Electric Specifications
Model
T6K T6KS T10K T10KS 3T10KS
3T15KS
3T20KS
Rated capacity
6KVA/4.2KW
10KVA/7KW 15KVA/10.5KW
20KVA/14KW
Input
Voltage 220VAC
380VAC/220VAC
Frequency 50/60±4
Hz
Power factor
≥
0.98
≥
0.95
Phase wire
1 phase 3 wires
3 phase 5 wires
Maximum current
32A
50A
50A
75A
100A
Output
Voltage
208/220/230/240VAC
±
1 %
Phase wire
1 phase 3 wire
Battery 0.1
%
Frequency
stability
Utility power Synchronize with the utility power (±4HZ)
Instantaneous response
<5% (50% - 100%
-
50% linear load transformation)
Waveform distortion
<2% (linear load)
;
<6% (RCD load)
Overload
(
Line mode
)
105%<Load<130%: Alarm and Transfer to Bypass after 10min
Load>130%: Alarm and Transfer To Bypass after 1sec
Overload
(
Bypass mode
)
105%<Load<130%: Alarm
,
Input Breaker May Trip
Load>130%: Alarm
,
Input Breaker May trip
,
and Cut Off Output after 1min
Overload
(
Battery mode
)
105%<Load<130%: Alarm and Cut Off Output after 10sec
Load>130%: Alarm and Cut Off Output after 1sec
Efficiency (full load)
>
88%
Transfer time
Line mode to Battery mode Zero interruption
Battery mode to Line mode Zero interruption
INV mode to Bypass mode Zero interruption
Bypass mode to INV mode Zero interruption
Other SPEC
Noise
≤
55dB
≤
60dB
Temperature
0°C – 40°C
,
No condensing
Altitude
0 – 1000m
Humidity <95%
Warning device
Double warning with BUZZER beeping and LCD prompt
Communication interface
RS232
,
AS400
,
RS485
,
SNMP
Weight
90 35 93 38 39
55
55
Dimension W*D*H (mm)
260mm×717mm×570mm