Armstrong Air 4SHP16LS Series Installation Instructions Manual Download Page 8

506860-03

Issue  1946

Page 8 of 27

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

LIQUID LINE SERVICE VALVE

LIQUID LINE

BRAZE LINE SET

Wrap both service valves with water-saturated cloths as illustrated here and as mentioned in step 4, before brazing to line set.

Cloths must remain water-saturated throughout the brazing and cool-down process.

WATER-SATURATED

CLOTH

IMPORTANT  — 

Allow  braze  joint  to  cool.  Apply

additional  water-saturated cloths to help cool brazed

joint.  Do  not  remove  water-saturated  cloths  until

piping  has  cooled.  Temperatures  above  250ºF  will

damage valve seals.

6

VAPOR LINE

WATER-SATURATED

CLOTH

VAPOR LINE

 SERVICE VALVE

After all connections have been brazed, disconnect manifold gauge set from service ports. Apply additional water-saturated cloths to both

services valves to cool piping. Once piping is cool, remove all water-saturated cloths.

WHEN BRAZING LINE SET TO

SERVICE VALVES, POINT FLAME

AWAY FROM SERVICE VALVE.

PREPARATION FOR NEXT STEP

7

WRAP SERVICE VALVES

To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use

additional water-saturated cloths underneath the valve body to protect the base paint.

4

FLOW NITROGEN

Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and

out of the vapor valve stem port. See steps 

3A, 3B 

and 

3C

 on manifold gauge set connections.

5

WARNING

FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE

may result if you do not wrap a water-saturated cloth around

both liquid and suction line service valve bodies and copper

tube  stub  while  brazing  the  line  set!  The  braze,  when

complete, must be quenched with water to absorb any

residual heat.

Do not open service valves until refrigerant lines and

indoor coil have been leak-tested and evacuated. Refer

to Leak Test and Evacuation section of this manual.

WARNING

While protecting the 

service valve seals with 

water-saturated cloths, 

ensure that water does 

NOT enter the system.

Summary of Contents for 4SHP16LS Series

Page 1: ...local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Canadian Electrical Code Canada Compliance should be determ...

Page 2: ...ing parts 4 Handle refrigerant with caution refer to proper MSDS from refrigerant supplier 5 Use care when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living ar...

Page 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Page 4: ...24 3 8 3 4 36 3 8 7 8 48 3 8 7 8 60 3 8 1 1 8 For installations exceeding 50 refer to long line set guidelines Be extra careful with sharp bends Tubing can kink very easily and if this occurs the enti...

Page 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Page 6: ...hown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSE...

Page 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Page 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Page 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Page 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Page 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Page 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Page 13: ...OR AIR HANDLER RSBus RSBus OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM THERMOSTAT COMFORT SYNCTM ENABLED HEAT PUMP RSBus OPTIONAL OUTDOOR AIR SENSOR OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM ENAB...

Page 14: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Page 15: ...ocked out until power to the board is interrupted then re established or until the error is cleaned NOTE The control board ignores input from the low pressure switch terminals as follows During the TE...

Page 16: ...m the Comfort Sync thermostat must be used The complete configuration of the outdoor unit is performed using the Comfort Sync thermostat For complete details on how to integrate this unit into a Comfo...

Page 17: ...nication problem Hardware problem on the control Cycle power on control Replace if problem prevents service and is persistent Cleared 300 seconds after fault recovered E131 Corrupted control parameter...

Page 18: ...r unit blower motor dirty filters or clogged refrigerant filter Confirm that the evaporator coil is clean The alarm clears after a power rest E412 The outdoor unit pressure is above the required limit...

Page 19: ...ed by allowing the unit to run for 90 seconds before checking discharge sensor resistance If the discharge sensor resistance is not within range after 90 seconds the board will count one fault After 5...

Page 20: ...Hz Idle Mode Decimal point blinks at 1 Hz 0 5 second on 0 5 second off Display OFF Soft Disabled Top and bottom horizontal line and decimal point blink at 1 Hz Soft Disabled Top and bottom horizontal...

Page 21: ...650 pause A104 pause Outdoor Coil Temperature OCT Any time OCT is sensed in operating range value is displayed if unit is in diagnostic mode Following string is repeated if 2nd stage heat is active wi...

Page 22: ...minutes if coil temperature remains below terminate temperature or by pushing button down for less than 2 seconds Enter A test mode Display will string active error codes E ambient A coil c and disch...

Page 23: ...g procedure must be repeated Table 9 Configuring Unit Capacity Display Code Procedure Solid Pt Release push button Allows user to select type and number of stages on outdoor unit IMPORTANT Field repla...

Page 24: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Page 25: ...t may engage auxiliary heat during the defrost cycle to satisfy a heating demand however the unit will run to normal operation at the conclusion of the defrost cycle In case of extended power outage I...

Page 26: ...506860 03 Issue 1946 Page 26 of 27 4SHP16LS124 36 48 Wiring Diagrams...

Page 27: ...506860 03 Issue 1946 Page 27 of 27 4SHP16LS160...

Reviews: