Armstrong Air 4SHP16LS Series Installation Instructions Manual Download Page 25

506860-03

Issue  1946

Page  25  of 27

Indicating Light

Most heat pump thermostats have an amber light 

which indicates when the heat pump is operating in the 

emergency heat mode.

Temperature Indicator

The temperature indicator displays the actual room 

temperature.

Programmable Thermostats

Your system may be controlled by a programmable 

thermostat. These thermostats provide the added feature of 

programmable time-of-day set points for both heating and 

cooling. Refer to the user’s information manual provided 

with your particular thermostat for operation details.

Important System Information

•  Your system should never be operated without a clean 

air filter properly installed.

•  Return air and supply air registers should be free from 

restrictions or obstructions to allow full flow of air.

IF YOUR SYSTEM DOES NOT WORK, BEFORE 

REQUESTING A SERVICE CALL:

1.  Ensure thermostat is set below (cooling) or above 

(heating) room temperature and that the system lever 

is in the “COOL”, “HEAT” or “AUTO” position.

2. 

Inspect your return air filter: If it is dirty, your heat pump 

may not function properly.

3.  Check indoor and outdoor disconnect switches. 

Confirm circuit breakers are ON or that fuses have not 

blown. Reset breakers/replace fuses as necessary.

4.  Inspect the outdoor unit for clogged condenser coils, 

(grass cuttings, leaves, dirt, dust or lint). Ensure that 

branches, twigs or other debris are not obstructing the 

condenser fan.

IF YOUR SYSTEM STILL DOES NOT OPERATE, 

CONTACT YOUR SERVICING DEALER.

Be sure to describe the problem, and have the model and 

serial numbers of the equipment available.
If warranty replacement parts are required, the warranty 

must be processed through a qualified distribution location.

•  During the defrost cycle, you may notice steam rising 

from the outdoor unit. This is a normal occurrence. 

The thermostat may engage auxiliary heat during the 

defrost cycle to satisfy a heating demand; however, 

the unit will run to normal operation at the conclusion 

of the defrost cycle.

In case of extended power outage...

If the outdoor temperature is below 50°F and power to your 

outdoor unit has been interrupted for one hour or longer, 

observe the following when restoring power to your heat 

pump system.
•  Set the room thermostat selector to the “Emergency 

Heat” setting to obtain temporary heat for a minimum 

of 6 hours. This will allow system refrigerant pressures 

and temperatures enough time to return to a stabilized 

condition.

•  In Emergency Heat mode, all heating demand is 

satisfied  by  auxiliary  heat;  heat  pump  operation  is 

locked out. After a 6 hour “warm-up” period, the 

thermostat can then be switched to the “Heat” setting 

and normal heat pump operation may resume.

Thermostat Operation

The wall-mounted thermostat controls your heat pump. 

The thermostat is available in various configurations from 

different manufacturers. The information below is typical for 

most thermostats. Ask your dealer for specific information 

regarding the model of thermostat installed.

Fan Switch

In AUTO or INT (intermittent) mode, the blower operates 

only when the thermostat calls for heating or cooling. This 

mode is generally preferred when humidity control is a 

priority. 

The ON or CONT mode provides continuous indoor 

blower operation, regardless of whether the compressor or 

auxiliary heat are operating. This mode is required when 

constant air circulation or filtering is desired.

On models without a fan selection switch, the fan will cycle 

with the outdoor unit.

System Switch

Set the system switch for heating, cooling or auto 

operation. The auto mode allows the heat pump to 

automatically switch from heating mode to cooling mode to 

maintain predetermined comfort settings. Many heat pump 

thermostats are also equipped with an emergency heat 

mode which locks out heat pump operation and provides 

temporary heat supplied by the auxiliary heat.

Summary of Contents for 4SHP16LS Series

Page 1: ...local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Canadian Electrical Code Canada Compliance should be determ...

Page 2: ...ing parts 4 Handle refrigerant with caution refer to proper MSDS from refrigerant supplier 5 Use care when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living ar...

Page 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Page 4: ...24 3 8 3 4 36 3 8 7 8 48 3 8 7 8 60 3 8 1 1 8 For installations exceeding 50 refer to long line set guidelines Be extra careful with sharp bends Tubing can kink very easily and if this occurs the enti...

Page 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Page 6: ...hown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSE...

Page 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Page 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Page 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Page 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Page 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Page 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Page 13: ...OR AIR HANDLER RSBus RSBus OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM THERMOSTAT COMFORT SYNCTM ENABLED HEAT PUMP RSBus OPTIONAL OUTDOOR AIR SENSOR OPTIONAL DISCHARGE AIR SENSOR COMFORT SYNCTM ENAB...

Page 14: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Page 15: ...ocked out until power to the board is interrupted then re established or until the error is cleaned NOTE The control board ignores input from the low pressure switch terminals as follows During the TE...

Page 16: ...m the Comfort Sync thermostat must be used The complete configuration of the outdoor unit is performed using the Comfort Sync thermostat For complete details on how to integrate this unit into a Comfo...

Page 17: ...nication problem Hardware problem on the control Cycle power on control Replace if problem prevents service and is persistent Cleared 300 seconds after fault recovered E131 Corrupted control parameter...

Page 18: ...r unit blower motor dirty filters or clogged refrigerant filter Confirm that the evaporator coil is clean The alarm clears after a power rest E412 The outdoor unit pressure is above the required limit...

Page 19: ...ed by allowing the unit to run for 90 seconds before checking discharge sensor resistance If the discharge sensor resistance is not within range after 90 seconds the board will count one fault After 5...

Page 20: ...Hz Idle Mode Decimal point blinks at 1 Hz 0 5 second on 0 5 second off Display OFF Soft Disabled Top and bottom horizontal line and decimal point blink at 1 Hz Soft Disabled Top and bottom horizontal...

Page 21: ...650 pause A104 pause Outdoor Coil Temperature OCT Any time OCT is sensed in operating range value is displayed if unit is in diagnostic mode Following string is repeated if 2nd stage heat is active wi...

Page 22: ...minutes if coil temperature remains below terminate temperature or by pushing button down for less than 2 seconds Enter A test mode Display will string active error codes E ambient A coil c and disch...

Page 23: ...g procedure must be repeated Table 9 Configuring Unit Capacity Display Code Procedure Solid Pt Release push button Allows user to select type and number of stages on outdoor unit IMPORTANT Field repla...

Page 24: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Page 25: ...t may engage auxiliary heat during the defrost cycle to satisfy a heating demand however the unit will run to normal operation at the conclusion of the defrost cycle In case of extended power outage I...

Page 26: ...506860 03 Issue 1946 Page 26 of 27 4SHP16LS124 36 48 Wiring Diagrams...

Page 27: ...506860 03 Issue 1946 Page 27 of 27 4SHP16LS160...

Reviews: