background image

# 48478A006

Page 13

Cooling Cycle

Use gauge ports on suction line valve and liquid line valve for evacuating refrigerant lines and indoor coil. Use
suction gauge port to measure suction pressure during charging.

Figure 12

OUTDOOR COIL

DEFROST THERMOSTAT

EXPANSION/CHECK VALVE

BIFLOW
FILTER / DRIER

TO

R410A

DRUM

LOW

PRESSURE

HIGH

PRESSURE

COMPRESSOR

REVERSING VALVE

SUCTION
LINE
VALVE

MUFFLER

NOTE - ARROWS INDICATE

DIRECTION OF
REFRIGERANT FLOW

SUCTION

SERVICE

PORT

EXPANSION/CHECK VALVE

INDOOR UNIT

OUTDOOR UNIT

LIQUID

LINE

SERVICE

PORT

GAUGE MANIFOLD

DISTRIBUTOR

INDOOR

COIL

Low pressure gauge to suction line service valve

High pressure gauge to liquid line service valve

2. Close manifold gauge set valves. Connect the center

manifold hose to an upright cylinder of R410A.

3. If room temperature is below 70°F, set the room thermo-

stat to call for heat. This will create the necessary load
for properly charging the system in the cooling cycle.

4. Use a digital thermometer to record the outdoor

ambient temperature.

5. When the heating demand has been satisfied, switch

the thermostat to cooling mode with a set point of 68°F.
When pressures have stabilized, use a digital thermom-
eter to record the liquid and suction line temperatures.

6. The outdoor temperature will determine which charg-

ing method to use. Proceed with the appropriate
charging method.

Charge Using Weigh-In Method

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, first locate and repair any leaks then
use the weigh-in method to charge the unit.

1. Recover the refrigerant from the unit.

2. Conduct a leak check, then evacuate as previously

outlined.

3. Weigh in the charge according to the total amount

shown on the unit nameplate.

If weighing facilities are not available, use one of the
following procedures to charge the unit.

Charge Using Subcooling Method –
Outdoor Temperatures Below 65°F

When the outdoor ambient temperature is below 65°F, the
subcooling method can be used to charge the unit. It may
be necessary to restrict the air flow through the outdoor
coil to achieve pressures in the 200-250 psig range.
These higher pressures are necessary for checking the
charge. Block equal sections of air intake panels and
move obstructions sideways until the liquid pressure is in
the 200-250 psig range (see Figure 13 on page 14).

1. With the manifold gauge hose still on the liquid

service port and the unit operating stably, use a digital
thermometer to check the liquid line temperature. For
best results, use the same digital thermometer to
check both the outdoor ambient and the liquid line
temperatures.

2. At the same time, record the liquid line pressure reading.

3. Use the temperature/pressure chart (Table 5 on page 14)

to determine the saturation temperature for the liquid line
pressure reading.

Summary of Contents for 4SHP16LT Series

Page 1: ...mote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death WARNING The equipment covered i...

Page 2: ...his product has been designed and manu factured to meet ENERGY STAR criteria for energy effi ciency when matched with appropriate coil components However proper refrigerant charge and proper air flow...

Page 3: ...of the control box Connect conduit to the control box using a proper conduit fitting Units are approved for use only with copper conductors 24V Class II circuit connections are made in the low voltag...

Page 4: ...0 6 3 8 3 8 3 8 3 8 3 2 1 0 0 0 2 4 8 3 8 3 8 3 2 1 2 1 0 0 0 8 4 8 3 8 3 8 3 2 1 2 1 0 0 0 0 6 8 3 8 3 8 3 2 1 2 1 Figure 3 Thermostat Designations Some connections may not apply Refer to specific t...

Page 5: ...how to install line sets on horizontal runs Figure 6 shows how to make a transition from horizontal to vertical Figure 7 shows how to install line sets on vertical runs Brazing Connection Procedure 1...

Page 6: ...lex Liquid Line Strap Liquid Line to Vapor Line Figure 5 To hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties Strapping Material around vapor lin...

Page 7: ...an insulator preventing proper heat transfer It can also clog the thermal expansion valve reducing system performance and capacity Failure to properly flush system as explained in these instructions w...

Page 8: ...vices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 5 Remove the pressure tap valve cores from the 4SHP16LT unit s...

Page 9: ...ine to the equalizer port on the suction line and tighten to 8 ft lbs Table 3 TXV Data l e d o M t r a P r e b m u N 0 3 4 2 T L 6 1 P H S 4 1 0 V X T 4 H 6 3 T L 6 1 P H S 4 2 0 V X T 4 H T L 6 1 P H...

Page 10: ...inger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn t...

Page 11: ...e vacuum pump with vacuum gauge to the center port of the manifold gauge set 4 Open both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to a minimum of 500 microns or lo...

Page 12: ...ching indoor coil and outdoor coil with 15 line set For varying lengths of line set refer to Table 4 for If unit is equipped with a crankcase heater it should be energized 24 hours before unit start u...

Page 13: ...to use Proceed with the appropriate charging method Charge Using Weigh In Method If the system is void of refrigerant or if the outdoor ambient temperature is cool first locate and repair any leaks t...

Page 14: ...2 2 1 4 0 2 1 7 7 1 4 1 2 1 2 3 2 4 2 2 1 8 8 2 4 3 2 1 5 4 3 4 4 2 1 2 0 4 4 5 2 1 9 5 4 4 6 2 1 8 1 5 4 7 2 1 6 7 5 4 8 2 1 5 3 6 4 9 2 1 5 9 6 4 0 3 1 6 5 7 4 1 3 1 6 1 8 4 2 3 1 8 7 8 4 3 3 1 0 4...

Page 15: ...1 5 2 4 2 4 1 F 5 1 1 5 8 4 4 5 1 9 8 4 1 5 1 1 9 4 1 5 1 6 8 4 6 4 1 1 g n i t a e H t s y t i c a p a C w o L e g a t S F 0 4 7 3 3 3 9 8 2 3 8 9 9 6 3 5 7 1 5 3 3 6 F 0 5 2 2 3 7 1 1 3 3 3 8 1 1 6...

Page 16: ...ch temperature Approach Values for TXV Systems Approach value is the liquid line temperature minus the outdoor ambient temperature 1 F NOTE For best results use the same digital thermometer to check b...

Page 17: ...Strip Connections High Pressure Switch Defrost Thermostat Low Pressure Switch Reversing Valve Compressor Delay Pins Test Pins K1 Relay K2 Relay FAN DS1 L 24V P2 P5 O OUT DF Y1 OUT HI PS U1 U2 DS2 K3 R...

Page 18: ...The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is bypassed by placing the timer select jumper across th...

Page 19: ...l a n i m r e t e l u d o m t a t n e s e r p s i e g a t l o v y l p p u S P I R T d e R d n a m e d t a t s o m r e h T t n e s e r p s i 1 Y l a n g i s r o s s e r p m o c e h t t u b g n i n n u...

Page 20: ...i d n i w r o s s e r p m o C 7 e c n a t s i s e r g n i d n i w r o t o m r o s s e r p m o c k c e h C T R E L A w o l l e Y h s a l F 6 e d o C t i u c r i C t r a t S n e p O n u r n i y l n o t...

Page 21: ...o t d e t c e n n o c s i l a n i m r e t Y y f i r e V f f o n e h w C A V 5 0 w o l e b s l l a f s l i o c D E L T R E L A d n a D E L P I R T r e h t e g o t g n i h s a l f C A V 8 2 9 1 h t i w...

Page 22: ...pet urine cottonwood seeds etc Visually inspect the refrigerant lines and coils for leaks Check wiring for loose connections Check voltage at the indoor and outdoor units with units operating Check a...

Page 23: ...lean the outdoor coil with an unpressurized water hose to remove surface contaminants and debris It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are...

Page 24: ...and provides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emer gency heat mode...

Page 25: ...Fan ______________ Maximum Fuse or Circuit Breaker________________________ Electrical Connections Tight Indoor Filter Clean Supply Voltage Unit Off ________________ Indoor Blower RPM _____________ S P...

Page 26: ...SE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES LINE VOLTAGE FACTORY INSTALLED LINE VOLTAGE FIELD INSTALLED 24 VOLT FACTORY INSTALLED CLASS II VOLTAGE FIELD INSTAL...

Page 27: ...ly to you Only Warranty This written Limited Warranty is the only warranty made by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not...

Reviews: