background image

# 48478A006

Page 11

to protect the manifold gauge set from damage
caused by high pressure.)

2. With both manifold valves closed, connect the cylin-

der of R410A refrigerant. Open the valve on the
R410A cylinder (vapor only).

3. Open the high pressure side of the manifold to allow

R410A into the line set and indoor unit. Weigh in a
trace amount of R410A. (A trace amount is a maxi-
mum of 2 oz. of refrigerant or 3 lbs. pressure.) Close
the valve on the R410A cylinder and the valve on the
high pressure side of the manifold gauge set. Discon-
nect the R410A cylinder.

4. Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

When using high pressure gas such as nitrogen
for this purpose, be sure to use a regulator that
can control the pressure  down to 1 or 2 psig.

5. Adjust nitrogen pressure to 150 psig. Open the valve

on the high side of the manifold gauge set to pressur-
ize the line set and the indoor coil.

6. After a short period of time, open a refrigerant port to

make sure that an adequate amount of refrigerant has
been added for detection (refrigerant requirements will
vary with lengths). Check all joints for leaks. Purge
nitrogen and R410A mixture. Correct any leaks and
recheck.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper
piping and compressor parts.

Low pressure gauge to suction line service valve

High pressure gauge to liquid line service valve

2. Connect micron gauge.

3. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

4. Open both manifold valves and start vacuum pump.

5. Evacuate the line set and indoor unit to a minimum of

500 microns or lower. During the early stages of
evacuation, it is desirable to close the manifold gauge
valve at least once to determine if there is a rapid rise
in pressure. A rapid rise in pressure indicates a
relatively large leak. If this occurs, the leak testing
procedure must be repeated.

6. When 500 microns or lower is maintained, close the

manifold gauge valves, turn off the vacuum pump, and
disconnect the manifold gauge center port hose from
the vacuum pump. Attach the manifold gauge center
port hose to a nitrogen cylinder with pressure regulator
set to 150 psig and purge the hose. Open the manifold
gauge  valves to break the vacuum in the line set and
indoor unit. Close the manifold gauge valves.

7. Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

8. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line
set and indoor unit until 500 microns is maintained
within a 20-minute period after shutting off the
vacuum pump and closing the manifold gauge valves.

9. When the requirements above have been met,

disconnect the manifold hose from the vacuum pump.
Open the service valves to break the vacuum in the
line set and indoor unit.

Do not use a compressor to evacuate a sys-
tem. Avoid deep vacuum operation. Extremely
low vacuums can cause internal arcing and
compressor failure. Danger of equipment
damage. Damage caused by deep vacuum
operation will void warranty.

  WARNING

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument that
reads down to 50 microns.

1. Connect the manifold gauge set to the service valve

ports as follows:

Summary of Contents for 4SHP16LT Series

Page 1: ...mote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death WARNING The equipment covered i...

Page 2: ...his product has been designed and manu factured to meet ENERGY STAR criteria for energy effi ciency when matched with appropriate coil components However proper refrigerant charge and proper air flow...

Page 3: ...of the control box Connect conduit to the control box using a proper conduit fitting Units are approved for use only with copper conductors 24V Class II circuit connections are made in the low voltag...

Page 4: ...0 6 3 8 3 8 3 8 3 8 3 2 1 0 0 0 2 4 8 3 8 3 8 3 2 1 2 1 0 0 0 8 4 8 3 8 3 8 3 2 1 2 1 0 0 0 0 6 8 3 8 3 8 3 2 1 2 1 Figure 3 Thermostat Designations Some connections may not apply Refer to specific t...

Page 5: ...how to install line sets on horizontal runs Figure 6 shows how to make a transition from horizontal to vertical Figure 7 shows how to install line sets on vertical runs Brazing Connection Procedure 1...

Page 6: ...lex Liquid Line Strap Liquid Line to Vapor Line Figure 5 To hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties Strapping Material around vapor lin...

Page 7: ...an insulator preventing proper heat transfer It can also clog the thermal expansion valve reducing system performance and capacity Failure to properly flush system as explained in these instructions w...

Page 8: ...vices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 5 Remove the pressure tap valve cores from the 4SHP16LT unit s...

Page 9: ...ine to the equalizer port on the suction line and tighten to 8 ft lbs Table 3 TXV Data l e d o M t r a P r e b m u N 0 3 4 2 T L 6 1 P H S 4 1 0 V X T 4 H 6 3 T L 6 1 P H S 4 2 0 V X T 4 H T L 6 1 P H...

Page 10: ...inger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension to turn t...

Page 11: ...e vacuum pump with vacuum gauge to the center port of the manifold gauge set 4 Open both manifold valves and start vacuum pump 5 Evacuate the line set and indoor unit to a minimum of 500 microns or lo...

Page 12: ...ching indoor coil and outdoor coil with 15 line set For varying lengths of line set refer to Table 4 for If unit is equipped with a crankcase heater it should be energized 24 hours before unit start u...

Page 13: ...to use Proceed with the appropriate charging method Charge Using Weigh In Method If the system is void of refrigerant or if the outdoor ambient temperature is cool first locate and repair any leaks t...

Page 14: ...2 2 1 4 0 2 1 7 7 1 4 1 2 1 2 3 2 4 2 2 1 8 8 2 4 3 2 1 5 4 3 4 4 2 1 2 0 4 4 5 2 1 9 5 4 4 6 2 1 8 1 5 4 7 2 1 6 7 5 4 8 2 1 5 3 6 4 9 2 1 5 9 6 4 0 3 1 6 5 7 4 1 3 1 6 1 8 4 2 3 1 8 7 8 4 3 3 1 0 4...

Page 15: ...1 5 2 4 2 4 1 F 5 1 1 5 8 4 4 5 1 9 8 4 1 5 1 1 9 4 1 5 1 6 8 4 6 4 1 1 g n i t a e H t s y t i c a p a C w o L e g a t S F 0 4 7 3 3 3 9 8 2 3 8 9 9 6 3 5 7 1 5 3 3 6 F 0 5 2 2 3 7 1 1 3 3 3 8 1 1 6...

Page 16: ...ch temperature Approach Values for TXV Systems Approach value is the liquid line temperature minus the outdoor ambient temperature 1 F NOTE For best results use the same digital thermometer to check b...

Page 17: ...Strip Connections High Pressure Switch Defrost Thermostat Low Pressure Switch Reversing Valve Compressor Delay Pins Test Pins K1 Relay K2 Relay FAN DS1 L 24V P2 P5 O OUT DF Y1 OUT HI PS U1 U2 DS2 K3 R...

Page 18: ...The delay helps to protect the compressor from short cycling in case the power to the unit is interrupted or a pressure switch opens The delay is bypassed by placing the timer select jumper across th...

Page 19: ...l a n i m r e t e l u d o m t a t n e s e r p s i e g a t l o v y l p p u S P I R T d e R d n a m e d t a t s o m r e h T t n e s e r p s i 1 Y l a n g i s r o s s e r p m o c e h t t u b g n i n n u...

Page 20: ...i d n i w r o s s e r p m o C 7 e c n a t s i s e r g n i d n i w r o t o m r o s s e r p m o c k c e h C T R E L A w o l l e Y h s a l F 6 e d o C t i u c r i C t r a t S n e p O n u r n i y l n o t...

Page 21: ...o t d e t c e n n o c s i l a n i m r e t Y y f i r e V f f o n e h w C A V 5 0 w o l e b s l l a f s l i o c D E L T R E L A d n a D E L P I R T r e h t e g o t g n i h s a l f C A V 8 2 9 1 h t i w...

Page 22: ...pet urine cottonwood seeds etc Visually inspect the refrigerant lines and coils for leaks Check wiring for loose connections Check voltage at the indoor and outdoor units with units operating Check a...

Page 23: ...lean the outdoor coil with an unpressurized water hose to remove surface contaminants and debris It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are...

Page 24: ...and provides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emer gency heat mode...

Page 25: ...Fan ______________ Maximum Fuse or Circuit Breaker________________________ Electrical Connections Tight Indoor Filter Clean Supply Voltage Unit Off ________________ Indoor Blower RPM _____________ S P...

Page 26: ...SE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES LINE VOLTAGE FACTORY INSTALLED LINE VOLTAGE FIELD INSTALLED 24 VOLT FACTORY INSTALLED CLASS II VOLTAGE FIELD INSTAL...

Page 27: ...ly to you Only Warranty This written Limited Warranty is the only warranty made by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not...

Reviews: