background image

Page 8

# 48387H005

6. Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the
existing system line set and indoor coil.

7. Invert the cylinder of clean R-22 and open its valve to

allow liquid refrigerant to flow into the system through
the suction line valve. Allow the refrigerant to pass
from the cylinder and through the line set and the
indoor coil before it enters the recovery machine.

8. After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that
all of the R-22 vapor is recovered. Allow the recovery
machine to pull a vacuum on the system.

NOTE:

 A single system flush should remove all of the

mineral oil from the existing refrigerant lines and indoor
coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush. 

After each system

flush, allow the recovery machine to pull a vacuum
on the system at the end of the procedure.

9. Close the valve on the inverted R22 cylinder and the

gauge set valves. Pump the remaining refrigerant out
of the recovery machine and turn the machine off.

10. Use nitrogen to break the vacuum on the refrigerant lines

and indoor coil before removing the recovery machine,

When the low side system pressures reach 0 psig, close
the suction line valve. Disconnect all power to the
existing outdoor unit. Refer to the gauges after shutdown
to confirm that the valves are not allowing refrigerant to
flow back into the low side of the system. Disconnect the
liquid and suction lines from the existing outdoor unit.

2. Remove the existing outdoor unit. Set the new R410A

unit and follow the brazing connection procedure
outlined previously on this page to make line set
connections. 

Do not install the R410A thermal

expansion valve at this time.

3. Make low voltage and line voltage connections to the

new outdoor unit. 

Do not turn on power to the unit or

open the outdoor unit service valves at this time.

4. Remove the existing R-22 refrigerant flow control

orifice or thermal expansion valve before continuing
with flushing procedures. R-22 flow control devices
are not approved for use with R410A refrigerant and
may prevent proper flushing. Use a field-provided
fitting to reconnect the lines.

5. Remove the pressure tap valve cores from the

4SCU13LE unit’s service valves. Connect an R-22
cylinder with clean refrigerant to the suction service
valve. Connect the R-22 gauge set to the liquid line
valve and connect a recovery machine with an empty
recovery tank to the gauge set.

Figure 10

Flushing Connections

Note: The inverted R22 cylinder must contain

at least the same amount of refrigerant
as was recovered from the existing
system.

Summary of Contents for 4SCU13LE Series

Page 1: ...sk of electrical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury...

Page 2: ...e is shipped with the unit while the TXV expansion valve must be ordered separately from the manufacturer A filter drier approved for use with 410A is installed in the unit IMPORTANT This product has...

Page 3: ...coil Installation Instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage po...

Page 4: ...a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line set and or indoor coil will be used to complete the system refer to this sect...

Page 5: ...s to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordi nances based on how noisy the unit is at the neighbor s home no...

Page 6: ...por Line Figure 9 Refrigerant Line Sets Installing Vertical Runs new construction shown Outside Wall Wood Block Between Studs IMPORTANT Refrigerant lines must not contact wall Vapor Line Liquid Line W...

Page 7: ...l be sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the thermal expansion valve reducing system performance and capacity...

Page 8: ...ore removing the recovery machine When the low side system pressures reach 0 psig close the suction line valve Disconnect all power to the existing outdoor unit Refer to the gauges after shutdown to c...

Page 9: ...the piston orifice and used teflon seal Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 30 ft lbs Use backup wrench on all wrench flats Ov...

Page 10: ...wrench with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service v...

Page 11: ...r coil 6 After a short period of time open a refrigerant port to make sure that an adequate amount of refrigerant has been added for detection refrigerant requirements will vary with lengths Check all...

Page 12: ...ge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to ev...

Page 13: ...tage must be within the range listed on the unit nameplate If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling dem...

Page 14: ...Table 6 to determine the saturation temperature for the liquid line pressure reading 4 Subtract the liquid line temperature from the satura tion temperature according to the chart to determine subcoo...

Page 15: ...Minor variations in these pres sures may be expected due to differences in installa tions Significant differences could mean that the system is not properly charged or that a problem exists with some...

Page 16: ...8 7 1 3 9 3 1 6 2 3 1 4 1 5 2 3 4 3 1 4 2 3 7 3 1 4 1 3 4 3 1 5 2 3 7 3 1 4 3 3 0 3 1 F 5 9 3 6 3 2 4 1 6 7 3 2 4 1 2 7 3 6 3 1 4 7 3 9 3 1 2 6 3 5 3 1 6 8 3 9 3 1 3 8 3 3 3 1 F 5 0 1 3 1 4 4 4 1 8 2...

Page 17: ...for correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged a...

Page 18: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Page 19: ...L AND LOCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINI...

Page 20: ...ade by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to assume for it any...

Reviews: