background image

# 48387H005

Page 7

Brazing Connection Procedure

1. Cut ends of refrigerant lines square (free from nicks

or dents). Debur the ends. The pipe must remain
round; do not pinch end of line.

2. Before making line set connections, use dry nitrogen to

purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the system.

3. Use silver alloy brazing rods (5% or 6% silver alloy for

copper-to-copper brazing or 45% silver alloy for
copper-to-brass or copper-to-steel brazing) which are
rated for use with R410A refrigerant.

4.

Remove the Schrader core assemblies before brazing
to protect them from damage due to extreme heat.
Replace the cores when brazing is complete.

5. Remove light maroon washers from service valves and

shield light maroon stickers to protect them during
brazing. Wrap a wet cloth around the valve body and
copper tube stub to protect it from heat damage.

6. Braze the line set to the service valve. Quench the joints

with water or a wet cloth to prevent heat damage to the
valve core and opening port. 

The tube end must stay

bottomed in the fitting during final assembly to
ensure proper seating, sealing, and rigidity.

7. Install the factory-supplied fixed orifice (or thermal

expansion valve which is sold separately and which is
approved for use with R410A refrigerant) in the liquid
line at the indoor coil (see 

Refrigerant Metering

Device

 on page 9).

Flushing Existing Line Set and Indoor Coil

Polyol ester (POE) oils used with R410A
refrigerant absorb moisture very quickly. It is
very important that the refrigerant system be
kept closed as much as possible. DO NOT
remove line set caps or service valve stub
caps until ready to make connections.

  WARNING

When flushing existing line set and/or indoor
coil, be sure to empty all existing traps. Residual
mineral oil can act as an insulator, preventing
proper heat transfer. It can also clog the thermal
expansion valve, reducing system performance
and capacity. Failure to properly flush system as
explained in these instructions will void warranty.

  CAUTION

This procedure should not be performed on systems
which contain contaminants, such as compressor
burn out.

Required Equipment

The following equipment is needed to flush the existing
line set and indoor coil (see Figure 10 on page 8): Two
clean R22 recovery bottles, an oil-less recovery machine
with a “pump down” feature, and two sets of gauges (one
for use with R22 and one for use with R410A).

Flushing Procedure

IMPORTANT:

 The line set and/or indoor coil must be

flushed with at least the same amount of refrigerant that
previously charged the system. Check the charge in the
flushing cylinder before flushing the unit.

1. Remove existing R22 refrigerant using the appropriate

procedure.

If the existing outdoor unit is not equipped with shutoff
valves, or if the unit is not operational AND the 

existing

R22 refrigerant will be used to flush the system:

Disconnect all power to the existing outdoor unit.
Connect the existing unit, a clean recovery cylinder, and
the recovery machine according to the instructions
provided with the recovery machine. Remove all R22
refrigerant from the existing system. Refer to the
gauges after shutdown to confirm that the entire system
is completely void of refrigerant. Disconnect the liquid
and suction lines from the existing outdoor unit.

If the existing outdoor unit is equipped with manual
shutoff valves AND 

new

 R22 refrigerant will be used

to flush the system:

Start the existing R22 refrigerant system in cooling mode
and close the liquid line valve. Pump all the existing R22
refrigerant back into the outdoor unit.

(It may be necessary to bypass the low pressure
switches to ensure complete refrigerant evacuation.)

Summary of Contents for 4SCU13LE Series

Page 1: ...sk of electrical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury...

Page 2: ...e is shipped with the unit while the TXV expansion valve must be ordered separately from the manufacturer A filter drier approved for use with 410A is installed in the unit IMPORTANT This product has...

Page 3: ...coil Installation Instructions for additional wiring application diagrams and refer to unit rating plate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage po...

Page 4: ...a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line set and or indoor coil will be used to complete the system refer to this sect...

Page 5: ...s to consider when placing and installing a high efficiency outdoor unit Placement Be aware that some localities are adopting sound ordi nances based on how noisy the unit is at the neighbor s home no...

Page 6: ...por Line Figure 9 Refrigerant Line Sets Installing Vertical Runs new construction shown Outside Wall Wood Block Between Studs IMPORTANT Refrigerant lines must not contact wall Vapor Line Liquid Line W...

Page 7: ...l be sure to empty all existing traps Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the thermal expansion valve reducing system performance and capacity...

Page 8: ...ore removing the recovery machine When the low side system pressures reach 0 psig close the suction line valve Disconnect all power to the existing outdoor unit Refer to the gauges after shutdown to c...

Page 9: ...the piston orifice and used teflon seal Insert nozzle end of the expansion valve along with a new teflon seal into the distributor and tighten to 20 30 ft lbs Use backup wrench on all wrench flats Ov...

Page 10: ...wrench with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service v...

Page 11: ...r coil 6 After a short period of time open a refrigerant port to make sure that an adequate amount of refrigerant has been added for detection refrigerant requirements will vary with lengths Check all...

Page 12: ...ge hose from the cylinder Open the manifold gauge valves to release the nitrogen from the line set and indoor unit 8 Reconnect the manifold gauge to the vacuum pump turn the pump on and continue to ev...

Page 13: ...tage must be within the range listed on the unit nameplate If not do not start equipment until the power company has been consulted and the voltage condition corrected 6 Set thermostat for cooling dem...

Page 14: ...Table 6 to determine the saturation temperature for the liquid line pressure reading 4 Subtract the liquid line temperature from the satura tion temperature according to the chart to determine subcoo...

Page 15: ...Minor variations in these pres sures may be expected due to differences in installa tions Significant differences could mean that the system is not properly charged or that a problem exists with some...

Page 16: ...8 7 1 3 9 3 1 6 2 3 1 4 1 5 2 3 4 3 1 4 2 3 7 3 1 4 1 3 4 3 1 5 2 3 7 3 1 4 3 3 0 3 1 F 5 9 3 6 3 2 4 1 6 7 3 2 4 1 2 7 3 6 3 1 4 7 3 9 3 1 2 6 3 5 3 1 6 8 3 9 3 1 3 8 3 3 3 1 F 5 0 1 3 1 4 4 4 1 8 2...

Page 17: ...for correct voltage at unit with unit operating 6 Check amp draw outdoor fan motor Unit nameplate _________ Actual _________ NOTE If owner complains of insufficient cooling the unit should be gauged a...

Page 18: ...nician ________________________________________ Nameplate Voltage ______________ Rated Load Ampacity ________ Compressor _______________ Outdoor Fan ___________________ Maximum Fuse or Circuit Breaker...

Page 19: ...L AND LOCAL CODES OUTDOOR FAN F C H 1 2 3 R S C C 2 3 1 EQUIPMENT GROUND HR1 L2 208 230 60 1 L1 K1 1 BLACK YELLOW RED RED C12 BLACK ORANGE B4 PURPLE K1 S4 S24 A4 C Y1 TO 24 VAC POWER SOURCE 20 VA MINI...

Page 20: ...ade by the warrantor this warranty is in lieu of and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to assume for it any...

Reviews: