background image

506318-01

Page  4  of  17

Issue  0946

Installation of Line Sets

DO NOT fasten liquid or suction lines in direct contact

with the floor or ceiling joist.  Use an insulated or suspension
type of hanger.  Keep both lines separate, and always
insulate the suction line.  Long liquid line runs (30 feet or
more) in an attic will require insulation.  Route refrigeration
line sets to minimize length.

DO NOT let refrigerant lines come in direct contact with

foundation.  When running refrigerant lines through the
foundation or wall, openings should allow for a sound and
vibration absorbing material to be placed or installed
between tubing and foundation.  Any gap between
foundation or wall and refrigerant lines should be filled with
a vibration damping material.

  

CAUTION

If ANY refrigerant tubing is buried, provide a 6 inch vertical
rise at service valve.  Refrigerant tubing lengths up to 36
inches may be buried without further special
consideration.  For lengths above 36 inches, consult your
local distributor.

Before making braze connections, be sure all joints are

clean.  Before heat is applied for brazing, dry nitrogen should
be flowing through the tubing to prevent oxidation and scale
formation on the inside of the tubing.

The following is the recommended method for making

braze connections at the refrigerant line connections:

1.

Debur and clean refrigerant tube end with emery
cloth or steel brush.

2.

Insert tubing into swage fitting connection.

3.

Wrap wet rags over valves to protect from heat.

4.

Allow dry nitrogen to flow through refrigerant lines.

5.

Braze joint, using a suitable brazing alloy for copper
to copper joints.

6.

Quench the joint and tubing with water using a wet
rag.  Leave rag on fitting body and re-wet with water
to help cool area.

Leak Check

Refrigeration lines and indoor coil must be checked for

leaks after brazing and before evacuation.  The
recommended procedure is to apply a trace amount of vapor
refrigerant (approximately two ounces or 3 psig) into the
line set and indoor coil, then pressurize with 150 psig of dry
nitrogen.  Use a refrigerant leak detector to check all joints.
The system may also be checked for leaks using a halide
torch or pressure and soapy solution.  After completion of
leak check, relieve all pressure from system before
evacuation.

Evacuating And Charging Instructions
NOTE: Intentional release of CFC or HCFC refrigerant
to the atmosphere violates Federal Law.  It may also
violate State and Local Codes.  Check all Federal, State
and Local Codes before proceeding.

These outdoor units are pre-charged at the factory with

adequate refrigerant to handle 

15 feet

 of refrigerant tubing.

NOTE:

DO NOT use any portion of the charge for purging

or leak testing.  It is mandatory that a thorough evacuation
of the refrigeration lines and indoor coil be performed.

The liquid line and suction line service valves have been

closed after final testing at the factory.  

DO NOT disturb

these valves until the lines have been leak checked and
evacuated or the charge in the unit may be lost.

1.  Connect the vacuum pump to the center hose of the

manifold gauge set, the low-pressure manifold gauge to the
vapor service valve and the high pressure manifold gauge
to the liquid service valve.

NOTE:

Unnecessary  switching of hoses can be avoided

and complete evacuation of all lines can be achieved by
also connecting a branch hose from the manifold gauge
center port to a cylinder of the proper refrigerant.  Provide a
separate shut-off valve to vacuum pump to avoid
contaminating vacuum pump oil with refrigerant.

2.

The valves should be kept in the “front seated”

(closed) position.  This will allow evacuation of the
refrigeration lines and the indoor coil, without disturbing the
factory charge in the outdoor unit.

3.

Follow the vacuum pump manufacturer ’s

instructions.  Allow the pump to operate until the system
has been evacuated down to 300 microns.  Allow the pump
to continue running for an additional 15 minutes.  Turn OFF
the pump and leave the connections secured to the two (2)
service valves.  After 5 minutes, if the system fails to hold
500 microns or less, check all connections for tight fit and
repeat the evacuation procedure.

4.

Isolate the vacuum pump from the system by

closing the shutoff valves on the gauge-set.  Disconnect
the vacuum pump.

Opening Service Valves

After evacuation of the connecting lines, remove the

service valve cap and fully insert the hex wrench into the
stem.  A back-up wrench is required on the valve body to
open the valve stem.  Back-out counterclockwise until the
valve stem just touches the coined edge.

Wrench sizes:

3/8 service valve:  3/16" Hex wrench
3/4 service valve:  5/16" Hex wrench
7/8 service valve:  5/16" Hex wrench

Summary of Contents for 4HP13

Page 1: ...T SYSTEM Time Temp 7 DEFROST SYSTEM Demand Defrost 8 SINGLE PHASE WIRING DIAGRAM 13 SEER 14 SINGLE PHASE WIRING DIAGRAM 14 SEER 15 HOMEOWNER S INFORMATION 16 Improper installation adjustment alteration service or maintenance will void the warranty The qualified installer or agency must use factory authorized kits or accessories when added to this products Refer to the individual instructions inclu...

Page 2: ...se in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away form windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure...

Page 3: ...refrigerant line lengths DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 ...

Page 4: ...ressure from system before evacuation Evacuating And Charging Instructions NOTE Intentional release of CFC or HCFC refrigerant to the atmosphere violates Federal Law It may also violate State and Local Codes Check all Federal State and Local Codes before proceeding These outdoor units are pre charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing NOTE DO NOT use a...

Page 5: ...xtend wires from disconnect through power wiring hole provided and into unit control box Flexible conduit is required for the swing out control box feature WARNING ELECTRICAL SHOCK HAZARD Turn OFF electric power before connecting unit performing any maintenance or removing panels or doors More than one disconnect may be required to turn off all power FAILURE TO DO SO COULD RESULT IN BODILY INJURY ...

Page 6: ...line sets longer than 15 feet add charge Oil charge is sufficient for all line lengths Before final adjustment is made to the refrigerant charge it is imperative that proper indoor airflow be established Airflow will be higher across a dry coil versus a wet coil Blower charts are calculated with a dry or wet coil basis Recommended airflow is 350 450 CFM per ton 12 000 Btuh through a wet coil Refer...

Page 7: ...st when the liquid line warms up to 60 F Defrost Control The defrost control board includes the combined functions of a time temperature defrost control defrost relay diagnostic LEDs and terminal strip for field wiring connections The control provides automatic switching from normal heating operation to defrost mode and back During compressor cycle the control accumulates compressor run times at 3...

Page 8: ...ond start up period and for the first 90 seconds each time the reversing valve switches heat cool modes If the TEST pins are jumpered and the 5 minute delay is being by passed the LO PS terminal signal is not ignored during the 90 second start up period DEMAND DEFROST SYSTEM DESCRIPTION The demand defrost controller measures differential temperatures to detect when the system is performing poorly ...

Page 9: ...set by cycling OFF the 24 volt power to the control board or by shorting the TEST pins between 1 and 2 seconds All timer functions run times will also be reset If a pressure switch opens while the Y1 Out line is engaged a 5 minute short cycle will occur after the switch closes DEFROST SYSTEM SENSORS Sensors connect to the defrost board through a field replaceable harness assembly that plugs into t...

Page 10: ...wer R must be cycled OFF or the TEST pins on board must be shorted between 1 to 2 seconds to reset the board Defrost Temperature Termination Shunt Jumper Pins The defrost board selections are 50 70 90 and 100 F 10 21 32 and 38 C The shunt termination pin is factory set at 50 F 10 C If the temperature shunt is not installed the default termination temperature is 90 F 32 C DELAY MODE The defrost boa...

Page 11: ...s of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable system temperatures during the 20 minute calibration period If the board fails to calibrate another defrost cycle will be initiated after 45 minutes of heating mode compressor run time Once the defrost board is calibrated it initiates a dem...

Page 12: ...506318 01 Page 12 of 17 Issue 0946 ...

Page 13: ...Page 13 of 17 506318 01 Issue 0946 Defrost Control Board Diagnostic LEDs ...

Page 14: ...506318 01 Page 14 of 17 Issue 0946 H P 13 SINGLE PHASE WIRING DIAGRAM ...

Page 15: ...Page 15 of 17 506318 01 Issue 0946 H P 14 SEER WIRING DIAGRAM ...

Page 16: ...ate drain of the cooling coil Thermostat Operation The wall mounted thermostat controls your air condi tioner The thermostat is available in various configurations from different manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat installed Temperature Setting Levers Most heat pump thermostats have 2 tempera...

Page 17: ...ryers and fall off from trees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT...

Reviews: