background image

506318-01

Page  6  of  17

Issue  0946

Heat Pump Application with Electric Heat

Emergency Heat (heating heat pump)

If selector switch on thermostat is set to the emergency
heat position, the heat pump will be locked out of the heating
circuit, and all heating will be electric heat ( if applicable).  A
jumper should be placed between W and E on the
thermostat so that the electric heat control will transfer to
the first stage heat on the thermostat.  This will allow the
indoor blower to cycle on and off with the electric heat when
the fan switch is in the AUTO position.

*  Add Jumper on Subbase (Optional)

Start-Up Procedure

1. Check to ensure:

!

Service valve and gage port caps are installed and
tightened.

!

Voltage supply at unit agrees with nameplate rating.

!

Field wiring connections are tight and factory wiring
has not been disturbed and are tight.

!

Indoor fan motor is on correct speed tap.

2. Set thermostat selector switch to OFF and fan control

switch to “Auto” is so equipped.

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature.  Be sure

set point is below indoor ambient temperature.

5. Set the system switch of the thermostat on COOL (or

HEAT if applicable) and fan switch for continuous
operation (ON) or AUTO, as desired.  There will be a 5
minute short cycle compressor delay on startup.  Operate
unit for 15-20 minutes, then check the system refrigerant
charge.

6. Adjust refrigerant charge per “Adjusting Charge” section.

Adjusting Charge

Factory charge is shown on the rating label located on

the access panel.

All split  system  heat pumps are  factory charged

for 15 feet of connecting line set and matched indoor
fan coil. 

 Nameplate refrigerant charge should initially be

adjusted for line set lengths other than 15 feet.  For line
sets shorter than 15 feet in length, remove charge.  For line
sets longer than 15 feet, add charge.  Oil charge is sufficient
for all line lengths.

Before final adjustment is made to the refrigerant charge,

it is imperative that proper indoor airflow be established.
Airflow will be higher across a dry coil versus a wet coil.
Blower charts are calculated with a 

dry or wet coil

 basis.

Recommended airflow is 

350-450 CFM per ton

 (12,000

Btuh) through a 

wet coil

.  Refer to indoor unit instructions

for methods of determining air flow and blower performance.

All heat pump units are only rated with TXV installed on

indoor coil.

The optimum method for checking the charge is by

weight.  However the following methods may be used
to confirm the proper charge:

Cooling Mode:

1. Operate unit a minimum of 10 minutes before

checking charge.

2. Measure liquid service valve pressure by attaching

an accurate gage to service port.  Determine
saturation temp. from T/P chart.

3. Measure liquid line temperature by attaching an

accurate thermistor type or electronic thermometer
to liquid line near outdoor coil.

4. Calculate subcooling (saturation temp.  measured

temp.) and compare with table on back of central
box cover.

5. Add refrigerant if subcooling is lower than table.

Recover refrigerant if subcooling is high.

6. If ambient temp is lower than 60°F, check charge in

heating mode or weigh refrigerant according to
name plate data.

Heating Mode

:

Check charge in heating mode if ambient temp is below

60° F.  Indoor temp must be between 65° and 75° F.

Follow steps (1) to (6) above and compare with heating

mode subcooling range on the table on back of central box
cover.

Charge must be rechecked again during the cooling

season.

Cold Weather Application

A cold weather accessory kit may be required for heat

pumps operating at ambient conditions below 25°F.
Supplemental heat should be provided for these conditions
due to the expected performance degeneration.

Refrigeration Charge Adjustment

Liquid Line Diameter

Oz. Per Linear Foot *

3/8”

.6

* Factory charge for series is for 15’ (ft.) line sets

   and matched fan coil.

Summary of Contents for 4HP13

Page 1: ...T SYSTEM Time Temp 7 DEFROST SYSTEM Demand Defrost 8 SINGLE PHASE WIRING DIAGRAM 13 SEER 14 SINGLE PHASE WIRING DIAGRAM 14 SEER 15 HOMEOWNER S INFORMATION 16 Improper installation adjustment alteration service or maintenance will void the warranty The qualified installer or agency must use factory authorized kits or accessories when added to this products Refer to the individual instructions inclu...

Page 2: ...se in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away form windows patios decks etc where unit operation sounds may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to capacity of unit 3 Run refrigerant tubes as directly as possible by avoiding unnecessary turns and bends 4 Leave some slack between structure...

Page 3: ...refrigerant line lengths DO NOT LOCATE THE UNIT On brick concrete blocks or unstable surfaces Near clothes dryer exhaust vents Near sleeping area or near windows Under eaves where water snow or ice can fall directly on the unit with clearance less than 2 ft from a second unit with clearance less than 4 ft on top of unit Operating Ambient The minimum outdoor operating ambient in cooling mode is 55 ...

Page 4: ...ressure from system before evacuation Evacuating And Charging Instructions NOTE Intentional release of CFC or HCFC refrigerant to the atmosphere violates Federal Law It may also violate State and Local Codes Check all Federal State and Local Codes before proceeding These outdoor units are pre charged at the factory with adequate refrigerant to handle 15 feet of refrigerant tubing NOTE DO NOT use a...

Page 5: ...xtend wires from disconnect through power wiring hole provided and into unit control box Flexible conduit is required for the swing out control box feature WARNING ELECTRICAL SHOCK HAZARD Turn OFF electric power before connecting unit performing any maintenance or removing panels or doors More than one disconnect may be required to turn off all power FAILURE TO DO SO COULD RESULT IN BODILY INJURY ...

Page 6: ...line sets longer than 15 feet add charge Oil charge is sufficient for all line lengths Before final adjustment is made to the refrigerant charge it is imperative that proper indoor airflow be established Airflow will be higher across a dry coil versus a wet coil Blower charts are calculated with a dry or wet coil basis Recommended airflow is 350 450 CFM per ton 12 000 Btuh through a wet coil Refer...

Page 7: ...st when the liquid line warms up to 60 F Defrost Control The defrost control board includes the combined functions of a time temperature defrost control defrost relay diagnostic LEDs and terminal strip for field wiring connections The control provides automatic switching from normal heating operation to defrost mode and back During compressor cycle the control accumulates compressor run times at 3...

Page 8: ...ond start up period and for the first 90 seconds each time the reversing valve switches heat cool modes If the TEST pins are jumpered and the 5 minute delay is being by passed the LO PS terminal signal is not ignored during the 90 second start up period DEMAND DEFROST SYSTEM DESCRIPTION The demand defrost controller measures differential temperatures to detect when the system is performing poorly ...

Page 9: ...set by cycling OFF the 24 volt power to the control board or by shorting the TEST pins between 1 and 2 seconds All timer functions run times will also be reset If a pressure switch opens while the Y1 Out line is engaged a 5 minute short cycle will occur after the switch closes DEFROST SYSTEM SENSORS Sensors connect to the defrost board through a field replaceable harness assembly that plugs into t...

Page 10: ...wer R must be cycled OFF or the TEST pins on board must be shorted between 1 to 2 seconds to reset the board Defrost Temperature Termination Shunt Jumper Pins The defrost board selections are 50 70 90 and 100 F 10 21 32 and 38 C The shunt termination pin is factory set at 50 F 10 C If the temperature shunt is not installed the default termination temperature is 90 F 32 C DELAY MODE The defrost boa...

Page 11: ...s of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable system temperatures during the 20 minute calibration period If the board fails to calibrate another defrost cycle will be initiated after 45 minutes of heating mode compressor run time Once the defrost board is calibrated it initiates a dem...

Page 12: ...506318 01 Page 12 of 17 Issue 0946 ...

Page 13: ...Page 13 of 17 506318 01 Issue 0946 Defrost Control Board Diagnostic LEDs ...

Page 14: ...506318 01 Page 14 of 17 Issue 0946 H P 13 SINGLE PHASE WIRING DIAGRAM ...

Page 15: ...Page 15 of 17 506318 01 Issue 0946 H P 14 SEER WIRING DIAGRAM ...

Page 16: ...ate drain of the cooling coil Thermostat Operation The wall mounted thermostat controls your air condi tioner The thermostat is available in various configurations from different manufacturers The information below is typical for most thermostats Ask your dealer for specific information regarding the model of thermostat installed Temperature Setting Levers Most heat pump thermostats have 2 tempera...

Page 17: ...ryers and fall off from trees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT...

Reviews: