ARITERM SWEDEN AB 

 ARITERM OY

 

• Asennus ja käyttöohje • Installation och driftanvisning • Installation and operating instruction • 19.11.2009 • 12/32

 

MENU STRUCTURE

The following tables give an overview of the messages that may appear on the display of the 
control unit.  They also indicate which parameters the user is allowed to change freely and 
which parameters he/she is allowed to change only if instructed to do so by an authorised in-
staller. NOTE! Part of the menu options are displayed only when they are active.

Menu

Setting

Description

Temperature 

  Boiler xx (80) °C

5-95°C

Boiler temperature, set temperature in brackets.

Flue gas xx (250) °C

120-280°C

Flue gas temperature, alarm limit in brackets.

Burner Off (On) mode

On/Off

Burner start-up and stop. Burner operating 

mode below.

Residual oxygen x.x%

-

Displays the amount of residual oxygen while 

the burner is in Maintain mode (Accessory)

Auger, external 

manual operation Off (On)

On/Off

External auger start-up (visible if the burner is 

in Off mode). The remaining operating time is 

shown in brackets.

Heating

Pellets
P electricity
Electricity

Heating method selection (visible if the electrical 

resistances are being used and the burner is in 

On mode - see "Burner Settings").

Outdoor xx°C / Temperature 

xx(xx) °C / Room xx(xx) °C

Room 0-30°C

Temperature display of heat regulation circuits 

(visible if activated from the Accessories menu). 

Fine adjustment

0-20 °C

Fine adjustment of heating circuit 1 (visible if 

activated from the Accessories menu and if the 

internal sensor is not connected)

Menus

-

Accessing submenus: Burner Adjustments, Ope-

rating Time, Pellet Store, Power, Heat Regulati-

on, Service.

 

Main menu

Menu

Setting

Description

Electrical resistances 

0-3

Activation of electrical resistances
0 = not in use, 
1 = 6 kW
3 = 9 kW

Activation difference

10-40 °C

Activation temperature of electrical resistances.

Level switch 99% (50%)

10-90%

Displays the pellet level between the level swit-

ches of the burner.

Flame detection 99% 

(50%)

1-98%

Displays the flame strength.
Limit value in brackets.

Testing

-

The burner functions (e.g., auger burner, blower, 

etc.) can be tested in the menu.

Language Finnish

Suomi, Svenska, English, Ger-

man, Italiano

Menu language selection

Factory settings v090824

Yes / No

Restores the original factory settings.

Temperature differen-

ce No

No, 5-60°C

Burner operating lag time. The burner moves to 

Maintain mode at the target temperature and 

restarts when the temperature has decreased by 

an amount equal to the lag time.

Accessories

-

The menu can be used to take accessories into 

use.

 

Burner Adjustments menu

Text on the display

Setting

Description

Total xx h

-

Burner total operating time in Power mode.

Max xx h

-

Burner operating time at Max power.

Mean xx h

-

Burner operating time at Mean power.

Min xx h

-

Burner operating time at Min power.

Operating time electrical 

resistance 1

-

Operating time of the 6 kW electrical resistance.

Operating time electrical 

resistance 2

-

Operating time of the 3 kW electrical resistance

 

Operating Time menu

Summary of Contents for Biomatic+

Page 1: ... Ariterm Biomatic INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ...ered in a wooden frame The base is a platform from which the boiler can be safely lifted The package should be unwrapped as close to the installation site as possible The factory has insured the boiler against damage during transport from the factory to the first in termediate storage site It is important for the person who receives the boiler to verify the state of the boiler before its acceptanc...

Page 3: ...nce MMJ 5x1 5s 9 kW resistance MMJ 5x2 5s 6 kW resistance 3x10 A 9 kW resistance 3x16 A Burner ignition 500 W Burner normal 40 W 6 kW resistance about 7 kW depending on equipment 9 kW resistance about 10 kW depending on equipment TECHNICAL DATA ARITERM BIOMATIC Standard delivery Four way mixing valve ESBE TM 20 Sweeping gear Dirt trap Brick support Flue duct joint Shunt motor ESBE ARA661 3 point S...

Page 4: ...d in the lower part of the boiler Ash can also be removed into a special ash pan by means of an ash trap or a common vacuum cleaner However the ash may still be hot Therefore the ash trap must be heat resistant Standard equipment includes an automatic heat regulation system that adjusts the sup ply water temperature according to the tem perature outside For safety reasons the pellet heating centre...

Page 5: ...ce BURNER OPERATING PRINCIPLE Green The burner is on Red Alarm the burner is off Blinking light Warning light do not turn the burner off Arrow keys browsing menus changing set values C button exiting menus acknowledging warnings Enter button selecting settings accepting set values 1 Inner circulation pump switch 2 Inner circulation pump fuse 3 Display 4 Over heating sensor 5 Main switch 6 Operatio...

Page 6: ...ing the boiler the following should be checked the heating network and the boiler are full of water pressure at least 0 5 bar air is removed from the internal circulation pump through the venting screw located in the pump head the flue damper if any is open the circulation damper located in the convection part of the boiler is in place the circulation pump is running the network valves are open th...

Page 7: ...HEATING RADIATOR HEATING 3 CONNECTION SET OF THE ADDITIONAL HEATING CIRCUIT RADIATOR HEATING 4 HEAT PIPE PUMP FLOOR HEATING 5 HEAT PIPE PUMP RADIATOR HEATING 6 FLOOR HEATING NETWORK MANIFOLDS 7 RADIATOR HEATING NETWORK 8 EXPANSION VESSEL 9 SERVICE SHUT OFF VALVE 10 SAFETY VALVE 11 FILLING VALVE 12 FEED MIXING VALVE 13 DOMESTIC WATER CIRCULATION PUMP PIPE INSTALLATIONS VW CW DW ...

Page 8: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 8 32 WIRING DIAGRAM ...

Page 9: ...on When starting directly from phase 7K the burner stops for 10 minutes in order for the combustion process to normalise in the burner head If the flame does not ignite after phase 7K the burner gives a cold start alarm as described in Troubleshooting Do not change the settings during a cold start After cleaning the burner head make sure that the burner performs a cold start because there are no e...

Page 10: ...ternal storage auger When the pellet surface drops below the level switches the external auger activates factory setting 30 s The operating time of the external auger should be long enough for the pellet surface to rise to the level of the burner up per connection Time can be adjusted from Auger External in the Power menu If the time is too long the pellets rise to the drop pipe level In this case...

Page 11: ...ES ADJUSTMENT MAIN MENU High fan Low auger Low fan Min auger Min fan High auger Cleaning fan Holding time Auger external Manual Warmstart amount Coldstart amount POWER SETUP Drop2 Drop Fan Auger burner Ignition El step Shuntvalve Auger external Ash auger TEST OUTPUTS Conv cleaning Alarm Run message Cirkulation pump Flow water max Curve comp 5 Curve comp 0 Curve comp 5 Curve Cleaning Ash removal HE...

Page 12: ...ment 0 20 C Fine adjustment of heating circuit 1 visible if activated from the Accessories menu and if the internal sensor is not connected Menus Accessing submenus Burner Adjustments Ope rating Time Pellet Store Power Heat Regulati on Service Main menu Menu Setting Description Electrical resistances 0 3 Activation of electrical resistances 0 not in use 1 6 kW 3 9 kW Activation difference 10 40 C ...

Page 13: ...ts clean Ember maintenance 60 min No 0 120 min Time between ember maintenance cycles The auger burner carries out a 1 minute feeding cycle while the burner is in Maintain mode No The burner does not maintain the embers In this case the burner always performs a cold start when starting up To be used for example with an accumulator Auger external 30 s 0 250 s Operating time of the external auger whe...

Page 14: ...p setting Heating circuit 1 may also be equipped with an indoor tempera ture sensor The indoor temperature can be set to a certain value The temperature graph can be fine adjusted in order to reach this value The room coefficient can be used to determine the supply water correction coefficient in order for the indoor temperature to reach the set value The factory setting is 2 ºC In other words if ...

Page 15: ...pensation The graph can be compensated when the outdoor temperature is 5 ºC 0 ºC and 5 ºC In this case the air may be breezy and humid If so the temperature graph might have to be changed Compensation also affects the temperature graph of heating circuit 2 in the same way Circulation pump control The Circulation Pump Stop function can be used to determine the outdoor temperature at which the pump ...

Page 16: ...ndicative and fine adjustment might be required Floor heating system A thermostat is installed in the circulation pump control of the heating circuit The thermostat switches the pump control off if the supply water temperature rises above 45 ºC If the supply water temperature is too high this may damage parquet floor If when the outdoor temperature is below 0 ºC the room temperature is too low sli...

Page 17: ... 2 Ember maintenance time Power menu 1 Check the flame detection system as specified above 2 Check the embers while being in Maintain mode Excessive draught may burn the embers completely In this case reduce the draught and the time of the Ember Maintenance setting If the alarm has been given af ter cleaning the burner head increase the set temperature of boiler water temporarily in order for the ...

Page 18: ...fuel must be removed if it gets stuck in the blocking feeder or in one of the feeding augers Remove the upper connection and take out the possible fo reign object from the feeding auger or blocking feeder ALARMS AND TROUBLESHOOTING Alarm message Cause Check that Procedure Alarm heat sensor The boiler water temperature sensor is detached the boiler sensor is in place and the wi res are intact If th...

Page 19: ...ied out Ariterm Oy is not liable for damages occurred after the expiration of the guarantee period However compensation for such damages may be separately agreed on a case by case basis Decommissioning An end of life boiler is suitable for scrapping Its plastic parts are landfill waste Product no Description 1163 Overheat protection EGO 55 33412 010 1774 Gasket 2x183x200 burner 5660 Grundfos UPS 2...

Page 20: ... convection pipes with the cleaning brush delivered with the boiler see the next page Finally empty the ash box The ash from the ash box can be used to deter mine whether combustion has been good The ash should be powdery The interval for ash removal and boiler cleaning can be specified in the Service menu on the basis of experience The boiler should be cleaned when the temperature of flue gases r...

Page 21: ... maintenance work Other boiler cleaning operations Ash box emptying Flue duct cleaning Convection channel cleaning 2 times a year Combustion chamber cleaning as needed Convector cleanout hatch Clean the flame detector of impurities NOTE If the protective glass of the flame detector breaks or detaches the flame detector can no longer be used and must be replaced with a new one Remove all ash and po...

Page 22: ...d material must be continuously removed from the burner head Fuel storage Thanks to the feeding system it is possible to build the pellet store for so called bulk deliveries The store can be placed either inside or in a separate building outside the house The shorter the transport distance from the store to the burner the better the feeding system functions Fire regulations must be taken into cons...

Page 23: ...itres and its filling is facilitated by the intermediate grid in the silo Contrary to the figure the silo is delivered with a lid NOTE More information on the installation of PS300 Feedo can be found in separate manuals Depo Feed chute Depo is a patented pellet transfer system that effectively reliably and quietly feeds pellets from the silo via the feeding system to the burner Feedo Feedo is a pe...

Page 24: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 24 32 DECLARATION OF CONFORMITY ...

Page 25: ...stallation the burner must be adjusted using a flue gas analyser In order to use each power range press the Plus key in the On Off menu for more than 8 seconds This way the max mean and min powers can be selected manually To go back to normal position press the Minus key once NOTE In this function the burner does not stop when the boiler water reaches the set value Boiling risk If these installati...

Page 26: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 26 32 NOTES ...

Page 27: ...NOTES ...

Page 28: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 28 32 NOTES ...

Page 29: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 29 32 NOTES ...

Page 30: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 30 32 NOTES ...

Page 31: ...ARITERM SWEDEN AB ARITERM OY Asennus ja käyttöohje Installation och driftanvisning Installation and operating instruction 19 11 2009 31 32 NOTES ...

Page 32: ...ARITERM OY P O BOX 59 Uuraistentie 1 43101 Saarijärvi Telephone 358 0 14 426 300 Telefax 358 0 14 422 203 www ariterm fi ...

Reviews: