MENU STRUCTURE
Store menu
pellet store and consumption monitoring
Text on the display
Setting
Description
Estimated time xx days
Displays the amount of pel-
let fuel remaining in the sto-
re. A new value can be set
in connection with a change
in the pellet store.
Displays how many days the pellets in the store will last
at the average consumption level in question.
Pellet store x.x t
0.0-25.0 t
Displays the amount of pellet fuel remaining in the sto-
re. A new value can be set when reloading the pellet
store.
Feeding rate xx kg/h
0-76.0 kg/h
Feeding capacity of the storage auger.
Average consumption
kg/day
-
Displays the average consumption during the last 8
days.
Overall consumption
x.x t
-
Displays the overall consumption of pellets.
Auger external time
-
Displays the operating time of the external auger
Alarm store min x.x t
0.0-3.0 t
A warning appears on the display when the calculated
amount of pellet fuel left in the store is equal to the set
minimum level
Menu
Setting
Description
Burner type 20 kW
12/15/20/25/30 kW
Burner type selection. Select your own burner
type. Note! Restore the factory values also for
the settings related to heat regulation.
Power
Max auger 50%
Max blower 40%
Mean auger 50%
Mean blower 40%
Min auger 0%
Min blower 0%
0-100%
0-100%
0-100%
0-100%
0-100%
0-100%
Auger burner operating cycle at Max power.
Blower power at Max power
Auger burner operating cycle at Mean power
Blower power at Mean power
Auger burner operating cycle at Min power.
Blower power at Min power
Cleaning blow 2/h
Off, 2/h, 1/h, 1/2h, 1/3h
In Power mode, the blower goes to 100% power
and keeps the air vents clean.
Ember maintenance 60 min
No, 0-120 min
Time between ember maintenance cycles. The
auger burner carries out a 1-minute feeding
cycle while the burner is in Maintain mode.
No = The burner does not maintain the embers.
In this case, the burner always performs a cold
start when starting up. To be used, for example,
with an accumulator.
Auger, external 30 s
0-250 s
Operating time of the external auger when the
level switches
ask for pellets (see "Adjustment Example").
Manual operation 15 min
0-60 min
Operating time of the external auger during ma-
nual operation
(the burner
must be in Off mode, start-up from the main
menu)
Hot starts
0-
Number of hot starts
Cold starts
0-
Number of cold starts
Cold start settings
0-99
Power Adjustment menu
Menu
Setting
Description
Alarm
Ash removal x (100) h
0-250 h
Gives an alarm indicating that the ash box must be emptied (calcu-
lated from the operating time of the external auger). To be deter-
mined on the basis of experience.
Cleaning x (100) h
0-250 h
Gives an alarm indicating that the boiler and burner head must be
cleaned. To be determined on the basis of experience.
Service menu
The feeding rate of the storage auger can be determined, for example, by driving the storage au-
ger for 10 minutes and by measuring the weight of the pellets which arrived at the vessel. Mul-
tiplying this by six gives how many kilograms the storage auger brings in an hour (kg/h). The
feeding rate may vary according to pellet quality.
The Pellet Store setting is used to determine the amount of pellet fuel in the store. The au-
tomatic equipment calculates the consumption of pellets on the basis of the feeding rate and
operating time of the external auger. In addition, it estimates whether the amount of pellet fuel
will suffice for one day on the basis of average consumption.
The Alarm Store Min setting is used to determine the limit at which a message warning about
the termination of pellets appears on the burner screen.