1X-X3E Series Operation 
Manual 

P/N 501-419303-2-10 • REV 01 • ISS 17MAR14 

Summary of Contents for 1X-X3E Series

Page 1: ...1X X3E Series Operation Manual P N 501 419303 2 10 REV 01 ISS 17MAR14 ...

Page 2: ...other relevant provisions of Directive 1999 5 EC 2002 96 EC WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info 2006 66 EC batt...

Page 3: ...lity ii Introduction 1 Control panel overview 3 The user interface 3 Operator controls and indicators 4 Audible indicators 11 Control panel status indications 11 Control panel operation 18 User levels 18 Public user level operation 18 Operator user level operation 20 Maintenance 28 Regulatory information 29 ...

Page 4: ...r any lost profits or business opportunities loss of use business interruption loss of data or any other indirect special incidental or consequential damages under any theory of liability whether based in contract tort negligence product liability or otherwise Because some jurisdictions do not allow the exclusion or limitation of liability for consequential or incidental damages the preceding limi...

Page 5: ...ons for a single extinguishing area If a fire detection zone is not configured as part of the extinguishing detection area the control panel provides standard fire panel functionality for that fire detection zone For example the panel activates fire sounders fire routing and other auxiliary outputs Note Consult your system installer for configuration details about the fire zones that have been ass...

Page 6: ... alarm state or a start extinguishing manual call point was pressed In this state extinguishing sounders are activated Normally your system installer will have configured an intermittent tone If the extinguishing activation alarm is not cancelled by pressing an abort extinguishing manual call point or paused by pressing a hold extinguishing manual call point the system proceeds to the extinguishin...

Page 7: ...ing Fault LED 12 Service Detector LED 13 Expansion I O Fault Disabled LED 14 General Disable button and LED 15 General Test button and LED 16 Low Pressure LEDs 17 Extinguishing Agent Flow LEDs 18 Reset button and LED 19 Panel Silence button and LED 20 Fire Sounders Start Stop button and LED 21 Numeric keypad and Enter button 22 Manual Mode button and LED 23 System Fault LED 24 Out of Service LED 2...

Page 8: ...1 Zone buttons and LEDs Z1 Z2 Z3 Red Yellow Disables or tests a zone when pressed with the General Disable or General Test button A red LED indicates a fire alarm in the corresponding zone A flashing red LED indicates that the fire alarm was activated by a detector A steady red LED indicates that the fire alarm was activated by a manual call point A flashing yellow LED indicates a wiring fault in ...

Page 9: ... that the actuator has been activated and the control panel is waiting confirmation of the release of the extinguishing agent flow Consult your system installer to determine whether your system has this option configured A steady red LED indicates that the panel entered the extinguishing released state A flashing yellow LED indicates an actuator output wiring fault A steady yellow LED indicates an...

Page 10: ...es a safety door monitoring fault or disablement Safety door monitoring is optional A fast flashing LED indicates a safety door open or closed faulty status as follows When the control panel is not in activation or released state In automatic mode the control panel reports a fault if the safety door is open and the door fault delay expires In manual mode the control panel reports a fault if the sa...

Page 11: ...er details A steady General Disable LED and the corresponding feature or device yellow LED indicates a disablement 15 General Test button and LED Yellow Tests a system feature or device when pressed with the corresponding button Testing of some devices requires pressing the button for more than 3 seconds See Testing other extinguishing devices on page 26 for further details A steady General Test L...

Page 12: ...ounders If the LED is off pressing the button activates the fire sounders if the control panel status and operating mode allow manual activation of sounders The LED also indicates the status of the sounders Steady indicates that fire sounders are active or will be activated shortly Flashing indicates that a delay countdown is in progress fire sounders are activated when the configured delay elapse...

Page 13: ...eady yellow LED indicates that there is no mains power and the battery power is insufficient A flashing yellow LED indicates that the mains power is insufficient and there is no battery power 25 Earth Fault LED Yellow Indicates an earth isolation fault 26 Supply Fault LED Yellow Indicates a fault in the power supply A flashing LED indicates a battery or battery fuse fault A steady LED indicates a ...

Page 14: ... A flashing yellow LED indicates an open or short circuit wiring fault A steady yellow LED indicates a disablement or test 30 Fire Routing Delay button and LED Yellow Enables or disables a previously configured fire routing delay Fire routing is optional A steady LED indicates that a fire routing delay is configured and enabled A flashing LED indicates that a fire routing delay countdown is in pro...

Page 15: ... LED if a delay is enabled A steady Fire Routing Delay LED Figure 1 item 30 if a delay is enabled There is no audible indication Fire alarm fire only The fire alarm state applies to zones that are not linked to the extinguishing area and act as fire only zones A fire alarm in a detection zone that is not linked to the extinguishing area is indicated as follows General Fire Alarm LEDs Flashing if t...

Page 16: ...d the system is configured so that a second zone in the extinguishing area is required to activate the extinguishing event Extinguishing event conditions are detected one or two zones go into fire alarm depending on configuration but manual mode is activated or a fault or disable condition of an extinguishing device is preventing activation The start manual call point is pressed but a fault or dis...

Page 17: ... is in this state when In automatic mode the extinguishing event conditions are detected one or two zones go into fire alarm depending on the system configuration The start manual call point is pressed An extinguishing activation state is indicated as follows Preactivation LED Steady red Zone LEDs Flashing red for zones in fire alarm Note that these will always flash indicating detector alarms for...

Page 18: ...MCP Hold is deactivated the delay countdown determines when the panel enters the extinguishing activation state In Mode A activation of the MCP Hold turns on the MCP Hold LED which stays on until the panel is manually reset The yellow Preactivation LED flashes to indicate that the panel is being prevented from entering the extinguishing activation state The Preactivation LED flashes to show when t...

Page 19: ...on as usual if the extinguishing event that caused the release was not a start manual call point activation Fire routing indications if configured are shown in the usual manner linked to the fire alarm event The control panel buzzer sounds continuously Faults Faults are indicated with a flashing General Fault LED and an active fault indication LED corresponding to the feature or device with a faul...

Page 20: ...ishing switches are indicated by a steady General Disable LED and a steady yellow LED for Disable extinguishing switch There is no audible indication For BS 7273 mode the buzzer is intermittent when the extinguishing event is disabled Note Some disablements can prevent or disable the extinguishing event See Extinguishing event prevented on page 13 for more information Tests Zone tests are indicate...

Page 21: ... state there are no further fire alarm or fault signals from detection zones and no activation deactivaton or fault signals from input devices are processed The out of service state is indicated as follows Out of Service LED Steady indicates that there is no mains power and the battery power is insufficient Flashing indicates that the mains power is insufficient and there is no battery power Suppl...

Page 22: ...ssword security To enter the operator user level enter the password using the numeric keypad and then press Enter A long beep and a steady Reset LED indicate that the correct password was entered and that the operator user level is active Three short beeps accompanied by a flashing General Fault LED indicate that an incorrect password was entered The control panel automatically exits the operator ...

Page 23: ...ated by a manual call point overrides any configured delay and activates the fire sounders immediately Cancelling an active fire routing delay If a fire routing delay is enabled and active press the Fire Routing On button or the Fire Routing Delay button to cancel the delay and activate fire routing immediately The Fire Routing Delay LED indicates the following conditions Steady A delay is configu...

Page 24: ...Test fire routing Disable or enable a zone Test a zone Disable or enable the extinguishing event Disable other extinguishing devices Test other extinguishing devices Set the manual only mode of operation Resetting the control panel Note Investigate all alarms and system faults before resetting the control panel To reset the control panel and clear all current system events press the Reset button S...

Page 25: ... activation by pressing the Fire Sounders Start Stop button During the time from the end of the configured disable time period until the end of the configured fire sounder delay when the Fire Sounders Start Stop LED is flashing pressing the Fire Sounders Start Stop button will silence fire sounders before activation A configured fire sounder delay may still be cancelled while the delay is running ...

Page 26: ...lt if there is an alarm Note Disabling the extinguishing sounders automatically prevents disables the extinguishing event See Disabling or enabling the extinguishing event on page 25 for more information Fire sounder disablement is indicated as follows A steady General Disable LED A steady yellow LED for the Fire Sounders Delay button Extinguishing sounder disablement is indicated as follows A ste...

Page 27: ... Disable button and then press the Fire Routing Start button The disablement is indicated as follows A steady General Disable LED A steady yellow Fire Routing On LED To enable fire routing press the General Disable button and then press the Fire Routing On button again Note Disabled fire routing does not operate or indicate a fault if there is a fire alarm Disabling or enabling a fire routing dela...

Page 28: ... button The test is indicated as follows A steady General Test LED A steady fault disable test Zone LED When an alarm is activated in a zone in test The alarm Zone LED is steady or flashing depending on the source of the alarm Fire routing and other zone dependent functions are not activated Unless configured otherwise the fire sounders are activated for 5 seconds and the Fire Sounders Start Stop ...

Page 29: ...n prevent or disable the extinguishing event See Extinguishing event prevented on page 13 for more details Disabling other extinguishing devices The devices listed in Table 4 can also be disabled at the operator user level To disable any of these devices press the General Disable button for more than 3 seconds press the 1 and 3 buttons the Up and Down buttons to select the option to be disabled th...

Page 30: ...he corresponding device To exit from a test condition press the General Test button for more than 3 seconds press the 1 and 3 buttons to select the option and then press Enter Table 5 Additional input device test options Input device LED used Test functionality Pressure switch monitoring Low Pressure yellow A flashing Low Pressure LED indicates that the input has been activated Extinguishing agent...

Page 31: ...firm the test command the primary actuator output is activated immediately Set the manual only mode of operation If the control panel is not configured to use an external input to switch to manual only mode press the Manual Mode button on the control panel Manual only mode is indicated by a steady Manual Mode LED In this mode the extinguishing event can only be generated by activation of the MCP S...

Page 32: ...of the system This inspection must test at least one device per zone and verify that the control panel responds to all fault and alarm events The control panel power supply and battery voltage should be checked Annual maintenance Contact your installation or maintenance contractor to carry out an annual inspection of the system This inspection must test all system devices and verify that the contr...

Page 33: ...tection Type C only 8 3 Fault signals from points 8 4 Total loss of power supply 10 Test condition 1 Inputs and outputs on the optional 2010 1 SB expansion board do not support the optional requirement of EN 54 2 clause 7 8 and should not be used for fire alarm devices 2 Requires installation of optional 2010 1 SB expansion board not supplied Table 8 EN 12094 1 optional requirements Option Descrip...

Page 34: ...nufacturing representative UTC Fire Security B V Kelvinstraat 7 6003 DH Weert The Netherlands Year of first CE marking 13 Declaration of Performance number 360 3117 1999 EN 54 EN 54 2 1997 AC 1999 A1 2006 EN 54 4 1997 AC 1999 A1 2002 A2 2006 EN 12094 1 2003 Product identification See model number on product identification label Intended use See DoP point 3 Essential characteristics See DoP point 9...

Page 35: ......

Page 36: ......