45
boiler protection devices
Anti-frost Device.
The anti-frost function acts on the central heating
fl
ow temperature pro-
be, independently from other regulations, when the electrical supply is
turned on.
If the primary circuit temperature falls below 8°C the pump will run
for 2 minutes.
After the two minutes of circulation (
fi
xed) the boiler will check the
following:
a) if the central heating
fl
ow temperature is > 8°C, the pump stops;
b) if the central heating
fl
ow temperature is between 4 and 8°C, the
pump will run for another two minutes;
c) if the central heating
fl
ow temperature is < 4°C, the burner will
fi
re
(heating position) at minimum power until the temperature rea-
ches 33°C, the burner will go out and the pump will continue to
run for two minutes.
If the
fl
ow temperature remains between 4-8°C the pump will con-
tinue to run for two minutes for a maximum of 10 times unless a
temperature above 8°C is detected in the central heating
fl
ow, after
this the the burner will
fi
re. If lockout is caused by overheat the bur-
ner is kept OFF.
The anti-frost device activates only when (with the boiler operating
correctly):
- the system pressure is correct;
- the boiler is electrically powered;
- there is a supply of gas.
Important
If this shutdown occurs frequently, contact an authorised Technical Service
Centre for assistance. For safety reasons, the boiler will permit a maximum of 5
resets in 15 minutes (5 presses of the RESET button); at the 6th attempt within
this 15-minute period the boiler will shut down and may only be operated
again after the electricity supply has been disconnected. If the shutdown is
occasional or an isolated event, this is not a problem.
Summary of Contents for EGIS PREMIUM S 25
Page 3: ...3 CE CE 2009 142 CEE 2004 108 EC 92 42 CEE 2006 95 EC...
Page 4: ...4...
Page 5: ...5 OK ESC 1 2 3 4 6 7 5 Reset...
Page 8: ...8 F A B C D E I G H EGIS PREMIUM S 25 EGIS PREMIUM S 31...
Page 10: ...10 1 3 4 6 7 8 9 10 12 13 14 15 11 16 17 18 19 20 21 22 23 24...
Page 12: ...12 H05V2V2 F 60 N L...
Page 15: ...15 OK ESC...
Page 16: ...16 2 1 3 2 4 2 4 1...
Page 17: ...17 3 65 C 1 C02 4 C02 1 5 RESET Gas CO2 MAX G20 9 0 0 7 G31 10 0 0 7...
Page 18: ...18 31 25 231 220 236 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC OK ESC 1 6...
Page 20: ...20 3 bar EEPROM 15 5 OK ESC...
Page 21: ...21...
Page 22: ...22 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC ESC OK ESC 1 6...
Page 25: ...25 a c d b...
Page 26: ...26...