background image

40

commissioning

 Combustion checking procedure

The order of operations for this procedure must always be respected.

Operazione 1

  -  Supply pressure check

Loosen the screw 

1

 and insert the pressure gauge connection pipe 

into the pipe tap.

Switch  the  boiler  on  at  maximum  power,  enabling  the “Cleaning 
function” (press the button for 5 seconds; the display will show “ 

“).

The supply pressure should correspond to the value established in 

relation to the type of gas ,for which the boiler is designed see Table 

summarising changes.

Operation 2 - Preparing the measuring equipment

Connect the calibrated measuring device to the left-hand combustion 

outlet by unscrewing the screw and removing the blanking cover.

Operation  3  -  Adjusting  the  CO2  at  maximum  gas 

fl

 ow  rate

(domestic hot water)

Draw o

ff

  the domestic hot water at the maximum water 

fl

 ow rate.

Select 

the 

Cleaning 

function 

by 

pressing 

the 

RESET button for 10 seconds.

WARNING!  When  the  cleaning  function  is  activated,  the 

temperature  of  the  water  coming  out  of  the  boiler  may  be  more 

than 65°C.

The following icon appears on the display: 

  (gas  boiler  activated  at  the  C.H. 

maximum power)

Press the button 

    to elect the icon: 

 (D.H.W. maximum power)

Wait  1  minute  for  the  boiler  to  stabilise 

before  carrying  out  the  combustion 

analyses.

Read the CO2 value (%) and compare it with the values given in the 

table below

N.B.:

 values with the casing closed.

If the CO2 value (%) read di

ff

 ers from the values given in the table, 

then adjust the gas valve following the instructions below, otherwise 

move directly onto operation 4.

Adjusting the gas valve at D.H.W. maximum gas 

fl

 ow

Adjust the gas valve by turning setting screw 

4

 clockwise in increments to 

reduce the CO2 level (a 1/4 turn adjusts the CO2 level by approximately 

0.2%). 

Wait  1  minute  after  each 

change  in  setting  for  the  CO2 

value to stabilise.

Once  the  CO2  value  (%)  is 

close to the values given in the 

setting  table,  close  the  casing 

cover  and  measure  the 

fi

 nal 

CO2  value  after  waiting  one 

minute. 

If 

the 

value 

measured 

corresponds to the value given 

in  the  table,  adjustment  is 

complete, otherwise start the setting procedure again.

N.B.

 The cleaning function is automatically deactivated after 10 minutes 

or manually by brie

fl

 y pressing the RESET button.

13

24

2

4

1

EGI

S

 P

R

EMIUM 

S

2

5

3

1

Gas

C

O2

 (%)

G20

9,0 ± 0,7

G31

10,0 

± 0,7

Summary of Contents for EGIS PREMIUM S 25

Page 1: ...INSTALLATION AND SERVICING INSTRUCTIONS CONDENSING WALL HUNG GAS BOILER EGIS PREMIUM S HOT WATER I HEATING I RENEWABLE I AIR CONDITIONING...

Page 2: ...2 3 3 3 4 5 5 6 6 6 7 8 8 8 8 8 9 9 9 9 9 10 10 10 11 11 12 12 13 13 14 15 15 15 15 15 15 16 16 16 18 18 18 19 19 19 20 20 20 20 20 21 22 25 25 26 26 26 26 26...

Page 3: ...3 CE CE 2009 142 CEE 2004 108 EC 92 42 CEE 2006 95 EC...

Page 4: ...4...

Page 5: ...5 OK ESC 1 2 3 4 6 7 5 Reset...

Page 6: ...6 A B C D E 150 319 180 25 745 28 745 200 120 120 200 65 L 65 67 67 450 0 5 3 0 0 3 50 50 OK ESC 1 2 3 4 5 6 7 9 10 12 14 15 16 17 18 19 20 21 23 24 22 8 13...

Page 7: ...2 9 0 9 A 0 9 A s s a l c 2 2 2 2 0 0 1 0 0 1 a P 5 5 s s a l c 4 6 5 6 C C 0 9 0 9 1 0 1 m p p 2 O 0 5 4 5 4 4 9 4 h g K C 0 6 C 0 8 7 2 7 2 1 r a b 3 r a b 8 1 3 8 L 2 8 5 3 C 5 4 0 2 C 0 6 6 3 2 8...

Page 8: ...8 F A B C D E I G H EGIS PREMIUM S 25 EGIS PREMIUM S 31...

Page 9: ...9 0 1 2 3 4 5 6 7 0 100 200 300 400 500 600 700 800 900 1000 mCE l h EGIS PREMIUM S 25 EGIS PREMIUM S 31 I 15mm interno 22 mm...

Page 10: ...10 1 3 4 6 7 8 9 10 12 13 14 15 11 16 17 18 19 20 21 22 23 24...

Page 11: ...33 C43 10 60 100 B33 10 C13 C33 C43 30 80 125 B33 30 S1 S2 C13 26 26 80 80 0 6 0 6 5 1 5 1 C33 50 50 80 80 0 6 0 6 2 2 C43 26 26 80 80 0 6 0 6 5 1 5 1 S1 S2 C53 C83 50 80 80 8 60 60 B23 50 25 12 12 36...

Page 12: ...12 H05V2V2 F 60 N L...

Page 13: ...13 a b c d TA2 FLOOR SE SOL TA1 T B TA2 FLOOR SE SOL TA1 CN1 Outdoor sensor Under oor heating thermostat Room Thermostat 1 FLOOR SE SOL TA1...

Page 14: ...CN4 Bk Bk Gr Wh Rd Bl Bk Bk Br Bl Bk Bl Br CN2 CN11 1 1 CN14 CN3 1 1 CN8 1 CN25 1 N N FLAME L L TA2 FLOOR SE SOL TA1 CN19 CN1 CN4 1 LV HV CN14 CN3 1 1 CN8 CN9 1 1 CN25 1 1 CN6 CN11 1 1 Bk Bk Bk Bk Bk...

Page 15: ...15 OK ESC...

Page 16: ...16 2 1 3 2 4 2 4 1...

Page 17: ...17 3 65 C 1 C02 4 C02 1 5 RESET Gas CO2 MAX G20 9 0 0 7 G31 10 0 0 7...

Page 18: ...18 31 25 231 220 236 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC OK ESC 1 6...

Page 19: ...6 0 2 2 0 6 1 3 2 8 1 3 3 2 8 7 4 3 2 6 8 2 3 2 3 4 7 5 m m 3 3 2 7 1 3 7 1 2 6 9 2 0 5 0 9 6 0 25 G20 G31 9 6 0 7 7 6 5 4 55 55 8 1 80 91 6 3 0 5 2 0 2 5 7 2 9 7 1 3 4 2 9 1 0 8 5 0 15 C 1013 mbar 1...

Page 20: ...20 3 bar EEPROM 15 5 OK ESC...

Page 21: ...21...

Page 22: ...22 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC ESC OK ESC 1 6...

Page 23: ...232 RPM 0 99 233 RPM 0 99 234 RPM 0 99 236 0 7 3 247 0 1 2 1 250 234 OK 422 0_2 0_8 0_5 1_0 3_5 1_5 0 1 30 2 252 5 200 0 5 20 5 253 0 67 C 1 4 C 0 254 0 1 0 270 271 420 0 20 45 C 1 35 85 C 421 0 1 3 1...

Page 24: ...24 822 rx100RPM 831 C 832 C 842 425 35 85 C 420 1 82 20 45 C 420 0 45 426 35 85 C 420 1 40 20 45 C 420 0 25...

Page 25: ...25 a c d b...

Page 26: ...26...

Page 27: ...supply cable 36 Peripheral unit connection 37 Room Thermostat connection 37 Electrical diagram 38 Commissioning 39 Ignition procedure 39 Initial procedures 39 Electricity supply 39 Filling the hydraul...

Page 28: ...er leaking from damaged piping Make sure the installation site and any systems to which the appliance must be connected comply with the applicable norms in force Electrocution caused by contact with l...

Page 29: ...eously allows for accessing the setting adjustment and diagnostics parameters b Pressing the buttons simultaneously allows for modifying and saving the parameter settings Display Legend Digits indicat...

Page 30: ...th the clearances stated below 1 2 3 4 5 6 7 9 10 12 14 15 16 17 18 19 20 21 23 24 22 8 13 Legend 1 Flue connector 2 Air relief valve 3 Main heat exchanger 4 Detection Electrode 5 C H Return temperatu...

Page 31: ...stars Sedbuk class class A 90 A 90 Loss when stopped T 50 C Loss of burner gas when operating 2 2 2 2 EMISSIONS Available air pressure Pa 100 100 NoX class class 5 5 Flue gas temperature G20 80 C 60 C...

Page 32: ...er may be accessed after it has been installed should be respected WARNING No inflammable items should be left in the vicinity of the boiler Make sure the installation site and any systems to which th...

Page 33: ...re is too high the boiler will stop both do mestic hot water and the heating production and the error code 1 16 oor thermostat contact open will appear on the display The boiler will restart when the...

Page 34: ...he suction exhaust ducting split connection of the boiler to the exhaust ducting with air suction from outside split connection of the boiler to the exhaust ducting with air suction from the room Prod...

Page 35: ...ent fixing it in place using the screw provided Table of flue gas exhaust duct lengths S1 Air intake S2 Flue gas exhaust Type Maximum Extension Exhaust air m Diameter of pipe mm EGIS PREMIUM S 24 30 C...

Page 36: ...e manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the malfunctioning of the electricity mains supply Make sure that the system is able to withstan...

Page 37: ...t 1 Room thermostat connection Introduce the thermostat wire Loosen the cable clamp using a screwdriver and insert the wires leading from the room thermostat one at a time Connect the wires to the ter...

Page 38: ...e C H Flow temp probe Thermal fuse Thermal fuse D H W flow switch Switch ON OFF Br Rd Rd Bl Bl Br Br Br Bk Bk Bk HV connection N N FLAME L L CN19 CN4 Bk Bk Gr Wh Rd Bl Modulating Fan Detection electro...

Page 39: ...illing stage or if there is excess air in the system the deaeration cycle can be activated by holding the MODE button for 10 seconds The boiler will start a cycle which lasts approximately 7 minutes W...

Page 40: ...lowing icon appears on the display gas boiler activated at the C H maximum power Press the button 1 to elect the icon D H W maximum power Wait 1 minute for the boiler to stabilise before carrying out...

Page 41: ...1 minute after each adjustment for the CO2 value to stabilise WARNING this adjustment is sensitive a rotation of a 1 4 turn corresponds to 0 4 of CO2 Once the CO2 value is close to the values given i...

Page 42: ...lue e g 75 75 8 Press the OK button to save the change or press ESC to exit without saving To exit press the ESC button until the normal display screen is restored Checking slow ignition power The sof...

Page 43: ...Example 1 SINGLE ZONE SYSTEM HIGH TEMPERATURE WITH ON OFF ROOM THERMOSTAT In this case the following parameters must be set 4 21 Activation of temperature adjustment using sensors Select 04 Basic temp...

Page 44: ...the system If this is the case a plumber should be contacted Operation shutdown This type of error is non volatile which means that it is not removed automatically On the display flash Err and the err...

Page 45: ...to run for two minutes If the flow temperature remains between 4 8 C the pump will con tinue to run for two minutes for a maximum of 10 times unless a temperature above 8 C is detected in the central...

Page 46: ...f parameters value Programming ESC key to exit from the parameters The information relating to the parameters are indicated on the display Caution The menus reserved for qualified technicians may only...

Page 47: ...lay from 5 to 200 0 5 to 20 seconds 5 Anti water hammering 253 D H W switch logic 0 Anti scale stop at 67 C 1 At 4 C over set point 0 254 Post circulation and post ventilation after domestic hot water...

Page 48: ...e decrease in relation to the set point value from 14 to 14 C high temperature from 7 to 7 C low temperature Warning The curves can be shifted upwards or downwards without accessing the parameter usin...

Page 49: ...external bipolar switch and shut off the gas valve To access the inside of the boiler the following is necessary 1 Loosen the two screws on the front casing a pull it forwards and unhook it from the u...

Page 50: ...the flue system is sealed and operating correctly Draining procedures The heating system must be drained using the following procedure Switch off the boiler make sure the external bipolar switch is in...

Page 51: ...gas category 7 Gas setting 8 Installation type 9 Electrical data 10 Maximum domestic hot water pressure 11 Maximum heating pressure 12 Boiler type 13 NOx class Efficiency 14 Input rating nominal heati...

Page 52: ...ITALIAN DESIGN ariston com Ariston Thermo SpA Viale A Merloni 45 60044 Fabriano AN www aristonthermo it info it aristonthermo com 420010595100...

Reviews: