42
commissioning
Accessing the settings and adjustment parameters
Parameter 231
Maximum Heating Power adjustment
Parameter 220
Soft light Ignition
Parameter 236
Heating ignition delay
O
K
E
S
C
1
6
1.
Programming
“+”
and
“-”
key, to access and modify the
parameter
6.
Programming
“+”
OK
key, to save the changes of parameters
value
Programming
“-” ESC
key, to exit from the parameters
The information relating to the parameters are indicated on the
display.
Caution!
The menus reserved for quali
fi
ed technicians may only
be accessed after setting the access code.
To access to the parameters proceed as
follows:
1. Press simultaneously the
“+”
e
“-”
buttons for 5 seconds
The display requires the acces code,
222
222
will appear on the display
2. Press the
“+”
button to select code
234
234
.
3. Press the
“+” OK
button to access the
parameter list
4. On the display will appear the
fi
rst
parameter
220
220
5. To select the parameters press the
“+”
button.
-
exemple: modify the
231
231
parameter
6. Press the
“+” OK
button to access the
parameter. The display will indicate
the value “es:
70
70
”
7. Press the
“+”
and
“-”
buttons to
select the new value, e.g. “
75
75
”.
8. Press the
“+” OK
button to save
the change or press
“-” ESC
to exit
without saving.
To exit, press the
“-” ESC
button until the normal display screen
is restored.
Checking slow ignition power
The soft light can be adjusted between the maximum power and the
minimum power.
Change the parameter if the outlet pressure from the gas valve in
the ignition phase (measured when the boiler is in hot water heating
operation) does not coincide with the values shown in the Table
summarising changes.
To check the slow ignition power, access menu 2/sub menu 2/
parameter 0.
If needed, change the parameter value until suitable pressure is
achieved.
Heating ignition delay adjustment
This parameter can be used to set the delay time, before the
subsequent reignition of the burner after it has switched o
ff
on
reaching the desired temperature.
It is possible to set the delay in minutes between 0 and 7 minutes.
Maximun Heating Power adjustment
The maximum heating power can be adjusted to between the maxi-
mum power allowed by the boiler and the minimum power).
The display shows the value between “99” and 0 of this interval.
To check the maximum heating power, access menu 2/sub menu 3/
parameter 1, check the value and, if necessary, modify it as indicated
in the Table summarising changes.
31
25
Summary of Contents for EGIS PREMIUM S 25
Page 3: ...3 CE CE 2009 142 CEE 2004 108 EC 92 42 CEE 2006 95 EC...
Page 4: ...4...
Page 5: ...5 OK ESC 1 2 3 4 6 7 5 Reset...
Page 8: ...8 F A B C D E I G H EGIS PREMIUM S 25 EGIS PREMIUM S 31...
Page 10: ...10 1 3 4 6 7 8 9 10 12 13 14 15 11 16 17 18 19 20 21 22 23 24...
Page 12: ...12 H05V2V2 F 60 N L...
Page 15: ...15 OK ESC...
Page 16: ...16 2 1 3 2 4 2 4 1...
Page 17: ...17 3 65 C 1 C02 4 C02 1 5 RESET Gas CO2 MAX G20 9 0 0 7 G31 10 0 0 7...
Page 18: ...18 31 25 231 220 236 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC OK ESC 1 6...
Page 20: ...20 3 bar EEPROM 15 5 OK ESC...
Page 21: ...21...
Page 22: ...22 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC ESC OK ESC 1 6...
Page 25: ...25 a c d b...
Page 26: ...26...