OPERATING
CONDITION
SYMPTOMS
POSSIBLE
CAUSES
REPAIR
PROCEDURES
CB1 on.
AC power present.
Low voltage L.E.D. on
when output voltage is
normal.
Low voltage misad-
justed.
Jumper J2 missing.
Faulty front panel PCB.
Adjust Low Voltage
control.
Replace J2.
Replace front panel
PCB assembly.
CB1 on.
AC power present.
Unit does not share load
with paralleled rectifiers.
Slope control misad-
justed.
Front panel PCB as-
sembly faulty.
Control circuit failure
U6, U7, U8, U9.
Adjust slope control.
Replace front panel
PCB assembly.
Repair control circuit.
ARGUS TECHNOLOGIES
Document #010-002-C0 Rev. H Page 33