4.7 Access code
An access code adjustable from 0000 to 9999 serves to protect the meter
and its output from unauthorized programming, and to lock the access to
some functions.
0 0 0 0 Factory code
x x x x
0 to 5 Access to the display shifting
6 to 9 No access
0 to 5 Access to the display and output simulations
6 to 9 No access
0 to 5 Access to the teleloading of files
6 to 9 No access
4.8 Programming of a new access code
PCOD
OLD
NO
Enter pre-
vious code
if code not valid
(old)
display during 2s.
and revert to the
measure display
New code registered, and revert to
the measure display
if code correct
(old)
Enter the
new code
Reminder:
If no key is pressed during 1 min, the instrument will revert
to the measure display.
The access code is 0000 on factory exit.
NEW
Note
: The instrument no longer measures during the simulation. The
analog output will react according to the displayed value.
SIMU
SIMU
Value of the
display
if
M
Press Menu to
revert to the
measure
display.
4.9 Functions which can be accessed from the main menu
4.9.1 Simulation of the display
(accessible according to the programmed access code)
The display can be simulated with the converter in order to validate the
configuration of the analog output in the installation.
Entering of a new
display value
GENE
GENE
Value of the
output
if
Enter the value
to be injected
M
Press Menu to
revert to the
measure dis-
play
Note
: The instrument will carry on measuring during the simulation. Only
the analog output no longer reacts to the measure.
(accessible according to the programmed access code)
4.9.2 Simulation of the analog output
(mode generator)