PECA 30 / 30 E : programming-configuration
29
ARDETEM
PROGRAMMING OF PULSE OUTPUTS :
This programming goes on for :
- the outputs 1,2 and 3 of a « PULS » type board,
- the outputs 4 and 5 of an « AnA.P » type board.
Example
:
For an « AnA.P » type mixed board in position 1, we want :
for the first output (output 4) : 1 pulse for 1KWh of the active energy OUT,
for the second output (output 5) : 1 pulse for 2KWh of the reactive energy IN, with a 250ms pulse width.
The board Nr 1 is chosen (in position 1)
Choice of the output 4 of the board Nr 1 (type board : « AnA.P »)
Capture of the parameter number corresponding to the output
(see the parameters list on page 13)
Pulse provided by an energy increase
value and unit (10 3 = KILO)
Choice of the pulse width : 50ms, 100ms or 250ms
Back to the output choice : output 5 of the board Nr 1 validation
Capture of the parameter number corresponding to the output
(see the parameters list on page 13)
see the next page
See capture Nr 1 page 16
back to the boards choice
back to the measurement
JbUS
brd.1
brd.2
Sor.4
brd.1
AnA.P
24
brd.1
PArA
1.000
brd.1
Acc
10 3
brd.1
Acc
250.0
brd.1
dEL
Sor.5
brd.1
AnA.P
27
brd.1
PArA