Table. 5.2.2 - 35. Harmonic voltage measurements.
Name
Unit
Range
Step Default
Description
Harmonics
calculation values
("Harm Abs.or
Perc.")
-
0: Percent
1: Absolute
-
0:
Percent
Defines whether the harmonics are calculated as
percentages or absolute values.
Harmonics
display
-
0: Per unit
1: Primary V
2: Secondary V
-
0: Per
unit
Defines how the harmonics are displayed: in p.u. values, as
primary voltage values, or as secondary voltage values.
Maximum
harmonics value
("UxMaxH")
V
0.00…100000.00
V
0.01
V
-
Displays the maximum harmonics value of the selected
voltage input Ux.
Fundamental
frequency
("Ux Fund")
V
0.00…100000.00
V
0.01
V
-
Displays the voltage value of the fundamental frequency
value (RMS) of the selected voltage input Ux.
Ux harmonics
(2
nd
...31
st
harmonic)
V
0.00...100000.00
V
0.01
V
-
Displays the selected harmonic from the voltage input Ux.
5.2.3 Power and energy calculation
The relays that are equipped with both a voltage and a current measurement card can calculate power,
and can therefore have power-based protection and monitoring functions (the number of available
functions depends of the relay type). In addition to power calculations, energy magnitudes are also
calculated.
Power is divided into three magnitudes: apparent power (S), active power (P) and reactive power (Q).
Energy measurement calculates magnitudes for active and reactive energy. Energy can flow to the
forward direction (exported) or to the reverse direction (imported).
If a unit has more than one CT measurement module, the user can choose which module's current
measurement is used by the power calculation.
Line
Line-t
-to-ne
o-neutral v
utral volta
oltages a
ges avvailable
ailable
Power is calculated from line-to-neutral voltages and phase currents. If line-to-line voltages are
connected, the relay can calculate line-to-neutral voltages based on the measured zero sequence
voltage. The following equations apply for power calculations with the line-to-neutral mode and the line-
to-line voltage mode (with U0 connected and measured):
Figure. 5.2.3 - 65. Three-phase power (S) calculation.
A
AQ
Q-S215
-S215
Instruction manual
Version: 2.04
71
Summary of Contents for AQ-S215
Page 1: ...AQ S215 Bay control IED Instruction manual...
Page 249: ...Figure 7 4 151 Example block scheme A AQ Q S215 S215 Instruction manual Version 2 04 248...
Page 269: ...Figure 8 13 172 Device installation A AQ Q S215 S215 Instruction manual Version 2 04 268...
Page 287: ...10 Ordering information A AQ Q S215 S215 Instruction manual Version 2 04 286...