Appendix I: Instructions for Software Upgrading Operation
Functions:
The system software is allowed to upgrade through an USB disk.
The specific operation procedure is as follows:
1.File upgrading
Copy the upgrading file titled STARTCNC.EXE to an USB disk.
2.Operation procedure
Push and hold the button between
the red button 0 and the USB port.
Power the system on and release the button when upgrading window appears on the
display screen. Plug the USB disk into the port and press Key F1 under the display screen(the
key corresponds to "UPGRADE" in the menu displayed). The system will automatically start
upgrading operation.
3.Upgrading end
If program upgrading is successful, the system will prompt "Upgraded Successfully" and
sound one beep. If program upgrading fails, the system will prompt "Upgrade Failure" and
sound continuous beeps.
。
4.New program startup
Power the system off and unplug the USB disk. Reboot the system to start up the upgraded
program. The version number of the upgraded program will appear on the screen after booted
up.
Notes:
Please make the following check if upgrading operation fails.
1) The USB disk must be FAT or FAT32 format. FAT format is preferable.
2) The upgrading file must be titled as STARTCNC.EXE.
3) If no prompt appears in the upgrading process and the display returns to the main upgrading
window or upgrading operation fails due to any other interruption, verify first the name of
upgrading file and the format of USB disk. If these two factors are assured, try to upgrade the
program again following the specific operation procedure.