39
English
- ELECTRONIC BOARD
AND CONNECTIONS
RL2
RL1
Po
Po
F2
F2
L N N
SEA
230V
~
IN1
ON
12
34
IN2
(DSC)
MIN. SPEED
MAX. SPEED
L N
DIP
P1
Stand-by
P1
Low
Speed
P1
High
Speed
P1
Low
Speed
DL1
P1
DL2
DL3
LEGEND:
DIP
=
Configuration dipswitches
IN2
= DSC door contact
IN1
=
Remote ON-OFF (See DIP 3 setting)
FUNCTION OF THE AUXILIARY CONTACTS
• Contact IN1
: Remote ON-OFF (see DIP 3 setting).
- with DIP No 3 set on ON
is configured as remote ON/OFF where:
• contact closed = ON fan
• contact open = OFF fan
• Contact IN2
(
DSC
): - Dorr Contact -
When the contact is open the appliance can operate.
When the contact is closed the appliance is stopped.
Function associated with the post-ventilation (See
table Dip).
- DIPSWITCHES SETTINGS
Connecting auxiliary contacts IN1 / IN2
1
2
OFF
OFF
DIP
DEFAULT
POSITION
3
4
OFF
OFF
Button
P1
ENABLED
Button
P1
DISABLED
CONTACT
IN1
(remote On/Off)
ENABLED
CONTACT
IN1
(remote On/Off)
DISABLED
ON
DIP
DEFAULT
OFF
POSITION
0 sec. 30 sec. 60 sec. 90 sec.
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Dip dedicated to manufacturer
DIP No 1 and DIP No 2 -
SETTING TIME POST-VENTILA-
TION (Function is associated with DSC - door contact)
- USING THE CONTROL
P1 =
On / Stand By / Set the fan speed
DL1 =
On / Stand By led
DL2 =
Low speed led
DL3 =
High speed led
• At Power On the control takes the stored state at the
time of power failure.
• When you first turn all the leds are off:
press the
P1
button to select the stand-by mode.
In stand-by mode
DL1
is turned on, while
DL2
and
DL3
off.
• Press the
P1
button to set low speed:
DL1 and DL2
are
on while
DL3
off.
• Press again the
P1
button to set high speed:
DL1
and
DL3
are turned on, while
DL2
off.
NOTE!:
the fan remains active for the
time to post ventilation set using Dip n ° 1
and 2. (see
DIPSWITCHES SETTINGS
)
DCB-L