44
English
- ELECTRONIC BOARD
OF CONTROL
IN1
ON
1
2
3
4
IN2
(DSC)
DIP
5
6
J1
MC3
T-MB
SELV BOARD
LEGEND:
DIP
=
Configuration dipswitches
IN2
= DSC door contact
IN1
= Remote ON-OFF (See MC3 JUMPER setting)
RS485
=
Terminals TX-RC/GND for the Master-Slave
J1
= JUMPER MC3
CHIUSO
CLOSED
FERME
GESCHLOSSEN
CERRADO
ЗАКРЫТО
APERTO
OPEN
OUVERT
GEÖFFNET
ABIERTO
ОТКРЫТОЕ
FUNCTION OF THE AUXILIARY CONTACTS
• Contact IN1
:
Remote ON-OFF
When the contact is closed the appliance can operate.
When the contact is open the appliance is stopped.
If used, remove the MC3 (J1) Jumper for contact
closure.
• Contact IN2
(
DSC
):
- Dorr Contact -
When the contact is open the appliance can operate.
When the contact is closed the appliance is stopped.
Function associated with the post-ventilation (See
table Dip)
- DIPSWITCHES SETTINGS
ON
1 2 3 4
DIP
5 6
DIP No 1 and DIP No 2 -
SETTING TIME POST-VENTILA-
TION (Function is associated with DSC - door contact)
1
2
OFF
OFF
DIP
DEFAULT
POSITION
3
4
OFF
OFF
MASTER
SLAVE
Use with
T-MB control
ON
DIP
DEFAULT
OFF
POSITION
0 sec. 30 sec. 60 sec. 90 sec.
OFF
OFF
ON
OFF
OFF
ON
ON
ON
5
6
OFF
OFF
ASYNCHRONOUS
MOTOR
ECM
MOTOR
Use with
infra-red control
Operation mode
"DCB-E"
Operation mode
“DCB-W”
Dip dedicated to manufacturer
a
ttention
!
t
he
u
nits
with
electric
resistance
are
configured
,
BY
default
,
with
30
seconds
of
Post
V
entilation
.
(
indePendent
Parameter
BY
setting
diP1
and
diP2)
DCB-W / DCB-E