INSTALLATION

 

 
 

The controller and sensing unit should be securely mounted on a sound surface.  

The controller should be mounted within 5 feet of a 120 VAC, 60 Hz grounded outlet. 
 
 

The controller can be wired up to 300 feet from sensor unit (contact ACT for 

exceptions). ACT recommends mounting the controller in the most favorable 
environment possible. 
 

The 

standard well

 sensing unit is installed at the water level of the pool.  The 

center of the clear ½” PVC tube on the sensor unit should be at the normal 
operating water level of the pool.  An isolated static water line from the pool to 
the sensor unit is necessary to provide stable water conditions. A valve 
arrangement is provided.  The valves are installed so that the operator may 
maintain and clean the sensing unit. 

 

The 

sight glass

 sensing unit is installed by attaching the unit to a balance tank 

sight glass. The sensor should be mounted at normal operating water level of the 
balance tank using the attached clic connectors.  
 
The 

wet well

 sensing unit is installed in a 2” PVC pipe which serves as a still 

water stand pipe from the pool. The normal water level should sit approximately 
1.5” up from the bottom of the end cap.  

 

The 

surge tank

 sensing unit is installed in the surge tank at normal operating 

water level with the included clic connectors. The normal water level should sit 
approximately 1.5” up from the bottom of the end cap. 
 
The 

deck well

 sensing unit is installed at pool side. The unit has a ½” static line 

sight glass inside to attach a sight glass sensing unit to, which is also provided. 
The deck well is connected to the pool using a 2” static line. Conduit connection 
and drain connections are also present to make installation quick and easy.   
 
The 3 conductor extension cable provided with the system is the electrical 

connection for the sensor unit to the controller.  With the standard well, sight glass, wet 
well and deck well, a terminal strip is provided in the sensor housing for terminating the 
cable (please see wiring diagram for color connections located inside sensor box for 
standard well, sight glass, wet well, and deck well applications). The other end of the 
cable terminates inside the ELC-810.  The interconnecting cable carries low voltage.  
Local codes may require the cable to be housed in conduit. 
 
Refer to 

www.aquaticontrol.com

 for sensing applications, drawings, and other product 

information offered by AquatiControl Technology. 
 
 
 

Summary of Contents for ELC-810 Series

Page 1: ...810 AUTOMATIC WATER LEVEL CONTROLLER AquatiControl Technology 3820 South Federal Blvd Sheridan Colorado 80110 Toll Free 877 755 8817 Fax 303 761 1499 www aquaticontrol com Serial No __________________...

Page 2: ...ACT 2009 2 TABLE OF CONTENTS Introduction 3 Installation 4 5 Wiring Diagram 6 Operation 7 9 Routine Maintenance 10 Troubleshooting 11 12 Warranty 13...

Page 3: ...following pages of this manual The ELC 810 should ship with the following contents 1 Control unit Sensing Unit s Standard Well Sight Glass Wet Well Surge Tank Deck Well 1 Mounting Hardware 1 Operation...

Page 4: ...l water level should sit approximately 1 5 up from the bottom of the end cap The surge tank sensing unit is installed in the surge tank at normal operating water level with the included clic connector...

Page 5: ...In order to setup the use of an alternate level on the ELC 810 a second sensing application should be placed at the chosen lower water level and a flow switch supplied with the ELC 810 needs to be in...

Page 6: ...ACT 2009 6...

Page 7: ...arrows The enter button will bring you back to the startup screen Options can be changed by following the directions below The first six screens as you scroll down through the menu are for informatio...

Page 8: ...seconds to 99 seconds use up and down arrows to change To activate this option hold the left and right arrows for 3 seconds DEFAULT 10 seconds DELAY TO SHUTOFF time solenoid valve will stay on after s...

Page 9: ...ally closed flow switches Open or Closed use left and right arrows to change DEFAULT Closed SENSOR TYPE set to Other DEFAULT Other SOUNDER WITH ALARM beeping will occur when in alarm mode if yes is se...

Page 10: ...RGE TANK The Surge Tank Sensing Unit will not normally need to be cleaned however if the cap on the bottom of the sensing application becomes clogged with debris it can be unscrewed and rinsed until c...

Page 11: ...ective sensor Replace sensor Sensing unit not set properly Readjust sensor to water level Wiring is incorrect in sensor junction box Check wiring connection Level light does not come on Cable in ELC 8...

Page 12: ...ACT 2009 12 SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION Can t change settings Forgotten wrong password Reset ELC by turning the power on while holding the left and right arrows...

Page 13: ...or part which is returned transportation prepaid to the factory within one year of delivery to the original purchaser and which is proven defective upon examination ACT disclaims all liability for da...