ROUTINE MAINTENANCE

 

 

AquatiControl Technology’s Model ELC-810 controller is completely solid state 

and normally will not require any maintenance. 
 

S

ENSOR 

U

NIT 

C

LEANING

 

 

S

TANDARD 

W

ELL

 

The ½” PVC tube on the Standard Well Sensing Unit may need to be cleaned 
periodically.  To clean the tube, isolate the sensor unit by closing the valve that 
supplies the water to it.  Remove the cap from the top of the tube and fill with a 
diluted acid solution, 3 parts water to 1 part acid.  A brush may be used to clean 
the inside of the tube. 
 
The valve at the bottom of the sensing unit can be opened to drain out the acid 
solution. Place the solution into a container and dispose of it properly.  The tube 
can then be flushed with fresh water.  After flushing, open the valve from the 
pool.  The unit is now ready for operation. 

 

 

S

IGHT 

G

LASS

 

The Sight Glass Sensing Unit will not normally need to be cleaned. 
 

S

URGE 

T

ANK

 

The Surge Tank Sensing Unit will not normally need to be cleaned; however, if 
the cap on the bottom of the sensing application becomes clogged with debris, it 
can be unscrewed and rinsed until clean and then replaced.  
 

W

ET 

W

ELL

 

The Wet Well Sensing Unit will not normally need to be cleaned; however, if the 
cap on the bottom of the sensing application becomes clogged with debris, it can 
be unscrewed and rinsed until clean and then replaced.  
 

D

ECK 

W

ELL

 

The Deck Well Sensing Unit will not normally need to be cleaned; however, 
debris and stagnant water may enter the Deck Well which can be cleaned out 
being very careful not to get any water near the sensing unit or electrical conduit. 
 

S

ENSOR 

R

EPLACEMENT

 

 
 

The proximity switch used for the control system is good for thousands of on/off 

switching.  Typically the sensor should be replaced every three years for year round 
usage.  Seasonal pools may require replacing every five years or as needed. Replacement 
sensors are available from the distributor and factory for all but the surge tank sensing 
units which need to be replaced in whole.  

Summary of Contents for ELC-810 Series

Page 1: ...810 AUTOMATIC WATER LEVEL CONTROLLER AquatiControl Technology 3820 South Federal Blvd Sheridan Colorado 80110 Toll Free 877 755 8817 Fax 303 761 1499 www aquaticontrol com Serial No __________________...

Page 2: ...ACT 2009 2 TABLE OF CONTENTS Introduction 3 Installation 4 5 Wiring Diagram 6 Operation 7 9 Routine Maintenance 10 Troubleshooting 11 12 Warranty 13...

Page 3: ...following pages of this manual The ELC 810 should ship with the following contents 1 Control unit Sensing Unit s Standard Well Sight Glass Wet Well Surge Tank Deck Well 1 Mounting Hardware 1 Operation...

Page 4: ...l water level should sit approximately 1 5 up from the bottom of the end cap The surge tank sensing unit is installed in the surge tank at normal operating water level with the included clic connector...

Page 5: ...In order to setup the use of an alternate level on the ELC 810 a second sensing application should be placed at the chosen lower water level and a flow switch supplied with the ELC 810 needs to be in...

Page 6: ...ACT 2009 6...

Page 7: ...arrows The enter button will bring you back to the startup screen Options can be changed by following the directions below The first six screens as you scroll down through the menu are for informatio...

Page 8: ...seconds to 99 seconds use up and down arrows to change To activate this option hold the left and right arrows for 3 seconds DEFAULT 10 seconds DELAY TO SHUTOFF time solenoid valve will stay on after s...

Page 9: ...ally closed flow switches Open or Closed use left and right arrows to change DEFAULT Closed SENSOR TYPE set to Other DEFAULT Other SOUNDER WITH ALARM beeping will occur when in alarm mode if yes is se...

Page 10: ...RGE TANK The Surge Tank Sensing Unit will not normally need to be cleaned however if the cap on the bottom of the sensing application becomes clogged with debris it can be unscrewed and rinsed until c...

Page 11: ...ective sensor Replace sensor Sensing unit not set properly Readjust sensor to water level Wiring is incorrect in sensor junction box Check wiring connection Level light does not come on Cable in ELC 8...

Page 12: ...ACT 2009 12 SYMPTOM POSSIBLE CAUSE CORRECTIVE ACTION Can t change settings Forgotten wrong password Reset ELC by turning the power on while holding the left and right arrows...