1.3.3 PIPEWORK 

 
1.3.3.1  Mains Water Supply 

i.

 

Fit an isolating valve in the supply to enable the unit to be isolated from the supply for maintenance. 

Make 

sure the float valve restrictor is fitted if the mains water inlet pressure exceeds 1.5 Bar. If the mains 

water inlet pressure is less than 1.5 Bar, the restrictor should not be fitted.

 

ii.

 

Float Valve Instructions as follows: - 

iii.

 

For category 4 & 5 installations remove the filler tube to comply with local water regulations. 

 

 

1.3.3.2 System 

Connection 

i. 

The unit must be connected with any expansion vessels and cooling vessels, to the underside of the return 
header on the suction side of the circulating pumps and boiler/chiller (see Location 1.3.1) 

ii. 

The system connection on the pressurisation unit is 15mm compression/1/2” BSP at the side of the cabinet. 
An isolating valve must be fitted to isolate the unit from the system. 

iv.

 

All hydraulic accumulators and expansion vessels fitted to the system must have isolating and drain off 

valves to enable them to be serviced. 

v.

 

All hydraulic accumulators and expansion vessels fitted to the system must have connecting pipework that 
is removable to give access for replacing vessel diaphragm, and must be large enough to avoid friction 
losses. 

 

 

Summary of Contents for MINIPACK MP Series

Page 1: ...ESSURISATION UNITS WITH MICROPROCESSOR CONTROLS MODELS MP31 32 71 72 ISSUE 6 30 01 2019 Head Office AGM House London Rd Copford Colchester Essex CO6 1GT UK Tel 01206 215121 Email aftersales agm plc co...

Page 2: ...e manual supplied with the unit Examples of units manufactured by Aquatech Pressmain are shown below Please note it is also possible for the pump controls tanks to have been sold as a separate item in...

Page 3: ...NG MiniPack Standard Basic B or Enhanced E UNITS 12 1 3 6 ELECTRICAL 12 2 USER INSTRUCTIONS 14 2 1 CUSTOMER ASSURANCE 14 2 2 COMMISSIONING 15 2 3 OPERATING INSTRUCTIONS 15 2 3 1 ADDITIONAL CAUTIONS 15...

Page 4: ...PSSR and the Owner User should be made aware of their responsibility for this see section 3 Servicing Failure to install operate use maintain the equipment as recommended below could cause damage to...

Page 5: ...or property 0 1 12 Pump motors with lifting eyes the lifting eyes are only suitable for lifting motors NOT the entire pump assembly This could cause injury to people or property 0 1 13 Ensure the bas...

Page 6: ...ssure safety device into the system with due respect to the suction pressure present on the pumpset the pump closed valve pressure stated on the pump the maximum working pressure stated on any of the...

Page 7: ...3 8 Ensure pumpset has an adequate water supply at all times to prevent dry running causing pump seal damage and water leakage 0 3 9 Do no attempt to start pumps without liquid in volutes pumps must b...

Page 8: ...the suction side of the circulating pump but not within any influences from the circulating pump and for a heating system at the point of lowest temperature i e before the boiler If the equipment is...

Page 9: ...stem Connection i The unit must be connected with any expansion vessels and cooling vessels to the underside of the return header on the suction side of the circulating pumps and boiler chiller see Lo...

Page 10: ...mm Float Valve 15mm Incoming Mains Supply Microprocessor Controller System connection on suction side of Circulating Pumps Sytem filling device e g quick fill loop check local water regulations Drain...

Page 11: ...r charge filling valve top and the diaphragm bottom on 70 C vessels top on 100 C vessels are accessible for future maintenance All vessels must have isolating and drain off valves fitted to enable the...

Page 12: ...et terminal on pcb card in series with the boiler chiller control circuits so that in the event of a fault condition occurring the boiler chillers shut down and remain inoperative until the fault cond...

Page 13: ...6a Typical standard B controller Wiring Diagram Fig 1 6b Typical Boiler wiring by others PCB1 PCB2 PCB3 O Keypad 2020Plus controller Pump 2 Auto Off Hand Pump 1 Auto Off Hand Display Pressure fault n...

Page 14: ...urance does not apply to those items not supplied by us or to defects arising from parts not made or approved by AquaTech Pressmain The individual manufacturers own policies for dealing with defects w...

Page 15: ...82 C or boiler power up to 1000kW READ GENERAL SAFETY INFORMATION 0 0 WARNINGS 0 1 and CAUTIONS 0 2 0 3 0 4 2 3 1 ADDITIONAL CAUTIONS 2 3 1 1 Isolate the pressurisation unit from the system before dra...

Page 16: ...tted their sequence is automatically rotated either by starting the pump that has been idle the longest and or by timed operation dependent upon unit type Indicator lights where fitted on the fascia s...

Page 17: ...is value High pressure delay time before alarm is initiated Duty delay to delay duty pump starting to circulator pump pressure dips Support delay to delay support pump starting in normal operation pre...

Page 18: ...ched off for a long period a turbine pump where fitted may have seized Switch off unit insert flat blade screwdriver into slot on end of motor shaft and rotate pump until free Replace fuse with T1Ax20...

Page 19: ...d signal present Check electrical supply is within tolerance or missing phase Pump seized motor failed Motor thermistor overheated No water in feed tank water level below supply tank low water alarm p...

Page 20: ...ocedure shown below to avoid damaging rupture of the internal diaphragm and consequences of E g High and or low pressure problems unstable pump operation 2 To adjust air charge pressure 4 0Bar isolate...

Page 21: ...s specialist fields are Pressure booster equipment and sealed systems for heating and chilled water distribution systems Regular servicing of any plant for essential services is vital because wear and...

Page 22: ...A AquaTech Pressmain AGM House London Rd Copford Colchester Essex CO6 1GT UK Telephone 01206 215121 OPERATING PARAMETERS SERIAL No MODEL MP THE SERIAL MODEL NUMBERS MUST BE QUOTED WHEN REQUESTING ASS...

Reviews: