2.3.4  ENHANCED “-E” CONTROLLER OPERATION 

 
The control is by AquaTech-Pressmain “2020Plus” Microprocessor, with a 2-line by 20 or 24 character display on the 
control panel, showing the current system pressure and status. 
 
 

When switched on the display shows, 
then self-checks, flashing all LED lights on keypad, 
 

 

and identifies configuration for pump operation 
(e.g. “MP” pressurisation unit) 
 
 

followed by the system status and pressure 

 
 
 
For “normal” operation, all Hand/Off/Auto switches should be left in “Auto”, all isolating valves should be left open, all 

hydraulic accumulator/expansion vessel isolating valves should be left open, and drain cock/valves should be left 

closed. Should it be necessary to have a situation that is not “normal” operation, then we would strongly recommend 

attendance to site by our trained/authorised service personnel. Please contact AquaTech-Pressmain for more details. 
 

Pump Operation 

Sealed system pressurisation unit; All Models:

 

The pressurisation unit automatically maintains a minimum set pressure, the “Cold Fill” pressure, in a heating or chilled 
system by transferring make-up liquid from a breaktank, into the system. When the system pressure falls below the 
required level the Duty pump automatically refills the system until the pressure is restored. If the Duty Pump fails to 
maintain the required pressure the Support pump (where fitted) will operate in addition to the Duty Pump. 
 

Duty Pump Rotation.

 To spread the wear evenly across both pumps (where fitted), their sequence is 

automatically rotated either by starting the pump that has been idle the longest and/or by timed operation (dependent 
upon unit type). 

Indicator lights (where fitted) on the fascia show which pump is running. 
 

Automatic Restart (when “manual restart” is set to “not enabled” on 2020 Plus controller) 

If there is an interruption to the electrical supply the unit will automatically restart on restoration of the supply. 
Pumps will restart at timed intervals. 

 
Manual Restart (when set to “enabled” on 2020 Plus controller) 

If there is an interruption to the electrical supply, or there is a low water level condition, the unit will need to be 
manually reset on restoration of the supply, or low water level condition, by pressing the “Reset Alarm” key. Pumps 
will then restart at timed intervals. 

 

Pressure setting. 

The pumpset is set at the default 'duty/cold fill' pressure at the factory. If necessary, the 

pressure will be adjusted at commissioning to suit local conditions. 

 

To view the parameters (Enhanced controller only) 

Press <SET/VIEW> on the keypad. Then, press the same key 

4

 more times. 

Press the <UP> (7) key, to view the next parameter. 
Page through the parameters by using the <UP> (7) and <DOWN> (8) keys to view: 
Various parameters will be displayed dependent upon unit type. The main parameters that customers are interested in 

are shown on the following page. 
 
Date and Time (24 hour clock) 

not password protected to allow 
on site adjustment. 

 

Fault Log (last 30 faults) 

press <view> to see log followed 
by <up> (7) or <down> (8) to view 
log. 

press <enter> to return 
  

 

Manual Restart upon power failure 

not password protected to 

AQUATECH 2020Plus V5.01 
PRESSMAIN 

MP 

 

Time 
14/01/15…….22:40:15 

Fault Log 
  

PRESSURE SYSTEM IS  O.K. 
Pressure  …………   bar 

Manual Restart 
            Not enabled 

Summary of Contents for MINIPACK MP Series

Page 1: ...ESSURISATION UNITS WITH MICROPROCESSOR CONTROLS MODELS MP31 32 71 72 ISSUE 6 30 01 2019 Head Office AGM House London Rd Copford Colchester Essex CO6 1GT UK Tel 01206 215121 Email aftersales agm plc co...

Page 2: ...e manual supplied with the unit Examples of units manufactured by Aquatech Pressmain are shown below Please note it is also possible for the pump controls tanks to have been sold as a separate item in...

Page 3: ...NG MiniPack Standard Basic B or Enhanced E UNITS 12 1 3 6 ELECTRICAL 12 2 USER INSTRUCTIONS 14 2 1 CUSTOMER ASSURANCE 14 2 2 COMMISSIONING 15 2 3 OPERATING INSTRUCTIONS 15 2 3 1 ADDITIONAL CAUTIONS 15...

Page 4: ...PSSR and the Owner User should be made aware of their responsibility for this see section 3 Servicing Failure to install operate use maintain the equipment as recommended below could cause damage to...

Page 5: ...or property 0 1 12 Pump motors with lifting eyes the lifting eyes are only suitable for lifting motors NOT the entire pump assembly This could cause injury to people or property 0 1 13 Ensure the bas...

Page 6: ...ssure safety device into the system with due respect to the suction pressure present on the pumpset the pump closed valve pressure stated on the pump the maximum working pressure stated on any of the...

Page 7: ...3 8 Ensure pumpset has an adequate water supply at all times to prevent dry running causing pump seal damage and water leakage 0 3 9 Do no attempt to start pumps without liquid in volutes pumps must b...

Page 8: ...the suction side of the circulating pump but not within any influences from the circulating pump and for a heating system at the point of lowest temperature i e before the boiler If the equipment is...

Page 9: ...stem Connection i The unit must be connected with any expansion vessels and cooling vessels to the underside of the return header on the suction side of the circulating pumps and boiler chiller see Lo...

Page 10: ...mm Float Valve 15mm Incoming Mains Supply Microprocessor Controller System connection on suction side of Circulating Pumps Sytem filling device e g quick fill loop check local water regulations Drain...

Page 11: ...r charge filling valve top and the diaphragm bottom on 70 C vessels top on 100 C vessels are accessible for future maintenance All vessels must have isolating and drain off valves fitted to enable the...

Page 12: ...et terminal on pcb card in series with the boiler chiller control circuits so that in the event of a fault condition occurring the boiler chillers shut down and remain inoperative until the fault cond...

Page 13: ...6a Typical standard B controller Wiring Diagram Fig 1 6b Typical Boiler wiring by others PCB1 PCB2 PCB3 O Keypad 2020Plus controller Pump 2 Auto Off Hand Pump 1 Auto Off Hand Display Pressure fault n...

Page 14: ...urance does not apply to those items not supplied by us or to defects arising from parts not made or approved by AquaTech Pressmain The individual manufacturers own policies for dealing with defects w...

Page 15: ...82 C or boiler power up to 1000kW READ GENERAL SAFETY INFORMATION 0 0 WARNINGS 0 1 and CAUTIONS 0 2 0 3 0 4 2 3 1 ADDITIONAL CAUTIONS 2 3 1 1 Isolate the pressurisation unit from the system before dra...

Page 16: ...tted their sequence is automatically rotated either by starting the pump that has been idle the longest and or by timed operation dependent upon unit type Indicator lights where fitted on the fascia s...

Page 17: ...is value High pressure delay time before alarm is initiated Duty delay to delay duty pump starting to circulator pump pressure dips Support delay to delay support pump starting in normal operation pre...

Page 18: ...ched off for a long period a turbine pump where fitted may have seized Switch off unit insert flat blade screwdriver into slot on end of motor shaft and rotate pump until free Replace fuse with T1Ax20...

Page 19: ...d signal present Check electrical supply is within tolerance or missing phase Pump seized motor failed Motor thermistor overheated No water in feed tank water level below supply tank low water alarm p...

Page 20: ...ocedure shown below to avoid damaging rupture of the internal diaphragm and consequences of E g High and or low pressure problems unstable pump operation 2 To adjust air charge pressure 4 0Bar isolate...

Page 21: ...s specialist fields are Pressure booster equipment and sealed systems for heating and chilled water distribution systems Regular servicing of any plant for essential services is vital because wear and...

Page 22: ...A AquaTech Pressmain AGM House London Rd Copford Colchester Essex CO6 1GT UK Telephone 01206 215121 OPERATING PARAMETERS SERIAL No MODEL MP THE SERIAL MODEL NUMBERS MUST BE QUOTED WHEN REQUESTING ASS...

Reviews: