![AQUATECH MINIPACK MP Series Manual Download Page 17](http://html1.mh-extra.com/html/aquatech/minipack-mp-series/minipack-mp-series_manual_2961177017.webp)
MINIPACK
X:/Aquatech-Pressmain Instruction manuals/current/MINIPACK
17
or low water level condition
allow user to enable/disable
Pumps 1 & 2 hours run time
Time elapsed since last service
service reminder after 6 months
Total run time (power up time)
not resetable
Enable service call
enable/disable service reminder
Low pressure alarm
low pressure alarm. Note: low
pressure approach warning is 0.2
bar more than this value
Low pressure delay
time before alarm is initiated.
High pressure
high pressure alarm. Note: high
pressure approach warning is 0.2
bar below this value
High pressure delay
time before alarm is initiated.
Duty delay
to delay duty pump starting to
circulator pump pressure dips
Support delay
to delay support pump starting in
normal operation preventing
electrical/pressure dips/surges
Starts in 12 minutes
sets frequency of pump starts
warning (system leak detection)
Duty pressure (cold fill)
duty pump cut-out/cold fill
pressure. All other pumps are
derived from this value.
Minimum run time
for each pump
Pump x run time
000123.4 Hours
Since last service
000987.6 Hours
Total run time
005000.0 Hours
Enable service call
Enabled
Low pressure
0.8 Bar
Low p delay
10 sec
High pressure
3.0 Bar
High p delay
10 sec
Duty delay
0 sec
Support delay
10 sec
Starts/12 mns
8
Duty pressure
1.6 bar
Min run time
3 sec