AquaStar 125B LPS Installation And Operating Instructions Manual Download Page 7

7

WARNING: Failure TO INCREASE THE VENT SIZE TO
SIX INCHES AND/or assure that the manifold pressure is
set to proper value listed for applications at high altitudes
will cause unsafe venting, asphyxiation, and will void IAS
Certification.

GAS CONNECTIONS and Gas Regulator

Before connecting the gas supply, check the rating plate
on the right side of the front cover to be sure that the heater
is rated for the same gas to which it will be connected.
In the United States: The installation must conform with
local codes or, in the absence of local codes, the National
Fuel Gas Code ANSI Z223.1/NFPA 54.
In Canada: The Installation should conform with CGA B149
INSTALLATION CODES and /or local installation codes.
NOTE: The Aquastar 125 B”S” is supplied with a gas
pressure regulator that must be installed on the heater
before attaching the gas supply line. See figure 4.
Failure to install the  gas regulator as shown in figure
4 will be a violation of IAS certification of the unit.
The regulator supplied with the heater is preset for
the gas shown on the rating plate to the correct
pressure. It is an appliance level regulator designed
for (low inlet) pressure (less than 1/2 Psig or 15” W.C.)
DO NOT connect to an unregulated or high pressure
propane line or to a high pressure commercial natural
gas line.

GAS LINE SIZE

It is strongly recommended that the natural gas pipe line
be 3/4" for the entire distance. If the maximum length is
above 40 feet, use 1" line. Flexible tubing is NOT
recommended, but if it is to be used, oversize it. With LP
gas installation, the recommended sizes are 5/8" up to a
maximum of 20 feet distance, 3/4" up to 50 ft distance
and 7/8" up to 100 feet.
National Fuel Gas Code requires that a sediment trap (drip
leg) be installed on gas appliances not so equipped. The
drip leg must be accessible and not subject to freezing
conditions. Install in accordance with the recommendations
of the serving gas supplier.

WARNING: The heater must be disconnected from the
gas supply piping system during any pressure testing of
that system at test pressures in excess of 0.5 psig.
The water heater must be isolated from the gas supply
piping system by closing the manual shutoff valve during
any pressure testing of the gas supply piping system at
test pressures equal to or less than 0.5 psig.
The water heater, including the pressure regulator provided
with it, must not be operated at gas supply pressures in
excess of 0.5 psig. If overpressure has occurred, such as
through improper testing of the gas lines or emergency
malfunction of the supply system, the gas valve and
regulator must be checked for safe operation. Make sure
that the regulator vent is protected against blockage.  Vent
blockage could occur during ice storms.
When your connections are made, check for gas leaks at
all joints (not just the ones you made). Apply some soapy
water to all gas fittings and gas valve. Soap bubbles are
a sign of a leak.
NOTE:
 Do not apply soap solution to pilot filter screen or
pilot orifice area. If you have a leak, shut off the gas. After
verifying that required gaskets are in place, tighten
appropriate fittings to stop leak. Turn the gas on and check
again with a soapy solution. Never test for gas leaks
using a match or flame
.

WATER CONNECTIONS

Although water piping throughout your structure may be
other than copper, we recommend that copper piping be
used for at least three feet before and after the heater
(follow local codes if more stringent). Keep water inlet pipe
to no less than 1/2 inch diameter to allow the full flow
capacity. Remember that water pressure must be  sufficient
to activate the heater when drawing hot water from the
top floor. If the hot and cold connections to the heater are
reversed, the heater will not function. The AquaStar
125B”S” is provided with two water connection adapters
that must be connected to the inlet and outlet fittings of
the water valve as shown in Fig 5. These fittings seal to
the water valve by means of a union connection with a
washer type gasket at the joint. No pipe dope or thread
tape is to be used at these joints. Be certain there are no
loose particles or dirt in the piping. Blow out or flush the
lines before connecting to the AquaStar. A ball valve should
be installed on the cold water feed line to facilitate servicing
the heater.

Fig. 4 - Installation of Gas Pressure Regulator

The pressure regulator provided with the heater is adjusted
to deliver the proper gas pressure (as indicated on the
rating plate and in the manual for altitude up to 2000 feet
(660 meters) above sea level. On appliances being
installed above 2000 ft (660 meters) elevation, the inlet
gas pressure should be set at installation to the value
shown below.
NOTE: The gas pressures specified below refer to
pressures taken at the test pressure nipple on the gas
inlet pipe
  just above the regulator (See Fig 4).  These
readings should be taken while the heater is operating
at full input — i.e. maximum water flow with the
temperature 
 dial selector turned all the way clockwise.

MAXIMUM INLET GAS FLOW PRESSURE SETTING

GAS INLET PIPE

PRESSURE TAP

PRESSURE REGULATOR

Altitude

Natural Gas

Liquid Propane

inches W.C:

inches W.C:

0' - 2.000 ft

5.7"

10.5"

2.000 ft - 4.500 ft

4.6"

8.4"

Above 4.500 ft consult your local gas supplier.

Summary of Contents for 125B LPS

Page 1: ...pliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phon...

Page 2: ...gy efficiency Automatic Thermostatic Control for steady hot water temperature Input BTU s modulate to zero to prevent overheating of water from pre heat source Safety thermocouple at pilot burner Auto...

Page 3: ...S FROM COMBUSTIBLE AND NON COMBUSTIBLE MATERIALS FOR ALCOVE INSTALLATIONS FRONT VIEW SIDE VIEW AQUASTAR MODELS 125B 125BL 125BS 125X MODEL 125B 125B LOW PRESSURE 125B SOLAR 125X TOP A 12 FRONT B OPEN...

Page 4: ...anada The Installation should conform with CGA B149 1 2 INSTALLATION CODES and or local installation codes 2 Carefully plan where you install the heater Correct combustion air supply and flue pipe ins...

Page 5: ...the building 2000 Btu hr if all air is taken from the outside by horizontal ducts 4000 Btu hr if all air is taken from the outside by direct openings or vertical ducts Louvers grills and screens have...

Page 6: ...vent pipe connectors require a 6 inch clearance from combustibles National Fuel Gas Code specifies double wall Type B vent pipe be used in cold climates and for gas vents running through attics We co...

Page 7: ...ency malfunction of the supply system the gas valve and regulator must be checked for safe operation Make sure that the regulator vent is protected against blockage Vent blockage could occur during ic...

Page 8: ...adily accessible for servicing or replacement and be mounted as close to the water heater as possible See Fig 6 To install the PRV a suitable fitting connected to an extension on a T fitting can be sw...

Page 9: ...me and should resemble the diagram in Fig 8 If the flame is yellow or if the pilot knob has to remain depressed for a long time in order to keep the pilot lighted the pilot burner and or the pilot bur...

Page 10: ...coils should be flushed with a descaling solution Consult your dealer or Controlled Energy for instructions pulled off washed and blown out The pilot orifice has likewise to be cleaned or exchanged C...

Page 11: ...er valve assembly components need to be replaced immediately Note Water valve for model 125B S is part 8707002380 for both LP and NG models Contact service person to clean water valve or replace if co...

Page 12: ...at the tap the lower hot water pressure may be overpowered by a much higher cold water pressure which may cause the Aquastar burners to shut down Make sure faucet aerators or shower heads are free of...

Page 13: ...7 9 1 Heat exchanger 2 Pilot assembly 3 Burner manifold gas pressure test nipple 4 Main gas burner 5 Pilot gas tubing 6 Gas valve 7 Piezo igniter 8 Location of pressure tap screw 9 Water valve 10 Gas...

Page 14: ...14 AQ 125 BS Fig 11 INTERIOR COMPONENTS DIAGRAM AND PARTS LIST...

Page 15: ...lot Tube 8 700 707 316 15 Thermocouple 8 747 202 083 16 Burner assembly washer 8 710 103 060 17 Gas valve LP 8 707 011 467 Gas valve NG 8 707 011 469 18 Gas supply pipe 8 700 705 464 19 Electromagnet...

Page 16: ...ight Minimum Diameter Minimum Height 5 inches 6 feet NOTE Vent size must not be restricted Installation must comply with national fuel gas code venting requirements for a 117 000 Btu Category I applia...

Reviews: