BURNERS DO NOT IGNITE WHEN HOT WATER IS
TURNED ON

1. Pilot is not on.
Light the pilot. See lighting instructions.

2. Gas valve button not positioned on Burner Position
Be sure once the  pilot flame is on, that after a 15 to 20
second wait, the main burner button (       ) is pushed all
the way in.

3. Cold incoming water connection made to wrong

side of heater

Make sure cold water inlet connection is on the right side
of heater when you are facing the heater.

4.

Water flow rate at hot water tap is too low.

Note: The AquaStar models 125B”S” require 0.5 gallon
per minute flow to activate the burners. This is a flow which
would fill a quart jar in 30 seconds.

5. Cold water inlet filter on heater is dirty.
Remove filter and clean. This screen filter is located at
the inlet side of the brass water valve (fig. 11, #35). Check
and clean faucet aerators too.

6. Crossover in household plumbing
The AquaStar burner activates when there is sufficient
water pressure drop in the AquaStar water valve assem-
bly — ie. when a hot water faucet is opened. If there is a
crossover in the plumbing, the necessary pressure drop
in the AquaStar will be insufficient, or totally eliminated. A
plumbing crossover can be caused by a bad washer at a
single lever faucet or incorrect plumbing or a mixing valve
in the line, etc. which permits hot and cold water to mix in
the plumbing. The crossover will create a back pressure
in the system preventing the pressure drop in the Aquastar
— i.e. cold water is entering the water heater from both
sides and the burners will not come on. To confirm there
is no crossover in the plumbing, shut off the cold water
supply to the AquaStar. Open your hot water taps. There
should not be any water flowing. If there is water flowing,
there is a crossover in the plumbing. This is a plumbing
problem, not an Aquastar problem. Please contact your
plumber.

7. Water valve parts may be dirty or components

damaged.

Water valve and component parts must be totally free of
dirt. First check that the venturi is free os dirt particles. In
hard water areas, mineral deposits can eventually (3 to 5
years in hard water areas) corrode the water valve parts
to a point where they will need replacing. 

Any sign of mois-

ture or corrosion at the joint of the water valve and the gas
valve is a sign that the water valve assembly components
need to be replaced immediately.
Note: Water valve for model 125B”S” is part # 8707002380
for both LP and NG models. (Contact service person to
clean water valve or replace if corrosion is present).

PILOT LIGHT GOES OUT DURING OR IMMEDIATELY
AFTER HOT WATER HAS BEEN USED

1. Gas pressure too low
Very low gas pressure may be caused by low delivered
gas pressure, a jammed gas regulator or undersized gas
lines. If the gas lines are undersized, there may still be the
specified static gas line pressure. However when the water
valve opens,and gas enters the burners, the pressure could
drop sharply, causing the pilot flame to go out. Have a gas
technician confirm the gas pressure both static and at
maximum Btu output. Specifications for your heater are
on page 2.

2. Pilot may be dirty or weak
See Page 9 for instructions on pilot maintenance.

3. Burners are not shutting down immediately when

hot water is turned off

Note: If burners don’t shut down immediately when the
hot water is turned off, the heater will overheat and the
ECO will shut-off the gas. Rebuild the water valve assembly
using the repair kit from CEC (part #8 703 406 204).

WATER IS TOO HOT

1Water flow rate is too low.
Increase the flow rate.

2. Not enough cold water mixing at faucet
Contact your plumber to adjust mixing valves on faucets.

WATER IS NOT HOT ENOUGH

1. Water flow rate is too high.

Decrease the flow rate.

2. Btu input is too low due to insufficient gas pressure

It is extremely important for a tankless
instantaneous water heater to have the right size
gas line to obtain the correct gas pressure

See specifications on page 2. Unlike storage tank water
heaters, the burners of a tankless water heater must be
very powerful to heat water instantaneously since they do
this only at the time hot water is actually being used. It is
therefore  imperative that the gas pressure requirement
be met exactly.  Insufficient gas pressure will directly affect
the water temperature at the time of usage. See page 2
for correct gas pressure settings.

3. Thermostat calibration is incorrect or thermostat

is defective.

Contact your service person or call CEC.

4. Btu input is too low due to insufficient gas supply
Make sure your main gas line is fully opened. If using LP
gas, be sure that the size of the propane tank is adequate
to supply the required gas pressure.

5. Cold water is mixing with the hot water between

the AquaStar and the outlet

Compare water temperature at outlet of the AquaStar (hold

Summary of Contents for 125B LPS

Page 1: ...pliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phon...

Page 2: ...gy efficiency Automatic Thermostatic Control for steady hot water temperature Input BTU s modulate to zero to prevent overheating of water from pre heat source Safety thermocouple at pilot burner Auto...

Page 3: ...S FROM COMBUSTIBLE AND NON COMBUSTIBLE MATERIALS FOR ALCOVE INSTALLATIONS FRONT VIEW SIDE VIEW AQUASTAR MODELS 125B 125BL 125BS 125X MODEL 125B 125B LOW PRESSURE 125B SOLAR 125X TOP A 12 FRONT B OPEN...

Page 4: ...anada The Installation should conform with CGA B149 1 2 INSTALLATION CODES and or local installation codes 2 Carefully plan where you install the heater Correct combustion air supply and flue pipe ins...

Page 5: ...the building 2000 Btu hr if all air is taken from the outside by horizontal ducts 4000 Btu hr if all air is taken from the outside by direct openings or vertical ducts Louvers grills and screens have...

Page 6: ...vent pipe connectors require a 6 inch clearance from combustibles National Fuel Gas Code specifies double wall Type B vent pipe be used in cold climates and for gas vents running through attics We co...

Page 7: ...ency malfunction of the supply system the gas valve and regulator must be checked for safe operation Make sure that the regulator vent is protected against blockage Vent blockage could occur during ic...

Page 8: ...adily accessible for servicing or replacement and be mounted as close to the water heater as possible See Fig 6 To install the PRV a suitable fitting connected to an extension on a T fitting can be sw...

Page 9: ...me and should resemble the diagram in Fig 8 If the flame is yellow or if the pilot knob has to remain depressed for a long time in order to keep the pilot lighted the pilot burner and or the pilot bur...

Page 10: ...coils should be flushed with a descaling solution Consult your dealer or Controlled Energy for instructions pulled off washed and blown out The pilot orifice has likewise to be cleaned or exchanged C...

Page 11: ...er valve assembly components need to be replaced immediately Note Water valve for model 125B S is part 8707002380 for both LP and NG models Contact service person to clean water valve or replace if co...

Page 12: ...at the tap the lower hot water pressure may be overpowered by a much higher cold water pressure which may cause the Aquastar burners to shut down Make sure faucet aerators or shower heads are free of...

Page 13: ...7 9 1 Heat exchanger 2 Pilot assembly 3 Burner manifold gas pressure test nipple 4 Main gas burner 5 Pilot gas tubing 6 Gas valve 7 Piezo igniter 8 Location of pressure tap screw 9 Water valve 10 Gas...

Page 14: ...14 AQ 125 BS Fig 11 INTERIOR COMPONENTS DIAGRAM AND PARTS LIST...

Page 15: ...lot Tube 8 700 707 316 15 Thermocouple 8 747 202 083 16 Burner assembly washer 8 710 103 060 17 Gas valve LP 8 707 011 467 Gas valve NG 8 707 011 469 18 Gas supply pipe 8 700 705 464 19 Electromagnet...

Page 16: ...ight Minimum Diameter Minimum Height 5 inches 6 feet NOTE Vent size must not be restricted Installation must comply with national fuel gas code venting requirements for a 117 000 Btu Category I applia...

Reviews: