Disinfection
Super
Chlorination
Not
Fitted Disinfection
Minimum ORP
500
600
600
Maximum ORP
850
900
850
Default Value
550
850
750
$)3).&%#4)/.
$!93!434!24
$52HRS3%4M6
).47KS
Table 4.
Set Disinfection Screen
Refer to the Table 4. below. Allows the user to utilise a function of
the controller that applies a boost disinfection (superchlorination)
by means of raising the ORP control set point and dosing oxidising
biocide according to the program set. This program is for a time
interval in hours on any one day of the week, on any frequency of
weeks. The program allows the user to enter the day, start time,
duration, frequency interval, and the ORP control set point.
DAY: [OFF]
Options: (day of disinfection)
Day/OFF.
Use arrow keys to cycle these
selections.
START: [0]
Options: (disinfection start ) 24
hr timer.
Use arrow keys to cycle these
selections.
DUR: [0]
Options: (Disinfection duration)
Value between 1 and 24 hrs.
Use arrow keys to cycle these
selections.
INT: [0]
Options: (Disinfection frequency)
Value in the range of 1 to 12
weeks.
Use arrow keys to cycle these
selections.
Disinfection operates on the next available SET day after the
program has been entered. If Disinfection is set to operate at the
current date and time it will occur on the next available SET day
unless a one week interval is set in which case disinfection will
begin immediately.
SET: [550]
Options: (ORP control point) In the range of 500 to 850 mV.
Use arrow keys to cycle these selections
Warning default: Min 350/ Max 850. The controller will issue a
warning when these values are exceeded.