19
Set Inhibitor Screen
Allows the user to set inhibitor options.
PUMP CAP: [1.00]
Options: (Pump capacity in lts/hr)
Value between 0.01 and 20.0.
Use arrow keys to cycle these selections.
DOSE: [1.00]
Options: (Preferred dose rate)
Set a value in the range of 10 mls/hr (240 mls/day) to 20.0 lts/hr.
Use arrow keys to cycle these selections.
MODE: [BLEED]
Options: BLEED/CONT/FLOW/OFF
Use this function to give dose states that meet your specific needs.
Warning default:
Dose greater than 25% of pump capacity. The
controller will issue a warning when this value is exceeded.
[WM] option allows dosing based on impulse from external water
meter. The Makeup in WUM needs to be enabled for this option to
operate.
Value between 0.01 and 20.0.
PPM: [10]
(Parts per million)
Use arrow keys to cycle these selections.
Set Water Usage Meter (WUM) Screen
Allows user to set amount of water per impluse.
Use the ENT key to switch between the items. Then use the
arrow keys to cycle these selections.
Value for Makeup/Bleed/Bkwash can be set from Disabled to
1000 ltr per Pulse.
Water Meter Cable Connection
Water Meter for Makeup line is to be connected to mainboard
through the terminals for WM & Gnd.
Water Meter for Bleed line is to be connected to WUM board
through terminal WM1.
Water Meter for Backwash line is to be connected to WUM
board through terminal WM2.
2
System Configuration
2
System Configuration
Eg,
1 Plse = 0.25l would be used if
water meter provides 4 pulses
per litre.
1 Plse = 10.0l would indicate 1
pulse per 10 litres.