background image

1 2 |

P a g e

System Disinfection

With a new installation, or any time the UV system is shut down for service, without power, or is 

inoperative for any other reason, the lines in the home or facility could be contaminated. Use the 

following steps to fully disinfect the lines throughout the entire home or facility.

Step 1:  Check for and remove any “dead ends” in the lines throughout the home as these can 

harbor bacteria. Plug in the UV system and wait until it is ready for operation.

Step 2:  Remove the filter cartridge from the last sump and fill it with 1-2 cups of household 

bleach (most are 5.25% chlorine). Replace the sump and slowly turn on the water supply.

Step 3:  At a water outlet, run the water until bleach can be smelled. Repeat this for all faucets, 

toilets, shower heads, refrigerators, outdoor taps, the washing machine, dishwasher, etc. at the 

home or facility. Once finished, wait a minumum of 30 minutes before continuing.

Step 4:  Reinstall the filter cartridge into the sump and flush the chlorine solution by opening 

all faucets until chlorine can no longer be detected. Your home has now been completely dis-

infected with your AQUA FLO UV system ready to inactivate any microorganisms that enter the 

home.

Cleaning the Quartz Sleeve

Depending on the water quality, the quartz sleeve may require periodic cleaning. At a minimum, 

the quartz sleeve should be cleaned on an annual basis. The following steps outline a basic clean-

ing procedure.

Step 1:  If a by-pass assembly is installed, shut the inlet valve off to prevent water flow through 

the system. Otherwise, turn off main water inlet valve (and/or turn off the water pump).

Step 2:  Disconnect power cord of UV system from electrical outlet.

Step 3:  Release water pressure by opening a downstream faucet and then close the outlet 

shut-off valve (if any). If there is no outlet shut-off valve, expect water to drain from the system 

as the head pressure in the system will cause the water to flow back down.

Step 4:  Remove the captive ground screw from the ground lug on the UV reactor.

Step 5:  Remove the lamp connector from the reactor (gland nut) by pushing the lamp connec-

tor in and turning it ¼ turn counter-clockwise.  Disconnect the lamp connector from the lamp.  

CAUTION: the lamp may be hot!

Step 6:  Being careful to touch only the ceramic ends, remove the lamp out of the reactor.

Step 7:  Unscrew the gland nut from the reactor exposing the end of the quartz sleeve.

Step 8:  Remove the quartz sleeve and o-ring by gently twisting and pulling the quartz sleeve.

Step 9:  Using a soft, lint-free cloth or towel wipe the sleeve down using a commercial scale 

cleaner (i.e. CLR® or LIME-A-WAY®). This removes scaling or iron deposits that may be on the 

outside of the quartz sleeve. Be careful not to get any moisture or liquids inside of the sleeve.

Step 10:  Dry the sleeve with separate cloth. 

Summary of Contents for GEN4 Series

Page 1: ...m GEN4 3 GEN5 3 GEN6 3 3 gpm GENH4 10 GENH5 10 GENH6 10 10 gpm GEN4 6 GEN5 6 GEN6 6 6 gpm GENH4 15 GENH5 15 GENH6 15 15 gpm GEN4 10 GEN5 10 GEN6 10 11 gpm GENH4 25 GENH5 25 GENH6 25 25 gpm GEN4 15 GEN...

Page 2: ...pply with a UV system gives you reassurance that your family will have access to safe drinking water throughout your entire home with no chance of microbiological contamination This is chemical free p...

Page 3: ...14 GEN5 GEN6 Controllers 14 GEN5 GEN6Power up Sequence 14 GEN5 Operational Screens 15 GEN6 Operational Screens 16 Lamp Countdown Sequence 16 Lamp Replacement GEN4 systems 17 Lamp Replacement GEN5 GEN...

Page 4: ...vice instructions if required 7 Do not use this system for any purpose other than what it was intended for Misuse of this system could potentially cause harm to the user or others 8 Your system is int...

Page 5: ...required will depend on parameters being treated Hardness 7 gpg 120 mg L if hardness level is 7 gpg or slightly below the quartz sleeve must be cleaned periodically in order to ensure effi cient UV p...

Page 6: ...EN6 SYSTEMS 40040066 North American 40040102 Complete Assembly 40040103 Teflon Plug 40040084 O Ring 40040104 Brass Nut 40040001 GEN6 2 3 6 10 15 series 40040002 GEN6 20 series GLAND NUT O RING SLEEVE...

Page 7: ...GENH5 GENH6 SYSTEMS 40040074 fits all units POWER CORD 40040102 Complete Assembly 40040103 Teflon Plug 40040084 O Ring 40040104 Brass Nut 40040003 Standard series 40040086 North American 40040079 4004...

Page 8: ...or tap near est the pressure system and measure the amount of water drawn off until the pump starts again Depending on the size of the container used it is acceptable to turn the faucet on and off to...

Page 9: ...as it will allow you to isolate the UV reactor This will allow for easier access in case maintenance is required See Figure 3 Step 3 Use the supplied fasteners to mount the UV reac tor to wood or dryw...

Page 10: ...SE NOTE DO NOT install a UV lamp inside the quartz sleeve without the sleeve spring in place Step 8 Install the UV sensor GEN6 systems only Align the flat portion so it faces the gland nut end and mat...

Page 11: ...you The key will plug into the lamp key port on the right side of the controller Figure 8 Step 13 Plug the lamp connector into the lamp Note the keying for proper alignment see Fig ure 7a 7b Insert th...

Page 12: ...eaning At a minimum the quartz sleeve should be cleaned on an annual basis The following steps outline a basic clean ing procedure Step 1 If a by pass assembly is installed shut the inlet valve off to...

Page 13: ...f the sensor port Step 6 Holding the sensor in your hand wipe the flat portion sensor face of the sensor with isopropyl alcohol using a clean lint free cloth Step 7 Replace sensor following step 9 fro...

Page 14: ...ed description of the system s performance in addition to pro viding any applicable fault messages and system diagnos tics The controllers used in both the GEN5 and GEN6 are identical The difference i...

Page 15: ...ts screens by pressing the button located on the front of the controller GEN6 Operational Screens On systems with the UV monitor the system will display the same screens as on the GEN5 except the UV I...

Page 16: ...ible chirp Past the zero day threshold the LED or display screen changes to solid red with a continuous buzzer GEN5 GEN6 GEN4 At any point during this sequence the audible chirp or alarm can be deferr...

Page 17: ...pired it must be replaced with the same part number as indicated on the Maintenance Parts screen or on the label on the reactor With the system powered down re move and discard the lamp key from the c...

Page 18: ...on the reactor or on the Maintenance parts screen Low UV Intensity Remove and clean the quartz sleeve and sensor Check water quality meets requirements on page 5 and add filtration as required Replac...

Page 19: ...to the system Replace any module that is not detected when plugged directly into the controller COMING SOON Warning After any hard alarm the home or facility should be disinfected Follow the steps un...

Page 20: ...of water to allow fresh cooler water to enter the system The TRV works without power and comes complete with 10 of drain line Order PN 40040098 for 1 2 ports PN 40040099 for 3 4 ports PN 40040100 for...

Page 21: ...6 4 20 mA MODULE Outputs a 4 20mA signal of the UV output to a remote device such as a data logger or computer Order PN 40040007 The WiFi module and accompanying IoT application allows you to connect...

Page 22: ...22 39 50 42 Power Watts 14 20 30 49 62 51 Replacement Lamp 40040113 40040013 40040014 40040015 40040017 40040016 Replacement Sleeve 40040039 40040040 40040043 40040045 40040047 40040046 Reactor Dimens...

Page 23: ...pm 11 lpm 19 lpm 30 lpm 0 2 m3 hr 0 5 m3 hr 0 6 m3 hr 1 1 m3 hr 1 8 m3 hr Port Size MNPT MNPT 1 MNPT 1 MNPT 1 MNPT Electrical 90 265V 50 60Hz 1 5A Max Lamp Power Watts 18 34 45 67 101 Power Watts 20 3...

Page 24: ...anature WaterGroup s closest Distribution Facility or authorized service depot Canature WaterGroup will not be liable for any costs of removal installation transportation or any other charges which ma...

Page 25: ...RANTIES NOT SET FORTH HEREIN ARE WAIVED AND DISCLAIMED INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR USE CANATURE WATERGROUP S LIABILITY UNDER THIS LIMITED WARRANTY IS...

Page 26: ...2 6 P a g e...

Page 27: ...2 7 P a g e...

Page 28: ...Canada Inc Canature WaterGroup U S A Inc 855 Park St Unit 1 9760 Mayflower Park Drive Regina SK S4N 6M1 Suite 110 CANADA Carmel IN 46032 USA Toll Free 877 288 9888 Toll Free 877 288 9888 PN 910094 Ve...

Reviews: